Seattle City Council Bills and Ordinances
Information modified on December 11, 2013; retrieved on July 4, 2026 11:18 AM
Ordinance 123393
Introduced as Council Bill 116918
Title | |
|---|---|
| AN ORDINANCE relating to the Seattle Fire Code, adopting as the Seattle Fire Code the 2009 edition of the International Fire Code with some exceptions, amending and adding various provisions to that code; amending Section 22.600.020 of the Seattle Municipal Code; and repealing Sections 2-426 of Ordinance 122491. | |
Description and Background | |
|---|---|
| Current Status: | Passed |
| Fiscal Note: | Fiscal Note to Council Bill No. 116918 |
| Index Terms: | BUILDING-CODES, FIRE-CODES, FIRE-PROTECTION, PUBLIC-REGULATIONS |
| References: | Clerk File 312312; Ordinance 124288 |
Legislative History | |
|---|---|
| Sponsor: | BURGESS | tr>
| Date Introduced: | July 12, 2010 |
| Committee Referral: | Public Safety and Education |
| City Council Action Date: | September 20, 2010 |
| City Council Action: | Passed |
| City Council Vote: | 8-0 (Excused: Clark) |
| Date Delivered to Mayor: | September 22, 2010 |
|
Date Signed by Mayor: (About the signature date) | September 28, 2010 |
| Date Filed with Clerk: | September 29, 2010 |
| Signed Copy: | PDF scan of Ordinance No. 123393 |
Text | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
ORDINANCE _________________ AN ORDINANCE relating to the Seattle Fire Code, adopting as the Seattle Fire Code the 2009 edition of the International Fire Code with some exceptions, amending and adding various provisions to that code; amending Section 22.600.020 of the Seattle Municipal Code; and repealing Sections 2-426 of Ordinance 122491. BE IT ORDAINED BY THE CITY OF SEATTLE AS FOLLOWS: Section 1. The 2009 International Fire Code, along with Appendixes B, D, E, F, G, H, I, and J, as published by the International Code Council, Inc., one copy of which is filed with the City Clerk in Clerk File 310922, is hereby adopted by reference. Section 2. Section 22.600.020 of the Seattle Municipal Code is amended as follows:
22.600.020 ((
(( The Seattle Fire Code consists of :
1. the ((
2. ((
3. (( Wherever in this ordinance there is a conflict between metric units of measurement and English units, the English units govern. Section 3. Chapter 1 of the 2009 International Fire Code is amended as follows: Part 1---GENERAL PROVISIONS SECTION 101 SCOPE AND GENERAL REQUIREMENTS
101.1 Title. These regulations shall be known as the Seattle Fire Code (( Throughout this code, where references are made to the International Building Code, International Residential Code, International Mechanical Code, International Fuel Gas Code, and the International Existing Building Code, those references mean those codes with Seattle amendments. Where NFPA 70 is referenced, it means the Seattle Electrical Code, which is the National Electrical Code with Seattle amendments. 101.2 Scope. This code establishes regulations affecting or relating to structures, processes, premises , motor vehicles, vessels, and safeguards regarding: 1. The hazard of fire and explosion arising from the storage, handling or use of structures, materials or devices; 2. Conditions hazardous to life, property or public welfare in the occupancy of structures or premises; 3. Fire hazards in the structure or on the premises from occupancy or operation; 4. Matters related to the construction, extension, repair, alteration or removal of fire suppression or alarm systems; and 5. Conditions affecting the safety of fire fighters and emergency responders during emergency operations.
101.2.1 Appendices. Provisions in the appendices ((
101.3 Intent. The purpose of this code is to establish the minimum requirements consistent with nationally recognized good practice for providing a reasonable level of life safety and property protection from the hazards of fire, explosion or dangerous
conditions in new and existing buildings, structures , (( This code is enacted as an exercise of the police power of the City of Seattle to protect the public peace, health, safety and welfare, and its provisions shall be liberally construed to accomplish these purposes. The express purpose of this code is to promote the health, safety and welfare of the general public, and not to create or otherwise establish or designate any particular class or group of persons who will or should be especially protected or benefitted by the terms of this code or ordinance. The specific intent of this code is to place the obligation of complying with its requirements upon the owners or occupiers of premises, buildings, motor vehicles, vessels, and structures within its scope. No provision or term used in this code is intended to impose any duty whatsoever upon the city, or any of its officers or employees, for whom the implementation or enforcement of this code is discretionary, not mandatory. * * * 101.6 Point of information or code interpretation. Text marked "Point of Information" or "Code Interpretation" in the Seattle Fire Code is for guidance only and does not have the force of law. SECTION 102 APPLICABILITY
102.1 Construction and design provisions. The construction and design provisions of this code (( 1. Structures, facilities and conditions arising after the adoption of this code. 2. Existing structures, facilities and conditions not legally in existence at the time of adoption of this code. A condition is not "legally in existence at the time of adoption of this code" unless the condition is in compliance with the building code and fire code of the City of Seattle in effect when the condition first arose, and the practice, process, materials used and storage configurations have not changed since the condition first arose. 3. Existing structures, facilities and conditions when required in Chapter 46. 4. Existing structures, facilities and conditions which, in the opinion of the fire code official, constitute a distinct hazard to life or property. * * *
102.5 Application of residential code. ((
1. Construction and design provisions: Provisions of this code pertaining to the exterior of the structure ((
2. Administrative, operational and maintenance provisions: All such provisions of this code (( * * *
102.7 Referenced codes and standards. The codes and standards referenced in this code shall be those that are listed in Chapter 4 7 (( * * *
103.2 Appointment. (( * * * 103.4 Liability. Nothing contained in this code is intended to, nor shall be construed to, create or form the basis for any liability on the part of the city, its officers, employees or agents, for any injury or damage resulting from the failure of the owner or occupier of premises, buildings, structures, motor vehicles or vessels, to comply with this code, or for any injury or damage caused by any act or omission on the part of the city by its officers, employees or agents in the course of implementing or enforcing this code. Any lawsuit brought against the city, or its officers, or employees because of acts or omissions in the implementation or enforcement of this code, or other pertinent laws, ordinances, or regulations implemented through the enforcement of this code or enforced by the fire code official, shall, as provided by Seattle Municipal Code chapter 4.64, be defended by the City, and any resulting judgment or settlement shall be assumed or paid by the City as provided by Chapter 4.64 and other relevant sections of the Seattle Municipal Code. Limited public funds are available for the implementation and enforcement of this code. The issuance of permits, reviews of permit applications, and inspections conducted pursuant to this code are spot checks designed to encourage compliance, and are not representations, guarantees, or assurances that permits, or work undertaken pursuant to issuance of permits, comply with any applicable codes.
((
SECTION 104 GENERAL AUTHORITY AND RESPONSIBILITIES 104.1 General. The fire code official is hereby authorized to enforce the provisions of this code and shall have the authority to render interpretations of this code, and to adopt policies, procedures, rules and regulations in order to carry out the provisions of this code and clarify the application of its provisions. Such interpretations, policies, procedures, rules and regulations shall be in compliance with the intent and purpose of this code and shall not have the effect of waiving requirements specifically provided for in this code. * * * 104.3 Right of entry. Whenever it is necessary to make an inspection to enforce the provisions of this code, or whenever the fire code official has reasonable cause to believe that there exists in a building or upon any premises any conditions or violations of this code which make the building or premises unsafe, dangerous or hazardous, the fire code official shall have the authority to enter the building or premises at all reasonable times to inspect or to perform the duties imposed upon the fire code official by this code. If such building or premises is occupied, the fire code official shall present credentials to the occupant and request entry. If such building or premises is unoccupied, the fire code official shall first make a reasonable effort to locate the owner or other person having charge or control of the building or premises and request entry. If entry is refused, the fire code official has recourse to every remedy provided by law to secure entry. 104.3.1 Owner consent. With the consent of the owner or occupier of a building, premises, motor vehicle, or vessel, or pursuant to a lawfully issued warrant, the fire code official may enter any building, premises, motor vehicle, or vessel at any reasonable time to inspect or to perform the duties authorized by this code.
104.3.(( 104.4 Identification. The fire code official shall carry proper identification when inspecting structures or premises in the performance of duties under this code.
104.5 Notices and orders. The fire code official is authorized to issue such notices or orders as are required to affect compliance with this code in accordance with Sections 109(( 104.6 Official records. The fire code official shall keep official records as required by Sections 104.6.1 through 104.6.4. Such official records shall be retained for not less than five years or for as long as the structure or activity to which such records relate remains in existence, unless otherwise provided by other laws or regulations. 104.6.1 Approvals. A record of approvals shall be maintained by the fire code official and shall be available for public inspection during business hours in accordance with applicable laws.
104.6.2 Inspections. The fire code official shall keep a record of (( 104.6.3 Fire records. The fire department shall keep a record of fires occurring within its jurisdiction and of facts concerning the same, including statistics as to the extent of such fires and the damage caused thereby, together with other information as required by the fire code official. 104.6.4 Administrative. Application for modification, alternative methods or materials and the final decision of the fire code official on any such application shall be in writing and shall be officially recorded in the permanent records of the fire code official.
104.7 Approved materials and equipment. All approved materials, equipment and devices (( * * * 104.11.2 Obstructing operations. No person shall obstruct the operations of the fire department in connection with extinguishment , or control or investigation of any fire, or actions relative to other emergencies, or disobey any lawful command of the fire chief or officer of the fire department in charge of the emergency, or any part thereof, or any lawful order of a police officer assisting the fire department. * * * 104.12 Motor vehicle impoundment and removal. The fire code official may order the owner or operator to remove, or may request that the Seattle Police Department impound a motor vehicle under the following conditions: 1. The motor vehicle poses an immediate hazard to public safety; or 2. The motor vehicle is transporting hazardous materials, and is left unattended on a residential street or within 500 feet (152 400 mm) of any building containing a Group A, R, E or I occupancy, including, but not limited to, any dwelling apartment, hotel, day care, school, hospital or health care facility; or 3. The motor vehicle contains or is carrying hazardous materials, or flammable or combustible liquids or gases, and is left unattended while transferring such materials, liquids or gases by means of hose line. The Seattle Police Department shall carry out motor vehicle impoundment requests of the fire code official in accordance with the authority of Chapter 11.30 of the Seattle Municipal Code and impoundment procedures of the Seattle Police Department. 104.13 Prohibited uses, sales devices. The fire code official may prohibit the use, display or sale of any device, material or object that is designed to be used in such a manner as to violate any provisions of this code, or if the use or sale of such constitutes a distinct hazard to life or property. Any materials shown by test to have a life hazard greater than that indicated and controlled by building code interior finish regulations or fire code decorative material regulations is either prohibited or shall be installed or used with such additional fire safety features as are necessary to substantially reduce the life hazard. 104.14 Standby fire personnel and fire watch personnel. The fire code official has the authority to require, at no cost to the jurisdiction, standby fire personnel and/or fire watch personnel if in the opinion of the fire code official potentially hazardous conditions or reductions in a life safety feature exist. The owner, agent, or lessee shall provide one or more qualified persons, as required and approved, to be on duty. Such standby fire personnel or fire watch personnel shall be subject to the fire code official's orders at all times and remain on duty during the times such places are open to the public, when such activity is being conducted, or as required by the fire code official. SECTION 105 PERMITS 105.1 General. Permits shall be in accordance with Sections 105.1.1 through 105.7.14.
105.1.1 Permits required. Permits required by this code shall be obtained from the fire code official prior to engaging in the activities or operations for which they are required . Permit fees, if any, ((
105.1.2 Types of permits. There shall be (( 1. Operational permit. An operational permit allows the applicant to conduct an operation or a business for which a permit is required by Section 105.6 for either: 1.1. A prescribed period. 1.2. Until renewed or revoked.
2. (( 3. Temporary permit. A temporary permit is valid for a period not to exceed 6 months and establishes fire safety controls for: 3.1. A time-limited activity not specifically regulated, but where regulatory safeguards are necessary because of unusual circumstances; or 3.2. Interim operation of a regulated activity at reduced scope and/or with temporary fire safeguards until permanent fire prevention features are provided. * * * 105.2 Application. Application for a permit required by this code shall be made to the fire code official in such form and detail as prescribed by the fire code official. Applications for permits shall be accompanied by such plans as prescribed by the fire code official.
105.2.1 Refusal to issue permit. If the application for a permit describes a n activity (( 105.2.2 Inspection authorized. Before a new operational permit is approved, the fire code official is authorized to inspect the receptacles, vehicles, buildings, devices, premises, storage spaces or areas to be used to determine compliance with this code or any operational constraints required.
((
105.2. 3 (( 105.3 Conditions of a permit. The fire code official may condition any permit, increasing or decreasing the scope of activity, and/or specifying fire safety provisions in addition to those established by this code, if the fire code official deems such conditions necessary to provide reasonable public safety. A permit shall constitute permission to maintain, store or handle materials; or to conduct processes which produce conditions hazardous to life or property; or to install equipment utilized in connection with such activities; or to install or modify any fire protection system or equipment or any other construction, equipment installation or modification in accordance with the provisions of this code where a permit is required by Section 105.6 or 105.7. Such permission shall not be construed as authority to violate, cancel or set aside any of the provisions of this code or other applicable regulations or laws of the jurisdiction.
105.3.1 Expiration. An operational permit shall remain in effect until reissued, renewed, or revoked or for such a period of time as specified in the permit. ((
((
105.3.(( 105.3.2 Point of Information Approval to occupy a building or structure is granted by the Department of Planning and Development through issuance of a Certificate of Occupancy or Temporary Certificate of Occupancy. A Fire Department recommendation to issue an occupancy certificate is conditioned upon applicable provisions of this code being met.
105.3.((
105.3.((
((
105.3.((
105.3.(( 105.3.7 Liability Insurance. If liability insurance is required by any section of this code as a permit condition or for a license, the applicant shall maintain continuously on file with the fire code official for the entire period of the licensed or permitted activity, evidence of "Commercial General Liability" ("CGL") insurance coverage with a minimum limit of liability of $2,000,000 combined single limit per occurrence bodily injury and property damage subject to no deductible. Such evidence of insurance coverage shall be provided on an Acord Certificate of Liability Insurance or equivalent ("Certificate") issued to "Seattle Fire Department, 301 2nd Ave S., Seattle, WA 98104." "The City of Seattle" shall be an additional insured under CGL insurance on a primary and non-contributory basis per ISO Endorsement CG 20 26 or equivalent and a copy of the actual CGL policy provision documenting this must be attached to the Certificate. The fire code official may increase or decrease the above-stated minimum limits of liability. The purpose of the requirement is to insure that members of the public and the City will be compensated for losses caused by bodily injury or property damage resulting from the negligent acts of the licensees, permittees, or their agents or employees. If the issuance of a license or permit is conditioned upon obtaining CGL insurance by the applicant for such permit, the policy shall be: 1. Issued by a company or companies authorized to do business as an insurer in Washington State pursuant to the provisions of RCW Title 48; 2. Issued for the purpose of complying with the conditions and requirements of Section 105 of the Seattle Fire Code; 3. Canceled only on at least 30 days prior written notice to the fire code official, except 10 days notice cancellation for nonpayment of premium is allowed, or as specified in RCW 48.18.290, if applicable; and 4. Subject to approval as to sufficiency and form by the City's Risk Management Division at the request of the fire code official. 105.4 Construction documents. Construction documents shall be in accordance with this section.
105.4.1 Submittals. Construction documents and supporting data shall be submitted in one (( Exception: The fire code official is authorized to waive the submission of construction documents and supporting data not required to be prepared by a registered design professional if it is found that the nature of the work applied for is such that review of construction documents is not necessary to obtain compliance with this code.
105.4.1.1 Examination of documents. The fire code official (( * * *
105.4.4.1 Phased approval. The fire code official is authorized to issue a permit for the construction of part of a structure, system or operation before the construction documents for the whole structure, system or operation have been submitted,
(( * * *
((
105.5 Revocation of permits and certificates . ((
105.5.1 Nonemergency revocations, suspensions and denials of renewals. In accordance with applicable law, the fire code official may revoke or suspend a permit or certificate or deny a request to renew any permit or certificate upon evidence submitted to the fire code official that conditions or circumstances have changed so that continued use of the permit or certificate would be unsafe or would violate this code. Such conditions or circumstances include, but are not limited to: 1. The permit has been used by a person other than the person to whom the permit was issued, 2. The permit has been used for a location other than that for which it was issued, 3. Any of the conditions or limitations in the permit or the code have been violated, 4. The permittee failed, refused or neglected to comply within the time provided with orders or notices duly served in accordance with the provisions of this code, 5. There has been a false statement or misrepresentation as to a material fact in the application or plans on which the permit or application was based, or 6. The permit was issued in error or in violation of any code, regulation or other law. 105.5.1.1 Notification. The permit or certificate holder shall be notified in writing no later than five business days prior to the revocation, suspension or denial of a request to renew such permit or certificate. 105.5.1.2 Requesting a hearing. The permit or certificate holder may request in writing a hearing before the fire code official for reconsideration of the decision to revoke, suspend or deny renewal. The request shall be filed with the fire code official by 5 o'clock p.m. of the second business day following service of the notice. 105.5.1.3 Hearing. The hearing, if one is requested, shall be held no later than one business day after receipt of the written request. 105.5.1.4 Final decision. The fire code official shall issue a final decision, in writing, sustaining, modifying or withdrawing the initial decision to revoke, suspend or deny a request to renew the permit or certificate no later than the next business day following such hearing. Further appeals shall be in accordance with Section 108 of this code. 105.5.2 Emergency Revocations, suspensions and denials of requests to renew. The fire code official may revoke, suspend or deny a request to renew a permit or certificate in emergency situations, without providing prior notice to the permit or certificate holder, if an imminent fire, lifesafety, or other hazard regulated by this code exists, and failure to take immediate action may cause imminent harm to humans, domestic animals, livestock, wildlife, or to the immediate or neighboring property, lands or premises. 105.5.2.1 Surrendering permits. If such emergency is found to exist and if the fire code official revokes, suspends, or refuses to renew a permit or certificate, all certificates and permits shall be surrendered to the fire code official or his/her authorized representative upon demand. 105.5.2.2 Suspending activities. The activities sanctioned by the suspended or revoked certificates or permits shall be suspended until the fire code official finds the emergency no longer exists and reinstates the permit or certificate. 105.5.2.3 Requesting an appeal. Persons whose permits or certificates have been revoked or suspended without notice may appeal the fire code official's action by filing a written notice of appeal to the fire code official by 5 o'clock p.m. of the next business day following such revocation, suspension or denial or a request to renew a permit or certificate. 105.5.2.4 Hearing. The hearing with the fire code official shall be no later than one business day from the receipt of such written appeal. 105.5.2.5 Final decision. The fire code official shall issue a final decision in writing, sustaining, modifying or withdrawing the initial decision to revoke, suspend or deny a request to renew the certificate or permit no later than the next business day following such hearing. 105.5.2.6 Further appeals. Further appeals shall be in accordance with Section 108 of this code. 105.6 Required operational and temporary permits. The fire code official is authorized to issue operational and/or temporary permits for the operations set forth in Sections 105.6.1 through 105.6.46. * * * 105.6.3 .1 Aviation facilities. An operational permit is required to use a Group H or Group S occupancy for aircraft servicing or repair and aircraft fuelservicing vehicles. Additional permits required by other sections of this code include, but are not limited to, hot work, hazardous materials and flammable or combustible finishes. 105.6.3.2 Battery systems. An operational permit is required to maintain and operate a stationary storage battery system having an electrolyte capacity of more than 50 gallons (189 L) for flooded lead-acid, nickel cadmium (Ni-Cd) and valve-regulated lead acid (VRLA), or 1,000 pounds (454 kg) for lithium-ion and lithium metal polymer, used for facility legally-required standby power, emergency power or uninterrupted power supplies. 105.6.3.3 Bonfires. An operational permit is required to ignite a bonfire. * * * 105.6.7 .1 Combustible fibers. An operational permit is required for the storage and handling of combustible fibers in quantities greater than 100 cubic feet (2.8 m3). Exception: A permit is not required for agricultural storage. 105.6.7.2 Combustible storage. An operational permit is required to store in any building or upon any premises in excess of 2,500 cubic feet (71m3 ) gross volume of combustible empty packing cases, boxes, barrels or similar containers, rubber tires, rubber, cork or similar combustible material. * * * 105.6.9 .1 Covered mall buildings. An operational permit is required for: 1. The placement of retail fixtures and displays, concession equipment, displays of highly combustible goods and similar items in the mall. 2. The display of liquidor gas-fired equipment in the mall. 3. The use of open-flame or flame-producing equipment in the mall. 105.6.9. 2 Cruise ship hazardous operations. 105.6.9.2.1 An annual operational permit is required to conduct fuel transfers to or from a cruise ship at a passenger terminal. 105.6.9.2.2 A temporary permit is required to conduct hot work on a cruise ship at a passenger terminal. * * *
105.6.11 Cutting and welding. (( * * *
105.6.14 Explosives. An operational permit is required for the (( Exception s : 1. Storage in Group R-3 occupancies of smokeless propellant, black powder and small arms primers for personal use, not for resale and in accordance with Section 3306. 2. Model rocket motors stored in Group R-3 Occupancies meeting the requirements of NFPA 1122, 1125 and 1127 and in accordance with the United States Bureau of Alcohol, Tobacco, Firearms and Explosives. 105.6.14 Point of Information The manufacture of explosives is prohibited within Seattle City limits. * * * 105.6.16 Flammable and combustible liquids. An operational permit is required: 1. To use or operate a pipeline for the transportation within facilities of flammable or combustible liquids. This requirement shall not apply to the off-site transportation in pipelines regulated by the Department of Transportation (DOTn) nor does it apply to piping systems. 2. To store, handle or use Class I liquids in excess of 5 gallons (19 L) in a building or in excess of 10 gallons (37.9 L) outside of a building, except that a permit is not required for the following: 2.1. The storage or use of Class I liquids in the fuel tank of a motor vehicle, aircraft, motorboat, mobile power plant or mobile heating plant, or storage of approved portable motor boat fuel containers of 6 gallons (22.7 L) or less individual capacity and 12 gallons (45.4 L) aggregate capacity, unless such storage, in the opinion of the fire code official, would cause an unsafe condition. 2.2. The storage or use of paints, oils, varnishes or similar flammable mixtures when such liquids are stored for maintenance, painting or similar purposes for a period of not more than 30 days. 3. To store, handle or use Class II or Class IIIA liquids in excess of 25 gallons (95 L) in a building or in excess of 60 gallons (227 L) outside a building, except for fuel oil used in connection with oil-burning equipment. 4. To store, handle or use Class IIIB liquids in tanks or portable tanks for fueling motor vehicles at motor Fueldispensing facilities or where connected to fuel-burning equipment. Exception: Fuel oil and used motor oil used for space heating or water heating. 5. To remove Class I or II liquids from an underground storage tank used for fueling motor vehicles by any means other than the approved, stationary on-site pumps normally used for dispensing purposes. 6. To operate tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. 7. To place temporarily out of service (for more than 90 days) an underground, protected above-ground or aboveground flammable or combustible liquid tank. 8. To change the type of contents stored in a flammable or combustible liquid tank to a material that poses a greater hazard than that for which the tank was designed and constructed. 9. To manufacture, process, blend or refine flammable or combustible liquids. 10. To engage in the dispensing of liquid fuels into the fuel tanks of motor vehicles at commercial, industrial, governmental or manufacturing establishments. 11. To utilize a site for the dispensing of liquid fuels from tank vehicles into the fuel tanks of motor vehicles, marine craft and other special equipment at commercial, industrial, governmental or manufacturing establishments. 12. To store, handle or use Class III-B liquids in excess of 1,000 gallons (3785 L) not provided for in item 4 above. 13. To engage in the business of removing, abandoning or otherwise disposing of residential heating oil tanks. * * * 105.6.19 Fumigation and thermal insecticidal fogging. An operational permit is required to operate a business of fumigation or thermal insecticidal fogging and to maintain a room, vault , freight container, or chamber in which a toxic or flammable fumigant is used. 105.6.20 .1 Hazardous materials. An operational permit is required to store, transport on site, dispense, use or handle hazardous materials in excess of the amounts listed in Table 105.6.20. 105.6.20.2 Hazardous materials stabilization. A temporary permit is required to stabilize potentially unstable (reactive) hazardous materials. 105.6.21 .1 HPM facilities. An operational permit is required to store, handle or use hazardous production materials. 105.6.21.2 Helicopter lifts. A temporary permit is required to move suspended loads via helicopter over populated areas. * * * 105.6.23 Hot work operations. An operational permit is required for hot work including, but not limited to: 1. Public exhibitions and demonstrations where hot work is conducted.
2. Use of portable hot work equipment . ((
Exception s : (( 1. Within Group R, Division 3 and Group U Occupancies. 2. Torch assemblies connected for use to an acetylene gas cylinder having a maximum individual capacity of 40 cubic feet (1.13 m3). 3. Approved self-contained torch assemblies or similar appliances using LP-gas in accordance with the following: a. LP-gas cylinders that comply with UL 147A, Standard for Nonrefillable (Disposable) Type Fuel Gas Cylinder Assemblies. b. LP-gas cylinders that have a maximum water capacity of 2.7 lb (1.2 kg). c. The maximum aggregate water capacity of LP-gas cylinders in storage (e.g. not connected for use) and use does not exceed 2.7 lb (1.2 kg) per control area. 3. Fixed-site hot work equipment such as welding booths.
((
4. (( 5. Hot work on storage tanks, piping and associated systems containing or previously containing flammable or combustible liquids, or other hazardous materials that could present a fire or explosion hazard. 6. Hot work on vessels.
7. (( * * * 105.6.27 LP-gas. An operational permit is required for: 1. Storage and use of LP-gas. Exception s :
1. A permit is not required for individual containers with a (( 2. A permit is not required for LP-gas containers having a water capacity not exceeding 48 pounds [nominal 20 pounds (9 kg) LP-gas] connected to a LP-gas grill unless at a public assembly or on, or serving, a public way. 3. A permit is not required for storage of up to three spare forklift containers each having a maximum individual water capacity of 104 pounds (10 gallons LP-gas). 2. Operation of cargo tankers that transport LP-gas. * * *
105.6.29 Marine terminal. An annual operational permit is required to handle or temporarily locate containers, tanks, or cylinders of hazardous materials at marine terminals located within the Seattle City limits. (( 105.6.30 Open burning. An operational permit is required for the kindling or maintaining of an open fire or a fire on any public street, alley, road, or other public or private ground. Instructions and stipulations of the permit shall be adhered to. Exception: Recreational fires and portable outdoor fireplaces .
105.6.31 Open flames and torches. (( 105.6.32 Open flames and candles. An operational permit is required to use open flames or candles in connection with assembly areas, dining areas of restaurants or drinking establishments. 105.6.32 Point of Information Open flame and candle permit conditions are included in assembly permits at no additional fee. * * *
105.6.34 .1 (( 105.6.34.2 Temporary assembly occupancy. A temporary assembly occupancy permit is required for any outdoor place to be used for the assembly of more than 100 persons or where temporary alterations are made to the existing means of egress, character, or use of any building or facility used for the gathering of 50 or more people. Plans for such alterations shall be submitted when required by the fire code official. * * * 105.6.38 Refrigeration equipment. An operational permit is required to operate a mechanical refrigeration unit or system regulated by Chapter 6. Exception: Refrigeration systems that have a valid annual mechanical permit issued by the Department of Planning and Development. * * * 105.6.41 Spraying or dipping. An operational permit is required to conduct a spraying or dipping operation utilizing flammable or combustible liquids or the application of combustible powders regulated by Chapter 15. Exception: Mobile spray coaters licensed by, and meeting the requirements of, the Puget Sound Clean Air Agency. 105.6.41.1 Spraying with water-based paints. A nofee operational permit is required for spraying operations utilizing water-based paints in accordance with Chapter 15. 105.6.42 Storage of tires, scrap tires and tire byproducts. An operational permit is required to establish, conduct or maintain storage of scrap tires and tire byproducts that exceeds 2,500 cubic feet (71m3) of total volume of scrap tires and for indoor storage of tires and tire byproducts. An operational permit is also required for indoor storage of tires and tire byproducts as regulated by Chapter 23.
105.6.43 Temporary membrane structures and tents. See 105.7.14. ((
* * *
105.7 Required (( 105.7 Point of Information Building permits for construction are issued by the Department of Planning and Development (DPD). The fire code does not require separate Fire Department issued installation permits for the following: * Automatic fire-extinguishing systems. * Fire alarm and detection systems and related equipment. * Standpipe systems. All fire protection systems must be Confidence tested accordance with this code and Administrative Rule 9.02.09, Confidence Test Requirements for Life Safety Systems, and any future revisions of this rule adopted by the fire code official. Fire Department Installation and Operational Permits If an installation permit is required and an operational permit is also required, the approved installation permit is renewable annually as an operational permit.
105.7.1 Automatic fire-extinguishing systems. See Section 105.7 point of information for Department of Planning and Development required permit. ((
105.7.2 Battery systems. A permit is required to install stationary storage battery systems having an electrolyte capacity of more than 50 gallons (189 L) for flooded leadacid, nickel cadmium (Ni-Cd) and valve-regulated lead acid (VRLA), or 1,000
pounds (454 kg) for lithium-ion and lithium metal polymer, used for facility legally-required standby power, emergency power or uninterrupted power supplies. ((
105.7.3 Compressed gases. When the compressed gases in use or storage exceed the amounts listed in Table 105.6.8, a n installation (( Exceptions: 1. Routine maintenance. 2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
105.7.4 Cryogenic fluids. A n ((
105.7.5 Fire alarm and detection systems and related equipment. See Section 105.7 point of information for Department of Planning and Development required permit. ((
105.7.6 Fire pumps and related equipment. A n installation ((
105.7.7 Flammable and combustible liquids. A n installation (( 1. To install, repair or modify a pipeline for the transportation of flammable or combustible liquids. 2. To install, construct or alter tank vehicles, equipment, tanks, plants, terminals, wells, fuel-dispensing stations, refineries, distilleries and similar facilities where flammable and combustible liquids are produced, processed, transported, stored, dispensed or used. 3. To install, alter, remove, abandon or otherwise dispose of a flammable or combustible liquid tank.
105.7.8 Hazardous materials. A n installation (( Exceptions: 1. Routine maintenance. 2. For emergency repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
105.7.9 Industrial ovens. A n installation (( Exceptions: 1. Routine maintenance. 2. For repair work performed on an emergency basis, application for permit shall be made within two working days of commencement of work.
105.7.10 LP-gas. A n installation ((
105.7.11 Refrigeration permit. An installation permit is required to install a mechanical refrigeration unit or system regulated by Chapter 6. (( Exception: Refrigeration units or systems that have a valid mechanical permit issued by the Department of Planning and Development.
105.7.12 Spraying or dipping. A n installation ((
105.7.13 Standpipe systems. See Section 105.7 point of information for Department of Planning and Development required permit. ((
105.7.14 Temporary membrane structures and tents. A n installation (( 1. The membrane structure or tent will be erected for a time period not to exceed four weeks, 2. The membrane structure or tent will be located at least 200 feet from shorelines, 3. No stage, platform, bleacher or similar structure greater than 4 feet in height will be installed inside the membrane structure or tent, 4. The membrane structure or tent will not be attached to a building or other permanent structure for support, and 5. The installation permit does not propose foul weather use, or a structure of unusual shape, unusual location or large area or height. 105.7.14 Point of Information If any one of the above-noted conditions (items 1-5) is not met, a permit for the membrane structure or tent may be required from the Department of Planning and Development. Exceptions: 1. Tents used exclusively for recreational camping purposes. 2. Funeral tents and curtains or extensions attached thereto, when used for funeral services. 3. Tents and awnings open on all sides which comply with all of the following: 3.1. Individual tents shall have a maximum size of 700 square feet (65 m2). 3.2. The aggregate area of multiple tents placed side by side without a fire break clearance of not less than 12 feet (3658 mm) shall not exceed 700 square feet (65 m2) total. 3.3. A minimum clearance of 12 feet (3658 mm) to structures and other tents shall be maintained. * * *
106.2.2 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the fire code official. The fire code official, upon notification, shall make the requested inspections
and shall either indicate the portion of the (( * * * 106.5 Special inspections. The fire code official is authorized to appoint qualified persons or agencies having special technical skills as special inspectors or plan reviewers and accept their inspection, plan review and evaluation of specialized fire protection equipment or systems. 106.5.1 Other inspections. The fire code official is authorized to accept inspections performed by other jurisdictions and agencies and honor permits and certificates issued by other jurisdictions for activities regulated by this code, upon presentation to the fire code official of satisfactory evidence that such inspections, permits and certificates are substantially in accord with the fire safety requirements of this code. * * * 107.2.1 Test and inspection records. Required test and inspection records shall be available to the fire code official at all times or such records as the fire code official designates shall be filed with the fire code official. * * * 107.4 Rendering equipment inoperable. Portable or fixed fireextinguishing systems or devices and fire-warning systems shall not be rendered inoperative or inaccessible except as necessary during emergencies, maintenance, repairs, alterations, drills or prescribed testing. Exception: When approved by the fire code official. * * * 107.6 Overcrowding. Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. The fire code official, upon finding any overcrowding conditions or obstructions in aisles, passageways or other means of egress, or upon finding any condition which constitutes a life safety hazard, shall be authorized to direct actions be taken to reduce the overcrowding or to cause the event to be stopped until such condition or obstruction is corrected. SECTION 108
(( 108 Point of Information For information on appeals procedures, see Seattle Fire Department Information Bulletin Requesting a Review by the Seattle Fire Code Appeals Board at http://www.seattle.gov/fire/FMO/firecode/infobulletins/ fmoBulletins.htm
108.1 Appeals. Appeals from decisions or actions pertaining to the application and interpretation of this Code shall first be addressed to the fire code official. If not resolved with the fire code official, the appellant may submit a written
request to the fire code official for a review by the Fire Code Appeals Board in accordance with all applicable by-laws, rules, regulations and ordinances. The result of this review is advisory only, in accordance with City of Seattle Ordinance 119799.
Following receipt of the Fire Code Appeals Board recommendation the fire chief, who shall not have acted as the fire code official in the first appeal of the application or interpretation of the code, shall issue a final written decision.
((
((
(( SECTION 109 VIOLATIONS
109.1 Unlawful acts. It shall be unlawful for a person((
109.2 Notice of violation. When the fire code official finds a building, premises, vehicle, vessel, storage facility or outdoor area that is in violation of this code, the fire code official is authorized to ((
109.2.1 Service. A notice of violation issued pursuant to this code shall be served upon the owner, operator, occupant or other person responsible for the condition or violation, either by personal service, mail or by delivering the same to, and leaving
it with, some person of responsibility upon the premises. For unattended or abandoned locations, a copy of such notice of violation shall be posted on the premises in a conspicuous place at or near the entrance to such premises and the notice of
violation (( 109.2.2 Compliance with orders and notices. A notice of violation issued or served as provided by this code shall be complied with by the owner, operator, occupant or other person responsible for the condition or violation to which the notice of violation pertains.
109.2.3 Prosecution of violations. If the notice of violation is not complied with promptly or by the time specified in the notice , the fire code official is authorized to request the legal counsel of the jurisdiction to institute the
appropriate legal proceedings at law or in equity to restrain, correct or abate such violation , (( 109.2.4 Unauthorized tampering. Signs, tags or seals posted or affixed by the fire code official shall not be mutilated, destroyed or tampered with or removed without authorization from the fire code official.
109.3 ((
109.3.1 Alternative civil penalties. Any person (( 109.3.2 Alternative criminal penalty. Any person who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction or installation documents or directive of the fire code official, or of a permit or certificate used under provisions of this code, shall be guilty of a gross misdemeanor subject to the provisions of Seattle Municipal Code Chapters 12A.02 and 12A.04, except that absolute liability shall be imposed for such a violation or failure to comply and none of the mental states described in Section 12A.04.030 need be proved. The fire code official may request the City Attorney prosecute such violations criminally as an alternative to the civil penalties provision. Each day that a violation continues shall be deemed a separate offense.
109.(( SECTION 110 UNSAFE BUILDINGS , PREMISES, MOTOR VEHICLES AND VESSELS
110.1 General. If ((
110.1.1 Unsafe conditions. Structures , premises or existing equipment that are or hereafter become unsafe or deficient because of inadequate means of egress, ((
110.1.2 Structural hazards. When an apparent structural hazard is caused by the faulty installation, operation or malfunction of any of the items or devices governed by this code, the fire code official (( 110.2 Evacuation. The fire code official or the fire department official in charge of an incident shall be authorized to order the immediate evacuation of any occupied premises, building , motor vehicle or vessel deemed unsafe when such premises, building , motor vehicle, or vessel has hazardous conditions that present imminent danger to premises, building , motor vehicle, or vessel occupants. Persons so notified shall immediately leave the structure or premises , motor vehicle, or vessel and shall not enter or re-enter until authorized to do so by the fire code official or the fire department official in charge of the incident. 110.3 Summary abatement. Where conditions exist that are deemed hazardous to life and property, the fire code official or fire department official in charge of the incident is authorized to abate summarily such hazardous conditions that are in violation of this code. 110.4 Abatement. The owner, operator or occupant of a building or premises deemed unsafe by the fire code official shall abate or cause to be abated or corrected such unsafe conditions either by repair, rehabilitation, demolition or other approved corrective action. 110.5 Notification. The fire code official shall serve the responsible party with a copy of violations, correction letters and orders issued. SECTION 111 STOP WORK OR USE ORDER 111.1 Order. Whenever the fire code official finds any work or use regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work or use order. 111.2 Issuance. A stop work or use order shall be in writing and shall be given to the owner of the property, or to the owner's agent, or to the person doing the work or use . Upon issuance of a stop work or use order, the cited work or use shall immediately cease. The stop work or use order shall state the reason for the order, and the conditions under which the cited work or use is authorized to resume. 111.3 Emergencies. Where an emergency exists, the fire code official shall not be required to give a written notice prior to stopping the work or use .
111.4 Failure to comply. It is a violation of this code for (( * * * SECTION 113 FEES 113.1 Fees. A permit shall not be issued until the fees have been paid, nor shall an amendment to a permit be released until the additional fee, if any, has been paid. Exception: Those permits for which the fire code official, pursuant to the annual fee ordinance, authorizes invoices to be sent for the fees after the permits are issued.
113.2 Schedule of permit fees. A fee for each permit shall be paid as required, in accordance with the schedule ((
((
113.((
113.(( Section 4. Chapter 2 of the 2009 International Fire Code is amended as follows: *** 201.5 References to other codes. If an International, National or Uniform Code is referenced in this code, it means the edition that is currently in effect of that International, National or Uniform code, along with its adopted Seattle amendments. References to the "Building Code", "Fire Code", "Mechanical Code" and "Plumbing Code" mean the Seattle editions of those codes. *** SECTION 202 GENERAL DEFINITIONS *** [W] ADULT FAMILY HOME. Means a dwelling, licensed by Washington state, in which a person or persons provide personal care, special care, room and board to more than one but not more than six adults who are not related by blood or marriage to the person or persons providing the services. *** [W] ALERT SIGNAL. See Section 402.1. [W] ALERT SYSTEM. See Section 915. *** BERTH. See Section 9402.1. *** BOATHOUSE. See Section 9402.1. *** [B] CHILD CARE FACILITIES. Facilities that provide care on a 24-hour basis to more than five children, 21/2 years of age or less , shall be classified as Group I-2 . [W] CHILD DAY CARE. For the purposes of these regulations is the care of children during any period of a 24-hour day. [W] CHILD DAY CARE HOME, FAMILY. A child day care facility, licensed by Washington State, located in the dwelling of the person or persons under whose direct care and supervision the child is placed, for the care of twelve or fewer children, including children who reside at the home. *** CLOSED CONTAINER . See Section 2702.1. *** COVERED BOAT MOORAGE. See Sections 4502.1 and 9402.1. *** DESIGNATED HOT WORK FACILITY. See Section 4502.1. *** ELECTRICAL CODE. The National Electrical Code, promulgated by the National Fire Protection Association, as adopted and amended by this jurisdiction. *** [B] EMERGENCY POWER SYSTEM. An electrical system that complies with Seattle Electrical Code Article 700. *** FIRE DETECTION SYSTEM. See Section 902.1. *** [B] FIRE DISTRICT. See Section 2202.1. *** FLOAT. See Section s 4502.1 and 9402.1. *** [W] FULL LOCKDOWN. See Section 402.1. *** HIGH-RISE BUILDING. See Section 902.1. ***
[M] HOOD. ((
(( Type I. A kitchen hood for collecting and removing grease vapors and smoke generated from medium-duty, heavy-duty, extra-heavy-duty, and some light-duty cooking appliances. Such hoods are equipped with a fire suppression system. Type II. A general kitchen hood for collecting and removing steam, vapor, heat, odors and products of combustion generated from some light-duty cooking appliances. *** MOTOR VEHICLE. See Section 2202.1. MOTOR VEHICLE, UNATTENDED. See Section 2202.1 . *** [W] NIGHTCLUB. An A-2 Occupancy use under the 2006 International Building Code in which the aggregate area of concentrated use of unfixed chairs and standing space that is specifically designated and primarily used for dancing or viewing performers exceeds three hundred fifty square feet, excluding adjacent lobby areas. "Nightclub" does not include theaters with fixed seating, banquet halls, or lodge halls. *** OCCUPANCY CLASSIFICATION. For the purposes of this code, certain occupancies are defined as follows: *** [W] Day care. The use of a building or structure, or portion thereof, for educational, supervision or personal care services for more than five children older than 21/2 years of age shall be classified as an E occupancy. Exception: Family child day care homes licensed by the state of Washington for the care of twelve or fewer children shall be classified as Group R-3. *** [W] Group I-1. This occupancy shall include buildings, structures or parts thereof housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services. The occupants are capable of responding to an emergency situation without physical assistance from staff. This group shall include, but not be limited to, the following: Alcohol and drug centers Assisted living facilities Congregate care facilities Convalescent facilities Group homes Half-way houses Residential board and care facilities Social rehabilitation facilities
A facility such as the above with five or fewer persons and adult family homes licensed by Washington state shall be classified as Group R-3 or shall comply with the International Residential Code in accordance with Section 101.2 of the
International Building Code. (( A facility such as the above providing licensed care to clients in one of the categories listed in the Seattle Building Code Section 310.1 licensed by Washington state shall be classified as Group R-2.
[B] Group I-2. This occupancy shall include buildings and structures used for medical, surgical, psychiatric, nursing or custodial care on a 24-hour basis (( Child care facilities Detoxification facilities Hospice care centers Hospitals Mental hospitals Nursing homes (both intermediate-care facilities and skilled nursing facilities) [W] A facility such as the above providing licensed care to clients in one of the categories listed in Seattle Building Code Section 310.1 licensed by Washington state shall be classified as Group R-2. [W] A facility such as the above with five or fewer shall be classified as Group R-3 or shall comply with the Seattle Residential Code. *** [W] Adult care facility. A facility that provides accommodations for less than 24 hours for more than five unrelated adults and provides supervision and personal care services shall be classified as Group I-4.
Exception: Where the occupants are capable of responding to an emergency situation without physical assistance from the staff, the facility shall be classified as Group ((
[W] Child care facility. (( Exception s : 1. A child day care facility that provides care for more than five but no more than 100 children 21/2 years or less of age, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E. 2. Family child day care homes licensed by Washington state for the care of 12 or fewer children shall be classified as Group R-3. *** [W] Residential Group R. Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I or when not regulated by the International Residential Code in accordance with Section 101.2 of the International Building Code. Residential occupancies shall include the following: R-1 Residential occupancies containing sleeping units where the occupants are primarily transient in nature, including: Boarding houses (transient) with more than 10 occupants Hotels (transient) Motels (transient)
Congregate living facilities (transient) with more than 10 (( R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including: Apartment houses Boarding homes licensed by Washington state under Chapter 388-78A WAC Boarding houses (nontransient) with more than 16 occupants Convents Dormitories Fraternities and sororities Hotels (nontransient) Live/work units Monasteries Motels (nontransient) Residential treatment facilities as licensed by Washington state under Chapter 246-337 WAC Vacation timeshare properties
Congregate living facilities (nontransient) with more than 16 occupants ((
[W] R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, (( Buildings that do not contain more than two dwelling units. Adult care facilities that provide accommodations for five or fewer persons of any age for less than 24 hours.
((
Congregate living facilities (nontransient) (( Congregate living facilities (transient) with 10 or fewer occupants. Adult family homes, family child day care homes, and adult care and child care facilities that are within a single family home are permitted to comply with the International Residential Code. Foster family care homes licensed by Washington state are permitted, as an accessory use to a dwelling, for six or fewer children including those of the resident family.
(( [B] Storage Group S. Storage Group S occupancy includes, among others, the use of a building or structure, or a portion thereof, for storage that is not classified as a hazardous occupancy. Moderate-hazard storage, Group S-1. Buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following: Aerosols, Levels 2 and 3 Aircraft hangar (storage and repair) Bags: cloth, burlap and paper Bamboos and rattan Baskets Belting: canvas and leather Books and paper in rolls or packs Boots and shoes Buttons, including cloth covered, pearl or bone Cardboard and cardboard boxes Clothing, woolen wearing apparel Cordage Dry boat storage (indoor) Furniture Furs Glues, mucilage, pastes and size Grains Horns and combs, other than celluloid Leather Linoleum Lumber Motor vehicle and marine repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 2703.1.1(1) (see Section 406.6 of the International Building Code) Photo engravings Resilient flooring Silks Soaps Sugar Tires, bulk storage of Tobacco, cigars, cigarettes and snuff Upholstery and mattresses Wax candles Low-hazard storage, Group S-2. Includes, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Storage uses shall include, but not be limited to, storage of the following: Asbestos Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers Cement in bags Chalk and crayons Covered boat moorage not classified as Group U Dairy products in nonwaxed coated paper containers Dry cell batteries Electrical coils Electrical motors Empty cans Food products Foods in noncombustible containers Fresh fruits and vegetables in nonplastic trays or containers Frozen foods Glass Glass bottles, empty or filled with noncombustible liquids Gypsum board Inert pigments Ivory Meats Metal cabinets Metal desks with plastic tops and trim Metal parts Metals Mirrors Oil-filled and other types of distribution transformers Parking garages, open or enclosed Porcelain and pottery Stoves Talc and soapstones Washers and dryers *** OIL-BURNING EQUIPMENT. See Section 602.1. *** PF DEVICE. See Section 2602.1. *** PIER. See Section s 4502.1 and 9402.1 . *** POWER TAP. See Section 602.1. *** [W] RECALL SIGNAL. See Section 402.1. *** SHIPYARD. A pier, wharf or series of piers and wharves and related onshore facilities, designated by the fire code official, that by virtue of the pier construction, location, emergency vehicle access, fire protection, hydrant availability and onsite safety personnel in accordance with Seattle Fire Department Administrative Rule 26.02.09, Designated Hot Work Facilities and Shipyards and any future revisions of this rule adopted by the fire code official, is suitable to permit repairs, including major conversions, on marine vessels of any length. *** SLIP. See Section 9402.1. *** [B] STANDBY POWER SYSTEM, LEGALLY REQUIRED. An electrical power system that complies with Seattle Electrical Code Article 701, Legally Required Standby Systems. *** STANDBY FIRE PERSONNEL. Uniformed employees of the Seattle Fire Department. *** SUBSTRUCTURE. See Section 4502.1. SUPERSTRUCTURE. See Section 4502.1. *** VAULT. See Section 3402.1. ***
VESSEL. (( *** WHARF. See Section s 4502.1 and 9402.1 . *** Section 5. Chapter 3 of the 2009 International Fire Code is amended as follows: *** SECTION 302 DEFINITIONS *** BONFIRE. An outdoor fire utilized for ceremonial or recreational purposes and exceeding the size of a recreational fire . ***
PORTABLE OUTDOOR FIREPLACE. A n (( *** 303.2 Location. Asphalt (tar) kettles shall not be located within 20 feet (6096 mm) of any combustible material, combustible building surface or any building opening and within a controlled area identified by the use of traffic cones, barriers or other approved means. Asphalt (tar) kettles and pots shall not be utilized inside or on the roof of a building or structure. Roofing kettles and operating asphalt (tar) kettles shall not block means of egress, gates, roadways or entrances. Exception: If a practical difficulty is satisfactorily demonstrated, tar kettles may be located on a roof. All roof top kettles require a temporary permit. *** 303.10 LPG fuel containers. The maximum individual LPG container capacity and the aggregate quantity of LPG allowed to be used in conjunction with tar kettles shall be in accordance with Chapter 38. ***
304.3 Containers. Combustible rubbish, and waste material kept within or near a structure shall be stored in accordance with Sections 304.3.1 through 304.3.(( 304.3.1 Spontaneous ignition. Materials susceptible to spontaneous ignition, such as oily rags, shall be stored in a listed disposal container. Contents of such containers shall be removed and disposed of daily. 304.3.2 Capacity exceeding 5.33 cubic feet. Containers with a capacity exceeding 5.33 cubic feet (40 gallons) (0.15 m3) shall be provided with lids. Containers and lids shall be constructed of noncombustible materials or of combustible materials with a peak rate of heat release not exceeding 300 kW/m2 when tested in accordance with ASTM E 1354 at an incident heat flux of 50 kW/m2 in the horizontal orientation. Exception s : 1. Wastebaskets in Group I-3 occupancies shall comply with Section 808.1. 2. Waste accumulated for collection by the City's solid waste utility shall be stored in containers (to include recycling containers) specified in the City's solid waste collection contracts authorized by ordinance. 3. Containers in areas protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.
((
304.3. 3 (( Exceptions: 1. Dumpsters in areas protected by an approved automatic sprinkler system installed throughout in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Storage in a structure shall not be prohibited where the structure is of Type I or IIA construction, located not less than 10 feet (3048 mm) from other buildings and used exclusively for dumpster or container storage. *** 306.1.1 Fire extinguishers. Two approved fire extinguishers with a minimum 10-B:C rating shall be installed and maintained ready for use in projection rooms. *** SECTION 307 OPEN BURNING, BONFIRES, RECREATIONAL FIRES AND PORTABLE OUTDOOR FIREPLACES
307.1 General. ((
((
307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling (( 307.2.1 Authorization. Where required by state or local law or regulations, open burning shall only be permitted with prior approval from the state or local air and water quality management authority, provided that all conditions specified in the authorization are followed.
307.3 Extinguishment authority. The fire code official is authorized to order the extinguishment by the permit holder, another person responsible or the fire department of open burning((
((
307.4((
307. 5 ((
307. 6 (( Exception: Portable outdoor fireplaces used at oneand twofamily dwellings.
307. 7 (( 307.8 General burning prohibitions Trash, yard waste, rubbish and paper are prohibited as fuel for bonfires, recreational fires and fires in outdoor fireplaces. Smoke or odor emissions from bonfires, recreational fires and use of outdoor fireplaces that make such fires hazardous shall be prohibited. The fire code official is authorized to order the extinguishment of a bonfire, recreational fire or fire in an outdoor fireplace which creates or adds to a hazardous situation. 307.8 Point of Information Hazards from bonfires, recreational fires, and fires in outdoor fireplaces may include but are not limited to smoke or odor emissions causing potential for false alarms, medical alarms, hazards to health, and exposure to other structures from fire. If conducting a bonfire or recreational fire or if using an outdoor fireplace, fire extinguishing equipment in accordance with SFC 307.7 shall be available for immediate use. For additional regulations and information pertaining to outdoor fires and burning, see RCW 70.94. Go to www.pscleanair.org for information on how to register an air quality complaint with the Puget Sound Clean Air Agency. See SFD Information Bulletin Recreational and Cooking Fire Regulations at www.seattle.gov/fire. For air quality and burn ban status information and regulations contact the Puget Sound Clean Air Agency referenced above. SECTION 308 OPEN FLAMES 308.1 General. Open flame, fire and burning on all premises shall be in accordance with Sections 308.1.1 through 308.4.1 and with other applicable sections of this code. Exception: Bonfires, recreational fires and use of portable outdoor fireplaces shall be in accordance with Section 307. ***
((
308.1.((
308.1.(( Exception: Use within inhabited premises or designated campsites which are a minimum of 30 feet (9144 mm) from grass-, grain-, brushor forest-covered areas.
308.1.(( Exception: The proper use of fuses at the scenes of emergencies or as required by standard railroad operating procedures.
308.1.(( Exceptions: 1. LP-gas-fueled devices used for sweating pipe joints or removing paint in accordance with Chapter 38. 2. Cutting and welding operations in accordance with Chapter 26.
3. Torches or flame-producing devices in accordance with Section 308.((
4. Candles and open-flame decorative devices in accordance with Section 308.((
308.1.(( A competent adult shall remain within 15 feet (4572 mm) of a child carrying a hand-held candle at all times, unless an alternative equivalent safety standard is approved.
((
308.1.((
308.1.(( 1. A 1-ounce (29.6 ml) container; or 2. A container not exceeding 1-quart (946.5 ml) capacity with a controlled pouring device that will limit the flow to a 1ounce (29.6 ml) serving.
308.1.((
308.1.((
308.1.((
308.1.(( 308.1.8 Aisles and exits. Candles shall be prohibited in areas where occupants stand, or in an aisle or exit. Exception: Candles used in religious ceremonies. See Section 308.1.6. 308.1.9 Open-flame decorative devices. Open-flame decorative devices used in assembly areas, dining areas of restaurants or drinking establishments shall comply with all of the following restrictions: 1. Class I and Class II liquids and LP-gas shall not be used. 2. Liquidor solid-fueled lighting devices containing more than 8 ounces (237 ml) of fuel must self-extinguish and not leak fuel at a rate of more than 0.25 teaspoon per minute (1.26 ml per minute) if tipped over. 3. The device or holder shall be constructed to prevent the spillage of liquid fuel or wax at the rate of more \ than 0.25 teaspoon per minute (1.26 ml per minute) when the device or holder is not in an upright position. 4. The device or holder shall be designed so that it will return to the upright position after being tilted to an angle of 45 degrees from vertical. Exception: Devices that self-extinguish if tipped over and do not spill fuel or wax at the rate of more than 0.25 teaspoon per minute (1.26 ml per minute) if tipped over. 5. The flame shall be enclosed except where openings on the side are not more than 0.375 inch (9.5 mm) diameter or where openings are on the top and the distance to the top is such that a piece of tissue paper placed on the top will not ignite in 10 seconds. 6. Chimneys shall be made of noncombustible materials and securely attached to the open-flame device. Exception: A chimney is not required to be attached to any open-flame device that will self-extinguish if the device is tipped over. 7. Fuel canisters shall be safely sealed for storage. 8. Storage and handling of combustible liquids shall be in accordance with Chapter 34. 9. Shades, where used, shall be made of noncombustible materials and securely attached to the open flame device holder or chimney. 10. Candelabras with flame-lighted candles shall be securely fastened in place to prevent overturning, and shall be located away from occupants using the area and away from possible contact with drapes, curtains or other combustibles. 308.2 Permits required. Permits shall be obtained from the fire code official in accordance with Section 105.6 prior to engaging in the following activities involving open flame, fire and burning: 1. Use of a torch or flame-producing device to remove paint from a structure. 2. Use of open flame, fire or burning in connection with Group A or E occupancies. 3. Use or operation of torches and other devices, machines or processes liable to start or cause fire in or upon wildfire risk areas. 308.3 Group A occupancies. Open-flame devices shall not be used in a Group A occupancy. Exceptions: 1. Open-flame devices are allowed to be used in the following situations, provided approved precautions are taken to prevent ignition of a combustible material or injury to occupants:
1.1. Where necessary for ceremonial or religious purposes in accordance with Section 308.1.((
1.2. On stages and platforms as a necessary part of a performance in accordance with Section 308.3.(( 1.3. Where candles on tables are securely supported on substantial noncombustible bases and the candle flames are protected. 2. Heat-producing equipment complying with Chapter 6 and the International Mechanical Code. 3. Gas lights are allowed to be used provided adequate precautions satisfactory to the fire code official are taken to prevent ignition of combustible materials.
((
308.3.((
308.4 Group R occupancies. Open flame, fire and burning in Group R occupancies shall comply with the requirements of Sections 308.1 through 308.1.(( *** 310.3 "No Smoking" signs. The fire code official is authorized to order the posting of "No Smoking" signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required "No Smoking" signs shall be approved. 310.3 Point of Information See Seattle Municipal Code 10.64 for requirements for posting "no smoking" signs in public places. ***
311.1.1 Abandoned premises. Buildings, structures and premises (( *** 311.2.2 Fire protection. Fire alarm, sprinkler and standpipe systems shall be maintained in an operable condition at all times. Exceptions: 1. When the premises have been cleared of all combustible materials and debris and, in the opinion of the fire code official, the type of construction, fire separation distance and security of the premises do not create a fire hazard.
2. Where approved by the fire code official (( *** 311.3 Removal of combustibles. Persons owning, or in charge or control of, a vacant building or portion thereof, shall remove therefrom all accumulations of combustible materials, flammable or combustible waste or rubbish and shall securely lock or otherwise secure doors, windows and other openings to prevent entry by unauthorized persons. The premises shall be maintained clear of waste or hazardous materials.
Exception((
((
(( ***
311.5 Placards. (( *** SECTION 313 FUELED EQUIPMENT
313.1 General. Fueled equipment including, but not limited to, (( Exceptions: 1. Buildings or rooms constructed for such use in accordance with the International Building Code.
2. If a temporary permit for exhibits, trade shows or special events has been issued in accordance with section 105.6.13. (( 3. Storage of equipment utilized for maintenance purposes is allowed in approved locations when the aggregate fuel capacity of the stored equipment does not exceed 10 gallons (38 L) and the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. 313.2 Fueled motor vehicles and watercraft. Fueled motor vehicles and watercraft, including but not limited to motorcycles, mopeds, and motor boats, shall not be stored, operated or repaired within a building. Exceptions: 1. Buildings or rooms constructed for such use in accordance with the International Building Code. 2. If under a temporary permit for exhibits, trade shows, or special events in accordance with Section 106.6.14.
313. 3 ((
313. 4 (( *** 315.2.2.1 Storage under stairways. Storage is prohibited under exit stairways. Exception: Enclosures under stairways in accordance with Section 1009.6.3. *** 315.2.5 Storage arrangements. Storage shall be within 20 feet (6096mm) of the two aisles each at least 44 inches (13411mm) wide. No block pile shall exceed 40 feet by 40 feet (12192mm by 12192mm) unless approved by the fire code official. No dead-end aisle shall be longer than 10 times the width. All storage in unsprinklered areas shall be within 150 feet (45720mm) aisle travel of fire department exterior access openings. Storage shall not obstruct access to extinguishers, standpipe outlets, sprinkler control shut down and safety controls or fire department access openings (for high-piled storage, see Chapter 23). *** SECTION 318 FIXED GUIDEWAY TRANSIT AND PASSENGER RAIL SYSTEMS 318.1 Fixed guideway transit and passenger rail systems. Fixed guideway transit and passenger rail systems shall be in accordance with NFPA 130 as amended. 318 Point of Information Adopted local amendments to NFPA 130 can be accessed at http://www.seattle.gov/fire/FMO/firecode/nfpaAmendments.htm SECTION 319 ROAD TUNNELS, BRIDGES AND OTHER LIMITED ACCESS HIGHWAYS 319.1 Road tunnels, bridges and other limited access highways. Road tunnels, bridges, and other limited access highways shall be in accordance with NFPA 502 as amended. 319 Point of Information Adopted local amendments to NFPA 502 can be accessed at http://www.seattle.gov/fire/FMO/firecode/nfpaAmendments.htm Section 6. Chapter 4 of the 2009 International Fire Code is amended as follows: ***
[W] 401.2 Approval. Where required by (( *** 401.3.2 Alarm activations. Upon activation of a fire or emergency alarm signal, employees or staff shall immediately notify the fire department. *** 401.9 Evacuation required. In the event of activation of a fire or emergency alarm, occupants of the building or portion of the building in which the alarm is activated shall make a safe and orderly evacuation out of the building, or as provided in the building's fire safety and evacuation plan. Exceptions: 1. Where the occupant's physical or other disability makes the occupant unable to evacuate without assistance and no assistance is immediately available; or 2. Where the presence of smoke, fire, structural collapse or other hazard or obstruction in the occupant's means of egress makes evacuation unsafe. *** SECTION 402 DEFINITIONS 402.1 Definition. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. [W] ALARM SIGNAL. See Section 902.1. [W] ALERT SIGNAL. A distinctive signal indicating the need for trained personnel and occupants to initiate a specific action, such as lockdown or shelter-in-place.
EMERGENCY (( LOCKDOWN. An emergency situation, in other than a Group I-3 occupancy, requiring that the occupants be sheltered and secured in place within a building when normal evacuation would put occupants at risk. [W] FULL LOCKDOWN. Occupants remain out of sight and as quiet as possible, with only limited authorized entry, exit, or movement within the building. Occupants in corridors, common areas, or unsecured areas move quickly to the nearest secured area. [W] MODIFIED LOCKDOWN. Occupants of a facility are isolated from potential outside threats by remaining within a building with exterior doors and other exits secured, and that entry and exit from the building is limited to that which is authorized. During a modified lockdown, interior movement and other activities within the building may be allowed or restricted in accordance to the lockdown plan. [W] SHELTER-IN-PLACE. An emergency response used to minimize exposure of facility occupants to chemical or environmental hazards by taking refuge in predetermined interior rooms or areas where actions are taken to isolate the interior environment from the exterior hazard. [W] RECALL SIGNAL. An electrically or mechanically operated signal used to recall occupants after an emergency drill or to terminate a lockdown or shelter-in-place event that shall be distinct from any alarm or alert signal used to initiate an emergency plan, or other signals. SECTION 403 PUBLIC ASSEMBLAGES AND EVENTS 403.1 Fire watch and standby fire personnel . When, in the opinion of the fire code official, it is essential for public safety in a place of assembly or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall provide, at no cost to the jurisdiction, one or more fire watch personnel or standby fire personnel , as required and approved, to remain on duty during the times such places are open to the public, or when such activity is being conducted. 403.1.1 Duties. Fire watch personnel shall keep diligent watch for fires, obstructions to means of egress and other hazards during the time such place is open to the public or such activity is being conducted and take prompt measures for remediation of hazards, extinguishment of fires that occur and assist in the evacuation of the public from the structures. Fire watch personnel and standby fire personnel are subject to the fire code official's orders at all times; shall remain on duty during the times such places are open to the public, or as otherwise required by fire code official; and shall not be required or permitted, while on duty, to perform any duties other than those specified by the fire code official. Where a fire protection system is out of service, the procedures detailed in Administrative Rule 9.06.07, Out-OfService Fire and Life Safety Systems and any future revisions of this rule adopted by the fire code official shall be implemented. *** [W] SECTION 404
FIRE SAFETY AND (( [W] 404.1 General. Fire safety, evacuation , shelter-in-place and lockdown plans and associated drills shall comply with the requirements of Sections 404.2 through 404.5.1. [W] 404.2 Fire safety and evacuation plans. Fire safety and evacuation plans shall comply with the requirements of Sections 404.2.1 through 404.2.2.2.
[W] 404.2 .1 Where required. A((
1. Group A(( 2. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 3. Group E. 4. Group F buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 5. Group H. 6. Group I. 7. Group R-1.
8. Group R-2 college and university buildings((
((
((
((
((
((
(( 404.2.1 Point of Information The State of Washington does not adopt Group R-4 occupancies. Group R-4 occupancies are considered "Group R-2 occupancies licensed by the State of Washington". Special provisions may apply.
[W] 404.((
[W] 404.(( 1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only. 2. Procedures for employees who must remain to operate critical equipment before evacuating. 3. Procedures for assisted rescue for persons unable to use the general means of egress unassisted. 4. Procedures for accounting for employees and occupants after evacuation has been completed. 5. Identification and assignment of personnel responsible for rescue or emergency medical aid. 6. The preferred and any alternative means of notifying occupants of a fire or emergency. 7. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization. 8. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan. 9. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
[W] 404.(( 1. The procedure for reporting a fire or other emergency. 2. The life safety strategy and procedures for notifying, relocating or evacuating occupants, including occupants who need assistance. 3. Site plans indicating the following: 3.1. The occupancy assembly point. 3.2. The locations of fire hydrants. 3.3. The normal routes of fire department vehicle access. 4. Floor plans identifying the locations of the following: 4.1. Exits. 4.2. Primary evacuation routes. 4.3. Secondary evacuation routes. 4.4. Accessible egress routes. 4.5. Areas of refuge. 4.6. Exterior areas for assisted rescue. 4.7. Manual fire alarm boxes. 4.8. Portable fire extinguishers. 4.9. Occupant-use hose stations. 4.10. Fire alarm annunciators and controls. 5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures. 6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires. 7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources. [W] 404.3 Shelter-in-place and lockdown plans. Shelter-inplace and lockdown plans shall comply with the requirements of Sections 404.3.1 through 404.3.3. [W] 404.3.1 Where required. A shelter-in-place and lockdown plan shall be prepared and maintained for all Group E occupancies. Exception: Daycares not collocated on a Group E campus. [W] 404.3.2 Shelter-in-place plan contents. Shelter-inplace plans shall include the following: 1. Identification of the procedures for initiating the shelter-in-place plan throughout the facility or campus. 2. Identification of prearranged alert and recall signals to notify all occupants. 3. Identification of procedures for reporting the facility is sheltering-in-place to the local emergency dispatch center. 4. A means of two-way communication between a central location and each secure area. 5. Identification of protective security measures. 6. Location of emergency supplies. 7. Accountability procedures for staff to report the presence or absence of occupants. 8. Identification of crisis response team members in accordance with the National Incident Management System. 9. Actions to be taken in the event of a fire or medical emergency while sheltering-in-place.
((
[W] 404.3.3(( 1. Identification of the procedures of initiating the lockdown plan throughout the facility or campus. 2. Identification of prearranged alert and recall signals to notify all occupants. 3. Identification of procedures for access to the facility for emergency responders. 4. Identification of procedures for reporting the facility is in lockdown to the local emergency dispatch center. 5. A means of two-way communication between a central location and each secure area. 6. Identification of protective security measures. 7. Location of emergency supplies. 8. Accountability procedures for staff to report the presence or absence of occupants. 9. Identification of crisis response team members in accordance with the National Incident Management System emergency while in lockdown. 10. Actions to be taken in the event of a fire or medical emergency while in lockdown.
((
((
((
404.4 Maintenance. Fire safety ((
404.5 Availability. Fire safety (( *** [W] SECTION 405
EMERGENCY ((
[W] 405.1 General. Emergency ((
[W] 405.2 Frequency. Required emergency (( 405.2.1 Group E Occupancies. At a minimum the following drills shall be conducted during each year. 1. One drill using the school mapping information system Exception: Daycares not co-located on a school campus. 2. Six fire evacuation drills 3. One shelter-in-place drill 4. One lockdown drill TABLE 405.2
((
a. The frequency ((
b. (( c. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. d. Applicable to Group R-2 college and university buildings in accordance with Section 408.3. e. Daycares collocated on a Group E campus shall participate in emergency drills occurring on the campus. f. Boarding homes, group homes, and residential treatment facilities licensed by the state of Washington. Table 405.2 Point of Information The State of Washington does not adopt Group R-4 occupancies. Group R-4 occupancies are considered "Group R-2 occupancies licensed by the state of Washington". Special provisions may apply. *** [W] 405.5 Record keeping. Records shall be maintained of required emergency evacuation drills and include the following information: 1. Identity of the person conducting the drill. 2. Date and time of the drill. 3. Notification method used. 4. Staff members on duty and participating.
5. Number of occupants (( 6. Special conditions simulated. 7. Problems encountered and corrective actions taken . 8. Weather conditions when occupants were evacuated. 9. Time required to accomplish complete evacuation , lockdown, or shelter-in-place .
[W] 405.6 Notification. Where required by the fire code official, prior notification of emergency (( [W] 405.7 Initiation. Emergency drills shall be initiated in accordance with Sections 405.7.1 through 405.7.3. 405.7.1 Fire evacuation drills. Where a fire alarm system is provided, emergency evacuation drills shall be initiated by activating the fire alarm system. The fire alarm monitoring company shall be notified prior to the activation of the fire alarm system for a proposed drill and again at the conclusion of the transmission and restoration of the fire alarm system to normal mode. Exception: Evacuation drills conducted between the hours of 9 p.m. and 6 a.m. in Group R-2 boarding homes, group homes, and residential treatment facilities licensed by the State of Washington are not required to be initiated by the fire alarm system. [W] 405.7.2 Shelter-in-place drills. Shelterin-place drills shall be initiated by the shelter-in-place alert signal, generated by the alerting system in accordance with Section 915. [W] 405.7.3 Lockdown drills. Lockdown drills shall be initiated from the lockdown alert signal. [W] 405.8 Accountability. As building occupants arrive at the assembly point, efforts shall be made to determine if all occupants have been successfully evacuated , locked down or sheltered-in-place have been accounted for.
[W] 405.9 Recall and reentry. (( SECTION 406 EMPLOYEE TRAINING AND RESPONSE PROCEDURES
406.1 General. Employees in the occupancies listed in Section 404.2 .1 shall be trained in the ((
[W] 406.2 Frequency. Employees shall receive training in the contents of the (( [W] 406.3 Employee training program. Employees shall be trained in fire prevention, evacuation , sheltering-inplace, lockdown and fire safety in accordance with Sections 406.3.1 through 406.3.4. ***
[W] 406.3.3 Emergency shelter-in-place and lockdown training. Where a facility has a shelter-in-place or lockdown plan, employees shall be trained on the alert and recall signals, communication system, location of
emergency supplies, the use of the incident notification and alarm system and their assigned duties and procedures in the event of an (( ***
407.2 Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be (( ***
407.7 Facility closure plans. When required by the fire code official, t (( ***
[W] 408.10 Group R-4 occupancies. This section is not adopted. ((
((
408.10 Point of Information The State of Washington does not adopt Group R-4 occupancies. Group R-4 occupancies are considered "Group R-2 occupancies licensed by the State of Washington". Special provisions may apply. ***
408.11.1.1 Submittal (( *** Section 7. Chapter 5 of the 2009 International Fire Code is amended as follows: *** SECTION 502 DEFINITIONS *** FIRE DEPARTMENT MASTER KEY. A limited issue key of special or controlled design to be carried by fire department officials in command which will open key boxes on specified properties. 502.1 Point of Information The fire code official has approved the "KnoxBox" as the access key box for use in the City of Seattle. *** 503.1 Where required. Fire apparatus access roads shall be provided and maintained in accordance with Sections 503.1.1 through 503.1.3 and Appendix D as amended. ***
503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of
not less than (( Exceptions: 1. Access roads serving not more than two Group R-3 or U occupancies shall have an unobstructed width of not less than 12 feet. 2. Public streets shall be in accordance with Seattle Right of Way Improvements Manual. ***
503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be (( Exception: Turnarounds in accordance with Appendix D as amended.
503.2.5 Dead ends. Dead-end fire apparatus access roads in excess of 150 feet (45 720 mm) in length shall be provided with a turnaround in accordance with Appendix D as amended. ((
503.2.6 Bridges and elevated surfaces. Where a bridge or an elevated surface is part of a fire apparatus access road, the bridge shall be constructed and maintained in accordance with the Seattle Right of Way Improvements Manual.
((
503.2.7 Grade. The grade of the fire apparatus access road shall be in accordance with Appendix D as amended. ((
503.2.8 Angles of approach and departure. The angles of approach and departure for fire apparatus access roads shall be in accordance with the Seattle Right of Way Improvements manual. ((
503.3 Marking. Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING---FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the
obstruction thereof. The (( ***
503.6 Security gates. The installation of security gates across a fire apparatus access road shall be approved by the fire code official (( *** 505.1 Address identification. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall be a minimum of 4 inches (101.6 mm) high for Group R occupancies and a minimum of 5 inches for other occupancies with a minimum stroke width of 0.5 inch (12.7 mm). Where access is by means of a private road and the building cannot be viewed from the public way, a monument, pole or other sign or means shall be used to identify the structure. 505.2 Street or road signs. Streets and roads shall be identified with approved signs. Temporary signs shall be installed at each street intersection when construction of new roadways allows passage by vehicles. Signs shall be of an approved size, weather resistant and be maintained until replaced by permanent signs. 505.2 Point of Information Where marking is required, the signs shall be posted by the Seattle Department of Transportation for city streets and right-of-ways, and by the owners for private property. *** 506.1 Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. 506.1 Point of Information The fire code official has approved the "KnoxBox" as the access key box for use in the City of Seattle. For more information see Seattle Fire Department Information Bulletin #965 Key Boxes for Emergency Access. *** 506.3 Elevator key box. An elevator key box locked and keyed to the standard city elevator access key shall be provided. The elevator key box shall meet the following standards: 1. Dimensions -6.5 inches (165 mm) high, 6 inches (152 mm) wide and 2 inches (50 mm) deep. 2. Material -16 gauge steel welded. 3. Color -red unless located in the main lobby above the call button, six feet nominal above the floor, in which case any color is approved. 4. Labeling -"FOR EMERGENCY USE." 5. Lock -Ace 1-inch (25 mm) cylinder cam lock key #39504. The elevator key box is to be installed at the designated recall floor above the Phase I recall switch or in the main lobby above the hall call button when no recall feature exists. The elevator key box is to be mounted 6 feet (1829 mm) nominal above the floor. Other locations may be approved by the building official upon request, with notification to the fire code official. 506.3.1 Elevator keys. Keys for access to and for the operation of elevator equipment shall be tagged, labeled and retained in the key box. The elevator key box shall contain fire emergency service keys (Phase I and II, one key for each switch). The elevator key box may, in addition, contain keys for any or all of the following: 1. Machine room door; 2. Secondary level door; 3. Pit door; 4. Roof door; 5. Independent, hospital emergency and/or attendant operation; 6. Hoistway access; 7. Mechanical hoist access devices (broken arm, lunar, etc.); 8. Miscellaneous switch keys; 9. Fire alarm panel room; 10. Sprinkler valve control room 506.3.1 Point of Information Due to security consideration, elevator key boxes should not contain master keys to tenant spaces. Keys in elevator key boxes should be limited to those for access of the building systems and equipment listed in Seattle Fire Code, Section 506.3.1. SECTION 507 FIRE PROTECTION WATER SUPPLIES 507.1 Required water supply. An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction, and for buildings undergoing a substantial alteration as determined by the Department of Planning and Development. ***
507.3 Fire flow. Fire flow requirements for buildings or portions of buildings and facilities shall be in accordance with Appendix B. (( Exceptions: 1. Fire flow requirements for shipyards and designated marine hot work facilities shall be in accordance with Administrative Rule 26.02.09 and any future revisions to this rule adopted by the fire code official. 2. Fire flow requirements for new and existing covered marinas shall be in accordance with Chapters 45 and 94 respectively. ***
507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 500 feet (152 m) (( Exceptions: 1. For Group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m). 2. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet (183 m). *** 507.5.6 Physical protection. Where fire hydrants are subject to impact by a motor vehicle, guard posts or other approved means shall comply with Section 312. Any horizontal, lateral or diagonal elements that are a part of the protection for a fire hydrant shall not interfere with the ability to freely access and safely operate the hydrant. *** 508.1.5 Required features. The fire command center shall comply with NFPA 72 and shall contain the following features: 1. The emergency voice/alarm communication system control unit. 2. The fire department communications system. 3. Fire detection and alarm system annunciator. 4. Annunciator unit visually indicating the location of the elevators and whether they are operational. 5. Status indicators and controls for air distribution systems. 6. The fire-fighter's control panel required by Section 909.16 for smoke control systems installed in the building. 7. Controls for unlocking stairway doors simultaneously. 8. Sprinkler valve and water-flow detector display panels. 9. Emergency and standby power status indicators. 10. A telephone for fire department use with controlled access to the public telephone system. 11. Fire pump status indicators. 12. Schematic building plans indicating the typical floor plan and detailing the building core, means of egress, fire protection systems, fire-fighting equipment and fire department access, and the location of fire walls, fire barriers, fire partitions, smoke barriers and smoke partitions. 13. Work table.
((
1 15. Elevator fire recall switch in accordance with ASME A17.1. 16. Elevator emergency or standby power selector switch(es), where emergency or legally-required standby power is provided. 17. On-site fire protection water tank fill valve control switch, tank level indicators, tank low level alarm, and tank fill signal. *** 510.1 Emergency responder radio coverage in buildings. All buildings shall have approved radio coverage for emergency responders within the building based upon the existing coverage levels of the public safety communication systems of the jurisdiction at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. The system shall meet the requirements of Appendix J of this code. Exceptions: 1. Where approved by the building official and the fire code official, a wired communication system in accordance with Section 907.2.13.2 shall be permitted to be installed or maintained in lieu of an approved radio coverage system. 2. Where it is determined by the fire code official that the radio coverage system is not needed. 3. One and two family dwellings and townhouses. 4. Buildings constructed primarily of wood-frame (Type V) construction without below grade storage or parking areas. 5. Buildings that are 35 feet high (as defined by the Seattle Building Code Section 502) or less without below grade storage or parking areas.
((
((
((
510.((
((
(( Section 8. Chapter 6 of the 2009 International Fire Code is amended as follows: *** 601.1 Scope. The provisions of this chapter shall apply to the installation, operation and maintenance of fuel-fired appliances and heating systems, emergency and legally required standby power systems, electrical systems and equipment, mechanical refrigeration systems, elevator recall, stationary storage battery systems and commercial kitchen hoods.
601.2 Permits. Permits shall be obtained for refrigeration systems , (( *** 602.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. *** [M] HOOD. An air-intake device used to capture by entrapment, impingement, adhesion or similar means, grease and similar contaminants before they enter a duct system.
Type I. A kitchen hood for collecting and removing grease vapors and smoke(( Type II. A general kitchen hood for collecting and removing steam, vapor, heat, odors and products of combustion generated from some light-duty cooking appliances. ***
603.1 Installation. The installation of nonportable fuel gas appliances and systems shall comply with the International Fuel Gas Code. The installation and/or use of all other fuel-fired appliances, (( ***
603.1.3 Electrical wiring and equipment. Electrical wiring and equipment used in connection with (( ***
603.1.6 Testing, diagrams and instructions. After installation of the fuel fired appliance ((
603.1.6.1 Diagrams. Contractors installing Industrial fuel fired appliances (( ***
603.1.7 Clearances. Working clearances between (( *** 603.3 Fuel oil storage systems. Fuel oil storage systems shall be installed in accordance with Chapter 34 of this code. Fuel oil piping systems shall be installed in accordance with the International Mechanical Code. ***
[W] 603.4 Portable unvented heaters. Portable unvented fuel-fired heating equipment shall be prohibited in occupancies in Groups A, E, I, R-1, R-2, and R3(( Exceptions: 1. Listed and approved unvented fuel-fired heaters, including portable outdoor gas-fired heating appliances, in oneand two-family dwellings. 2. Portable outdoor gas-fired heating appliances shall be allowed in accordance with Section 603.4.2. *** 603.4.2.1.1 Prohibited locations. The storage or use of portable outdoor gas-fired heating appliances is prohibited in any of the following locations: 1. Inside of any occupancy when connected to the fuel gas container. 2. Inside of tents, canopies and membrane structures. 3. On exterior balconies.
Exception: As allowed in Section 6.1(( *** 603.4.2.2.5 Ignition sources. Smoking and openflame devices (e.g., candles, flaming food or beverage preparation) are prohibited within 5 feet (1524 mm) of any gas-fired heating appliance. "No Smoking" signs shall be posted at affected areas. 603.4.2.2.6 Fire extinguishers. At least one portable fire extinguisher having a minimum rating of 2A:40BC shall be provided and mounted with the top located no higher than 5 feet (1524 mm) above grade. Travel distance to the extinguisher shall not exceed 50 feet (15 240 mm). 603.4.2.2.7 Leaking gas. In the event of a gas leak or suspected leak, the container shall be immediately removed from the premises. Periodic leak tests (with the use of soapy water) shall be conducted by trained personnel to ensure the container and fittings are tight. 603.4.2.2.8 Means of egress. Drinking and dining areas where portable gas-fired heating appliances are used shall be provided with at least two means of egress.
603.4.2.3 Gas containers. Fuel gas containers for portable outdoor gas-fired heating appliances shall comply with Sections 603.4.2.3.1 through 603.4.2.3.(( *** 603.4.2.3.5 Outdoor Storage. Gas containers shall be located outside within lockable, ventilated metal storage lockers or racks in accordance with Sections 603.4.2.3.5.1 through 603.4.2.3.5.4. 603.4.2.3.5.1 Storage locker location. Ventilated metal storage lockers or racks shall be located at least 20 feet (6096 mm) from exits, building openings, public ways and designated smoking areas. Exception: For a Group A occupancy, the storage locker or rack may be located in accordance with Table 3809.12 but not less than 20 feet from the Group A occupancy. 603.4.2.3.5.2 Security of storage locker. Ventilated metal storage lockers or racks shall be secured against unauthorized entry. 603.4.2.3.5.3 Vehicle protection. Ventilated metal storage lockers for gas containers shall be protected from vehicular impact in accordance with Section 312 if subject to possible vehicle impact. 603.4.2.3.5.4 Container position. Gas containers shall be stored in an upright position such that the pressure relief valve is in direct contact with the vapor phase of the container. *** SECTION 604 EMERGENCY AND LEGALLY REQUIRED STANDBY POWER SYSTEMS
604.1 Installation. Except for the 2-hour on-premises fuel supply required for high-rise buildings in 604.2.14.1.1, (( *** 604.2 Where required. Emergency and legally required standby power systems shall be provided where required by Sections 604.2.1 through 604.2.18.4. ***
604.2.2 Smoke control systems. (( Exception: Legally required standby power is acceptable for shaft pressurization systems in low-rise buildings in accordance with Section 909.22. ***
604.2.5 Accessible means of egress elevators. Legally required ((
604.2.6 Accessible means of egress platform lifts. Legally required ((
604.2.7 Horizontal sliding doors. Legally required (( ***
604.2.9 Membrane structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 2403.12.6.1. Legally required (( 604.2.10 Hazardous materials. Emergency or legally required standby power shall be provided in occupancies with hazardous materials in accordance with Sections 2704.7 and 2705.1.5. ***
604.2.12 Organic peroxides. Legally required (( 604.2.13 Covered mall buildings. Covered mall buildings exceeding 50,000 square feet (4645 m2) shall be provided with legally required standby power systems which are capable of operating the emergency voice/alarm communication.
604.2.14 High-rise buildings. ((
604.2.14.1 (( Exception: A generator set with a fuel tank system not exceeding 660 gallons (2498.3 L) is not required to be located in a rated room if installed in a sprinklered parking garage of type I or II construction, unless a 1-hour separation is required to separate control areas in accordance with Table 2703.1.1(1). 604.2.14.1.1 Fuel supply. An on-premises fuel supply, sufficient for not less than 2-hour full-demand operation of the system, shall be provided.
((
604.2.14.1.2 Capacity. The ((
604.2.14.1.3 Emergency Power Loads. The following are classified as emergency power loads: (( 1. Exit signs and means of egress illumination required by Chapter 10. 2. Elevator car lighting. 3. Emergency voice/alarm communications systems. 4. Automatic fire detection systems. 5. Fire alarm systems. 6. Power and lighting for the fire command center. 7. Lighting for mechanical rooms. 8. Electrically powered fire pumps. 9. Ventilation and automatic fire detection equipment for pressurized stairways. 10. Smoke control systems. 11. A selected elevator in each bank in accordance with Seattle Building Code Section 3016.7. A bank of elevators is a group of elevators or a single elevator controlled by a common operating system---all elevators that respond to a single call button constitute a bank of elevators. All elevators shall be transferable to emergency power.
((
604.2.15 Underground buildings. Emergency and legally required standby power systems in underground buildings covered in Chapter 4 of the International Building Code shall comply with Sections 604.2.15.1((
604.2.15.1 ((
[B] 604.2.15.1.1 (( 1. Smoke control system.
2. Ventilation and automatic fire detection equipment for (( 3. Fire pumps.
4. (( 5. Emergency voice/alarm communication systems. 6. Fire alarm systems. 7. Automatic fire detection systems. 8. Elevator car lighting. 9. Means of egress lighting and exit sign illumination as required by Chapter 10.
((
*** 604.2.17 Airport traffic control towers. A legally required standby power system shall be provided in airport traffic control towers more than 65 feet (19 812 mm) in height. Power shall be provided to the following equipment: 1. Pressurization equipment, mechanical equipment and lighting. 2. Elevator operating equipment. 3. Fire alarm and smoke detection systems.
604.2.18 Elevators. In buildings and structures where ((
604.2.18.1 Manual transfer. ((
604.2.18.2 One elevator. Where only one elevator is installed, the elevator shall automatically transfer to ((
604.2.18.3 Two or more elevators. Where two or more elevators are controlled by a common operating system, all elevators shall automatically transfer to ((
604.2.18.4 Venting. Where (( 604.2.19 Refrigeration systems. If treatment, detection, continuous ventilation, or alarm systems are required for refrigeration systems, such systems shall be connected to a legally-required standby source of power to supply electrical power in the event of loss from the primary source. 604.3 Maintenance. Emergency and legally required standby power systems shall be maintained in accordance with NFPA 110 and NFPA 111 such that the system is capable of supplying service within the time specified for the type and duration required. 604.3.1 Schedule. Inspection, testing and maintenance of emergency and legally required standby power systems shall be in accordance with an approved schedule established upon completion and approval of the system installation.
604.3.2 Written record. Written records of the inspection, testing and maintenance of emergency and legally required standby power systems shall include the date of service, name of the servicing technician, a summary of conditions noted and a
detailed description of any conditions requiring correction and what corrective action was taken. Such records shall be kept on the premises served by the emergency or legally required standby power system and (( 604.3.3 Switch maintenance. Emergency and legally required standby power system transfer switches shall be included in the inspection, testing and maintenance schedule required by Section 604.3.1. Transfer switches shall be maintained free from accumulated dust and dirt. Inspection shall include examination of the transfer switch contacts for evidence of deterioration. When evidence of contact deterioration is detected, the contacts shall be replaced in accordance with the transfer switch manufacturer's instructions. 604.4 Operational inspection and testing. Emergency power systems, including all appurtenant components shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111. Exception: Where the emergency power system is used for legally required standby power or peak load shaving, such use shall be recorded and shall be allowed to be substituted for scheduled testing of the generator set, provided that appropriate records are maintained. ***
606.8 Refrigerant detector. Refrigeration machinery rooms required by the Seattle Mechanical Code shall contain a refrigerant detector with an audible and visual alarm. The detector, or a sampling tube that draws air to the detector,
shall be located in an area where refrigerant from a leak will concentrate. The alarm shall be actuated at a value not greater than the corresponding TLV-TWA values shown in the (( The system shall also comply with the mechanical ventilation requirements for emergency conditions in accordance with Seattle Mechanical Code Section 1105.6.4. *** 606.12.5 Flaring systems. Flaring systems for incineration of flammable refrigerants shall be designed to incinerate the entire discharge. The products of refrigerant incineration shall not pose health or environmental hazards. Incineration shall be automatic upon initiation of discharge, shall be designed to prevent blowback and shall not expose structures or materials to threat of fire. Standby fuel, such as LP gas, and legally required standby power shall have the capacity to operate for one and one-half the required time for complete incineration of refrigerant in the system. *** 606.17 Standby source of power required. When treatment, detection, continuous ventilation or alarm systems are required, such systems shall be connected to a legallyrequired standby source of power to supply electrical power in the event of loss of power from the primary source. See Section 604.2 and the Seattle Electrical Code Article 701. SECTION 607 ELEVATOR RECALL AND MAINTENANCE 607.1 Emergency operation. Existing elevators with a travel distance of 25 feet (7620 mm) or more shall comply with the requirements in Chapter 46. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1. Phase I recall shall be initiated on any activation of the building's fire alarm system. *** 608.1 Scope. Stationary storage battery systems having an electrolyte capacity of more than 50 gallons (189 L) for flooded lead-acid, nickel cadmium and VRLA, or 1,000 pounds (454 kg) for lithium-ion and lithium metal polymer, used for facility legally required standby power, emergency power or uninterrupted power supplies shall comply with this section and Table 608.1. *** [W] [M] 609.2 Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Exception: A Type I hood is not required to be installed in R-2 occupancies licensed by the State of Washington. [W] 609.3 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with Sections 609.3.1 through 609.3.4 and Chapter 11 of NFPA 96 . *** Section 9. Chapter 8 of the 2009 International Fire Code is amended as follows: *** 801.1 Scope. The provisions of this chapter shall govern interior finish, interior trim, furniture, furnishings, decorative materials and decorative vegetation in buildings. Existing buildings shall comply with Sections 803 through 808. New buildings shall comply with Sections 804 through 808 of this code and Section 803 of the International Building Code. ***
[W] 806.1.1 Restricted occupancies. Natural cut trees shall be prohibited in Group ((
((
[W] 806.1.2 Support devices. The support device that holds the tree in an upright position shall be of a type that is stable and that meets all of the following criteria: 1. The device shall hold the tree securely and be of adequate size to avoid tipping over of the tree.
2. The device shall be capable of containing a minimum (( 3. The water level, when full, shall cover the tree stem at least 2 inches (51 mm). The water level shall be maintained above the fresh cut and checked at least once daily. [W] TABLE 806.1.2 SUPPORT STAND WATER CAPACITY
806.1.3 Dryness. The tree shall be removed from the building whenever the needles or leaves fall off readily when a tree branch is shaken or if the needles are brittle and break when bent between the thumb and index finger or whenever determined necessary by the fire code official . The tree shall be checked daily for dryness. *** 807.2 Acceptance criteria and reports. Where required to be flame resistant, decorative materials shall be tested by an approved agency and meet the flame propagation performance criteria of NFPA 701 or other approved standard , or such materials shall be noncombustible. Reports of test results shall be prepared in accordance with NFPA701 and furnished to the fire code official upon request. 807.2 Point of Information Acceptable flame certificates for decorative materials include: 1. Certificates indicating compliance with NFPA 701. 2. Certificates verifying approval through the California State Fire Marshal. 3. Certificates indicating compliance with CPAI-84 (Canvas Products Association International). *** SECTION 809 DECORATIVE MATERIALS USED IN TEMPORARY ASSEMBLY OCCUPANCIES 809.1 General. Combustible decorative materials used in temporary assembly occupancies shall be flame resistant as determined by the fire code official. Exceptions: 1. The display of salable goods. 2. Educational materials and product brochures that are stored, distributed and maintained in an approved manner. 3. Live vegetation of an approved type. *** Section 10. Chapter 9 of the 2009 International Fire Code is amended as follows: *** 901.4.5 Certification. Individuals who install, inspect, test or maintain fire protection systems shall obtain the proper certificate from the fire code official in accordance with Administrative Rule 9.01.09, Certification for Installing, Maintaining and Testing Life Safety Systems and Equipment and any future revisions of this rule adopted by the fire code official. Exception: Individuals who install, inspect, test, or maintain single and multiple station smoke alarms. ***
901.5.1 Occupancy. It shall be unlawful to occupy any portion of a building or structure until the systems required ((
901.6 Inspection, testing and maintenance. Fire detection(( 901.6.1 Confidence Test: All Fire protection systems, including nonrequired systems, shall be confidence tested in accordance with the Administrative Rule 9.02.09 Confidence Test Requirements for Life Safety Systems and any future revisions of this rule adopted by the fire code official. Exceptions: 1. NFPA 13D sprinkler systems 2. Single and multiple station smoke alarms 3. Fire hydrants and fire service mains
901.6. 2 ((
901.6. 3 ((
901.6. 3 ((
901.7 Systems out of service. Where a ((
*** 901.10 Cabinets. Cabinets containing fire-fighting equipment, such as standpipes, fire hose, fire extinguishers or fire department valves, shall not be blocked from use or obscured from view. 901.10.1 Cabinet equipment identification. Cabinets shall be identified in an approved manner by a permanently attached sign with letters not less than 2 inches (51 mm) high in a color that contrasts with the background color, indicating the equipment contained therein. Exceptions: 1. Doors not large enough to accommodate a written sign shall be marked with a permanently attached pictogram of the equipment contained therein. 2. Doors that have either an approved visual identification clear glass panel or a complete glass door panel. 901.10.2 Locking cabinet doors. Cabinets shall be unlocked. Exceptions: 1. Visual identification panels of glass or other approved transparent frangible material that is easily broken and allows access. 2. Approved locking arrangements. 3. Group I-3 occupancies. *** 902.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. *** FIRE DETECTION SYSTEM. A system of smoke or heat detectors monitored at an approved central station, with no requirement for notification appliances in the building. *** HIGH-RISE BUILDING. Buildings having occupied floors located more than 75 feet ( 22 860 mm) above the lowest level of fire department vehicle access. *** PORTABLE SCHOOL CLASSROOM. A structure, transportable in one or more sections, that requires a chassis to be transported, and that is designed to be used as an educational space with or without a permanent foundation. The structure shall be trailerable and capable of being demounted and relocated to other locations as needs arise. *** 903.2.1.2 Group A-2. An automatic sprinkler system shall be provided for Group A-2 occupancies where one of the following conditions exists: 1. The fire area exceeds 5,000 square feet (464m2). 2. The fire area has an occupant load of 100 or more. 3. The fire area is located on a floor other than a level of exit discharge serving such occupancies. Exception: Item 3 above does not apply to fire areas that include space located one floor above the level of exit discharge if the occupant load of the upper floor is less than 50. *** 903.2.1.6 Nightclub. An automatic sprinkler system shall be provided throughout nightclubs. Any space to be constructed for, used for, or converted to, occupancy as a nightclub shall provide an automatic sprinkler system as required by this section. ***
903.2.3 Group E. An automatic sprinkler system shall be provided for Group E occupancies . ((
Exceptions: 1. Portable school classrooms, if the aggregate area of any cluster of portable school classrooms does not exceed 5,000 square feet (1465 m2); and clusters of portable school classrooms shall be separated as required in Chapter 5 of the Seattle Building Code. 2. Group E occupancies with an occupant load of 50 or less. *** 903.2.7 Group M. An automatic sprinkler system shall be provided throughout buildings containing a Group M occupancy where one of the following conditions exists: 1. A Group M fire area exceeds 12,000 square feet (1115 m2). 2. A Group M fire area is located more than three stories above grade plane. 3. The combined area of all Group M fire areas on all floors, including any mezzanines, exceeds 24,000 square feet (2230 m2). 4. A Group M occupancy that is used for the display and sale of mattresses and upholstered furniture and the display area exceeds 5,000 square feet (464 m2) . *** 903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area. Exception: Buildings complying with the Seattle Residential Code and Chapter 5 of this code are not required to be sprinklered. *** 903.2.9.3 Liquor Warehouses. An automatic sprinkler system shall be installed in liquor warehouses. 903.2.9.3 Point of Information Stockrooms of retail liquor sales outlets are not liquor warehouses. *** 903.2.11.7 Basement storage and sale of combustible materials. An automatic sprinkler system shall be installed throughout basements that are not stories above grade plane that are used for storage or sale of combustible materials. Exceptions: 1. Sprinklers are not required in portions of the basement not containing combustible materials and protected by a fire barrier with at least a one-hour fire-resistance rating. 2. Sprinklers are not required in storage rooms meeting the following criteria: 2.1. The area of the room does not exceed 500 square feet (46.5 m2); 2.2. The room is protected by a fire barrier with at least a one-hour fire-resistance rating; 2.3. The room contains no material classified as a flammable liquid, hazardous material or highly combustible material; 2.4. The room is served by exterior fire access or interior access by a one-hour fire-resistance rated corridor; 2.5. No more than three such rooms are permitted in any one basement. 903.2.11.8 Covered boat moorage. Automatic sprinklers shall be provided for covered boat moorage exceeding 500 square feet (46.5m2) in projected roof area per pier, wharf or float. The sprinkler system shall be designed and installed in accordance with NFPA 13 for Extra Hazard Group 2 occupancy. If sprinklers are required by this section for covered moorage, any other structure exceeding 500 square feet (46.5 m2) in projected roof area on the pier, wharf or float is also required to be sprinklered. ***
903.3.1 Standards. Sprinkler systems shall be designed and installed in accordance with Sections 903.3.1.1 unless otherwise permitted by Sections(( 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1 and Administrative Rule 9.03.09, Automatic Sprinkler and Standpipe Systems, and any future revisions of this rule adopted by the fire code official . 903.3.1.1.1 Exempt locations. Automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire-resistance rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard, if approved by the fire code official. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the fire code official.
3. (( 4. Rooms or areas that are of noncombustible construction with wholly noncombustible contents. 5. Fire service access elevator machine rooms and machinery spaces. 903.3.1.1.2 High-rise building sprinkler system design. In high-rise buildings, combination standpipe/sprinkler risers using 6 inch pipe minimum shall be used with the sprinkler system connected between standpipe risers. Shut-off valves, water-flow devices and check valves (or pressure reducing valves) shall be provided on each floor at the sprinkler system connection to each standpipe. Two four-way fire department connections serving the combination system shall be provided on separate streets well separated from each other. At least one of the fire department connections shall be connected to the riser above a riser isolation valve. Also see section 905.3.6. When a mid-level fire pump is required by NFPA 14 two pumps with the same rating shall be installed. Dry-pipe sprinkler systems serving parking garages may use a single supply and one separate two-way fire department connection. The dry-pipe sprinkler system shall be supplied by the on-site water tank.
903.3.1.2 NFPA 13R sprinkler systems. (( ***
903.3.1.3 NFPA 13D sprinkler systems. (( ***
903.3.3 Obstructed locations. Automatic sprinklers shall be installed in accordance with NFPA 13 obstruction criteria and the listing requirements of the sprinkler head. (( Exception: Kitchen equipment under exhaust hoods protected with a fire-extinguishing system in accordance with Section 904. 903.3.4 Actuation. Automatic sprinkler systems shall be automatically actuated unless specifically provided for in this code. Exception: Elevator machine rooms and machinery spaces in accordance with Administrative Rule 9.08.05, Sprinkler Systems and Fire Alarms for Elevator Machinery Rooms, Hoist Ways and Pits and any future revisions of this rule adopted by the fire code official. ***
903.3.5.1 Domestic services. Both NFPA 13R and NFPA 13D sprinkler systems can be supplied by a domestic service (( ***
903.3.5. 2 (( 903.3.5.3 Fire Service A fire service shall be allowed for all types of sprinkler systems.
903.3.5. 4 (( Exception: Existing buildings, including those undergoing a substantial renovation. *** 903.4 Sprinkler system supervision and alarms. All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and water-flow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit. Exceptions: 1. Automatic sprinkler systems protecting oneand two family dwellings and, if approved by the fire code official, townhouses. 2. Limited area systems serving fewer than 20 sprinklers. 3. Automatic sprinkler systems installed in accordance with NFPA 13R where a common supply main is used to supply both domestic water and the automatic sprinkler system, and a separate shutoff valve for the automatic sprinkler system is not provided. 4. Jockey pump control valves that are sealed or locked in the open position. 5. Control valves to commercial kitchen hoods, paint spray booths or dip tanks that are sealed or locked in the open position. 6. Valves controlling the fuel supply to fire pump engines that are sealed or locked in the open position. 7. Trim valves to pressure switches in dry, preaction and deluge sprinkler systems that are sealed or locked in the open position. 903.4.1 Monitoring. Alarm, supervisory and trouble signals shall be distinctly different and shall be automatically transmitted to a central station service that is listed in the current edition of the Underwriters Laboratories FIRE PROTECTION EQUIPMENT DIRECTORY under the category Central Station (UUFX) as a Full Service Company or as a Monitoring Company.
Fire alarm systems in high-rise buildings and Group I and Group A occupancies (other than A-5) shall be monitored by a central station service that is listed in the current edition of the Underwriters Laboratories FIRE PROTECTION EQUIPMENT DIRECTORY
under the category Central Station (UUFX) as a Full Service Company or as a Fire Alarm Service--Local Company that subcontracts the monitoring, retransmission and associated record keeping and reporting to a listed Full Service Company or Monitoring
Company. The listing shall indicate that the Full Service Company or Fire Alarm Service -Local Company provides service to the Seattle area. (( Exceptions: 1. Underground key or hub valves in roadway boxes or any valve in underground vaults provided by the municipality or public utility are not required to be monitored. 2. Backflow prevention device test valves located in limited area sprinkler system supply piping shall be locked in the open position. In occupancies required to be equipped with a fire alarm system, the backflow preventer valves shall be electrically supervised by a tamper switch installed in accordance with NFPA 72 and separately annunciated. *** 903.4.3 Floor control valves. Approved supervised indicating control valves shall be provided at the point of connection to the riser on each floor in high-rise buildings , and at the point of connection to the riser on any combination sprinkler/standpipe riser in any building . *** 903.6.3 Nightclub. Existing nightclubs shall be provided with an automatic sprinkler system as required by Section 4603.4.3. *** 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and NFPA 14 , and Administrative Rule 9.03.09, Automatic Sprinklers and Standpipes and any future revisions of this rule adopted by the fire code official. 905.3 Required installations. Standpipe systems shall be installed where required by Sections 905.3.1 through 905.3.7 and in the locations indicated in Sections 905.4, 905.5 and 905.6. Standpipe systems are allowed to be combined with automatic sprinkler systems. Exception: Standpipe systems are not required in Group R3 occupancies and townhouses . ***
((
905.3. 2 (( 1. Within the mall at the entrance to each exit passageway or corridor. 2. At each floor-level landing within enclosed stairways opening directly on the mall. 3. At exterior public entrances to the mall. 4. At other locations as necessary so that the distance to reach all portions of a tenant space does not exceed 200 feet (60 960 mm) from a hose connection.
((
905.3. 3 ((
905.3. 4 ((
905.3. 5 (( 905.3.6 High-rise building standpipes. Standpipe risers in high-rise buildings shall be combination standpipe/sprinkler risers using a minimum pipe size of 6 inches (152 mm). Two 21/2-inch (64 mm) hose connections shall be provided on every floor level landing in every required stairway. If pressure reduction valves (prv) are required, each hose connection shall be provided with its own prv. The system shall be designed to provide a minimum flow of 300 gpm (19 L/s) at a minimum pressure of 150 psi (1034 kPa) [maximum 205 psi (1379 kPa)] at each standpipe connection, in addition to the flow and pressure requirements contained in NFPA 14. Also see section 903.3.1.1.2 905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations:
1. In every required stairway, a hose connection shall be provided for each floor level above or below grade. Hose connections shall be located at an intermediate floor level landing between floors, or the main floor landing, but must be
consistent throughout a building. (( 2. On each side of the wall adjacent to the exit opening of a horizontal exit. Exception: Where floor areas adjacent to a horizontal exit are reachable from exit stairway hose connections by a 30-foot (9144 mm) hose stream from a nozzle attached to 100 feet (30 480 mm) of hose, a hose connection shall not be required at the horizontal exit. 3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. Exception: Where floor areas adjacent to an exit passageway are reachable from exit stairway hose connections by a 30-foot (9144 mm) hose stream from a nozzle attached to 100 feet (30 480 mm) of hose, a hose connection shall not be required at the entrance from the exit passageway to other areas of the building.
4. In covered mall buildings, adjacent to each exterior public entrance to the mall, ((
5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), ((
6. Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) of hose travel distance from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960
mm) of hose travel distance from a hose connection, additional hose connections shall be provided that are accessed through protected enclosures. The protected enclosure shall be a corridor constructed as a smoke barrier from the exit
enclosure to the standpipe connection. Additional hose connections in parking garages are not required to be accessed through or located in protected enclosures. (( ***
((
905.5. 1 ((
905.5. 2 (( ***
((
905. 7 (( Exception: Where subject to freezing and in accordance with NFPA 14.
905. 8 (( Exceptions:
1. Valves (( 2. Valves locked in the normal position and inspected as provided in this code in buildings not equipped with a fire alarm system and/or not provided with monitoring by a central station service.
905. 9 ((
905. 10 (( SECTION 906 PORTABLE FIRE EXTINGUISHERS 906.1 Where required. Portable fire extinguishers shall be installed in the following locations.
1. In new and existing Group A, B, E, F, H, I, M, R-1, R2, ((
(( 2. Within 30 feet (9144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1. 5. Where required by the sections indicated in Table 906.1. 6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10 by individuals who possess the proper certificate from the fire code official in accordance with Administrative Rule 9.01.09 Certification for Installing, Maintaining and Testing Life Safety Systems and Equipment and any future revisions of this rule adopted by the fire code official. Exceptions: 1. The travel distance to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies. 2. Thirty-day inspections shall not be required and maintenance shall be allowed to be once every three years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device, provided that all of the following conditions are met: 2.1. Electronic monitoring shall confirm that extinguishers are properly positioned, properly charged and unobstructed. 2.2. Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal. 2.3. The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4. Electronic monitoring devices and supervisory circuits shall be tested every three years when extinguisher maintenance is performed. 2.5. A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10. 3. In Group I-3, portable fire extinguishers shall be permitted to be located at staff locations. *** SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing buildings and structures
The requirements of Section 907.2 are applicable to new buildings and structures. The requirements of Section 907.3 are applicable to existing buildings and structures. All fire alarm and fire detection systems shall be designed, installed and
maintained in accordance with the requirements of NFPA 72, except for the locations of initiating devices which shall comply with Section 907 of the Seattle Fire Code. For the purposes of Buildings required by this section to be provided with a fire alarm system shall be provided with a single fire alarm system. Exception: A single system is not required in existing buildings that are being increased in size and the existing fire alarm system is unable to expand into the new space. In those cases multiple systems shall be arranged as described below for nonrequired fire alarm systems. Buildings not required by this section to be provided with a fire alarm system may be provided with multiple partial fire alarm systems if: 1. The systems are connected so that all systems simultaneously activate alarm notification appliances upon a signal from any of the fire alarm systems in the building, and 2. The location of each system's annunciator panel (or main panel) is also provided with annunciator panels with reset capability for every other system in the building. *** 907.2.2 Group B. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in Group B occupancies where one of the following conditions exists: 1. The combined Group B occupant load of all floors is 500 or more. 2. The Group B occupant load is more than 100 persons above or below the lowest level of exit discharge. 3. The Group B fire area contains a Group B ambulatory health care facility. Exception: Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 and the occupant notification appliances will activate throughout the notification zones upon sprinkler water flow. ***
((
[W] 907.2.8 Group R-1. Fire alarm systems (( 907.2.8.1 Manual fire alarm system. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in Group R-1 occupancies.
Exception((
((
((
907.2.8.2 Automatic (( Exception: An automatic smoke detection system is not required in buildings that do not have interior corridors serving sleeping units and where each sleeping unit has a means of egress door opening directly to an exit or to an exterior exit access that leads directly to an exit. 907.2.8.3 Smoke alarms. Singleand multiple-station smoke alarms shall be installed in accordance with Section 907.2.11. 907.2.8.4 Carbon monoxide alarms. For new construction, an approved carbon monoxide alarm shall be installed by January 1, 2011, outside of each separate sleeping area in the immediate vicinity of the bedroom in dwelling and sleeping units. For studio type units that do not have a bedroom or a sleeping area separate from the unit itself, the carbon monoxide alarm shall be placed inside the sleeping or dwelling unit in the vicinity of the sleeping area. In a building where a tenancy exists, the tenant shall maintain the CO alarm as specified by the manufacturer including replacement of the batteries. [W] 907.2.8.4.1 Existing sleeping units. Existing sleeping units shall be equipped with carbon monoxide alarms by July 1, 2011. 907.2.8.4.2 Alarm requirements. Single station carbon monoxide alarms listed as complying with UL 2034 shall be installed in accordance with NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment and the manufacturer's installation instructions.
907.2.9 Group R-2. Fire alarm systems , (( 907.2.9.1 Manual fire alarm system. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.6 shall be installed in Group R-2 occupancies where: 1. Any dwelling unit or sleeping unit is located three or more stories above the lowest level of exit discharge; 2. Any dwelling unit or sleeping unit is located more than one story below the highest level of exit discharge of exits serving the dwelling unit or sleeping unit; or 3. The building contains more than 16 dwelling units or sleeping units. [W] 4. The building contains a boarding home licensed by the state of Washington. Exceptions: 1. A fire alarm system is not required in buildings not more than two stories in height where all dwelling units or sleeping units and contiguous attic and crawl spaces are separated from each other and public or common areas by at least 1-hour fire partitions and each dwelling unit or sleeping unit has an exit directly to a public way, exit court or yard.
2. A fire alarm system is not required in townhouses if approved by the fire code official. (( 3. A fire alarm system is not required in buildings that do not have interior corridors serving dwelling units and are protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, provided that dwelling units either have a means of egress door opening directly to an exterior exit access that leads directly to the exits or are served by open-ended corridors designed in accordance with Section 1026.6, Exception 4. [W] 4. In boarding homes licensed by the state of Washington, manual fire alarm boxes in resident sleeping areas are not required at exits if located at all constantly attended staff locations, if such staff locations are visible, continuously accessible, located on each floor, and positioned so no portion of the story exceeds a horizontal travel distance of 200 feet to a manual fire alarm box. 907.2.9.2 Smoke alarms. Singleand multiple-station smoke alarms shall be installed in accordance with Section 907.2.11. 907 .2.9.3 Automatic heat detection. An automatic heat detection system that activates the occupant notification system in accordance with Section 907.6 shall be installed throughout all unsprinklered interior areas outside dwelling units other than attics and crawl spaces. [W] 907.2.9.4 Carbon monoxide alarms. For new construction, an approved carbon monoxide alarm shall be installed by January 1, 2011, outside of each separate sleeping area in the immediate vicinity of the bedroom in dwelling and sleeping units. For studio type units that do not have a bedroom or a sleeping area separate from the unit itself, the carbon monoxide alarm shall be placed inside the sleeping or dwelling unit in the vicinity of the sleeping area. In a building where a tenancy exists, the tenant shall maintain the CO alarm as specified by the manufacturer including replacement of the batteries. [W] 907.2.9.4.1 Existing dwelling units. Existing dwelling units shall be equipped with carbon monoxide alarms by July 1, 2011. [W] 907.2.10 Group R-3. Carbon monoxide alarms shall be installed in Group R-3 occupancies as required in Sections 907.2.10.1 through 907.2.10.3. [W] 907.2.l0.1 Carbon monoxide alarms. For new construction, an approved carbon monoxide alarm shall be installed by January 1, 2011, outside of each separate sleeping area in the immediate vicinity of the bedroom in dwelling units. In a building where a tenancy exists, the tenant shall maintain the CO alarm as specified by the manufacturer including replacement of the batteries. [W] 907.2.10.2 Existing dwelling units. Existing dwelling units shall be equipped with carbon monoxide alarms by July 1, 2011. Exception: Owner-occupied Group R-3 residences legally occupied prior to July 1, 2010. 907.2.10.3 Alarm requirements. Single station carbon monoxide alarms listed as complying with UL 2034 shall be installed in accordance with NFPA 720, Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment and the manufacturer's installation instructions.
((
***
907.2.11.2 Groups R-2, R-3, (( 1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms. 2. In each room used for sleeping purposes. Exception: Singleor multiple-station smoke alarms in Group I-1 shall not be required where smoke detectors are provided in the sleeping rooms as part of an automatic smoke detection system. 3. In each story within a dwelling unit, including basements but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
907.2.11.3 Interconnection. Where more than one smoke alarm is required to be installed within an individual dwelling unit or sleeping unit in Group R-1, R2(( *** 907.2.13 High-rise buildings. Buildings with a floor used for human occupancy located more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall be provided with an automatic smoke detection system in accordance with Section 907.2.13.1, a fire department communication system in accordance with Section 907.2.13.2 and an emergency voice/alarm communication system in accordance with Section 907.6.2.2. Exceptions: 1. Airport traffic control towers in accordance with Section 907.2.22 and Section 412 of the International Building Code. 2. Open parking garages in accordance with Section 406.3 of the International Building Code. 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code. 4. Low-hazard special occupancies in accordance with Section 503.1.1 of the International Building Code.
((
5. (( 907.2.13.1 Automatic smoke detection. Automatic smoke detection in high-rise buildings shall be in accordance with Sections 907.2.13.1.1 and 907.2.13.1.2. 907.2.13.1.1 Area smoke detection. Area smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector , other than duct smoke detectors, required by this section shall operate the emergency voice/alarm communication system in accordance with Section 907.6.2.2. Smoke detectors shall be located as follows: 1. In each mechanical equipment, electrical, transformer, telephone equipment or similar room which is not provided with sprinkler protection. 2. In each elevator machine room and in elevator lobbies. 3. Within 5 feet (1524 mm) of doors exiting into stairways that are smokeproof enclosures, or that are pressurized stairways. Exception: If such locations are within parking garages, smoke detectors are not required. 907.2.13.1.2 Duct smoke detection. Duct smoke detectors complying with Section 907.4.1 shall be located as follows: 1. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet. 2. At each connection to a vertical duct or riser serving two or more stories from a return air duct or plenum of an air-conditioning system. In Group R-1 and R-2 occupancies, a smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air-inlet openings. 3. Two smoke detectors are required for stair and elevator shaft pressurization air intakes arranged to automatically shut down the pressurization fans only when both detectors activate. The detectors shall be located downstream of each fan and shall be connected to the fire alarm as a supervisory signal. 907.2.13.2 Fire department communication system. Where a wired communication system is approved in lieu of a radio coverage system in accordance with Section 510, the wired fire department communication system shall be designed and installed in accordance with NFPA 72 and shall operate between a fire command center complying with Section 508, elevators, elevator lobbies, emergency and standby power rooms, fire pump rooms, areas of refuge and inside enclosed exit stairways. The fire department communication device shall be provided at each floor level within the enclosed exit stairway. Eight portable handsets for the communication system shall be provided in the fire command center. *** 907.2.18.1 Smoke detectors. A minimum of one smoke detector listed for the intended purpose shall be installed in the following areas: 1. Mechanical equipment, electrical, transformer, telephone equipment, elevator machine or similar rooms. 2. Elevator lobbies. 3. The main return and exhaust air plenum of each air-conditioning system serving more than one story and located in a serviceable area downstream of the last duct inlet. 4. Each connection to a vertical duct or riser serving two or more floors from return air ducts or plenums of heating, ventilating and air-conditioning systems, except that in Group R occupancies, a listed smoke detector is allowed to be used in each return air riser carrying not more than 5,000 cfm (2.4 m3/s) and serving not more than 10 air inlet openings. 5. Within 5 feet (1524 mm) of doors exiting into staiways that are smokeproof enclosures, or that are pressurized stairways . Exception: If such locations are within parking garages, smoke detectors are not required. 6. Two smoke detectors are required for stair and elevator shaft pressurization air intakes, arranged to automatically shut down the pressurization fans only when both detectors activate. The detectors shall be located downstream of each fan and shall be connected to the fire alarm as a supervisory signal. *** 907.4.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection and shall not activate the occupant notification system . Exceptions: 1. The supervisory signal at a constantly attended location is not required where duct smoke detectors activate the building's alarm notification appliances. 2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble. ***
907.4.3 Elevator emergency operation. Automatic fire detectors installed for elevator emergency operation shall be installed in accordance with the provisions of (( *** 907.6 Occupant notification systems. A fire alarm system shall annunciate at the panel and shall initiate occupant notification upon activation, in accordance with Sections 907.6.1 through 907.6.2.3.4. Where a fire alarm system is required by another section of this code, it shall be activated by: 1. Automatic fire detectors, other than duct smoke detectors and smoke alarms located inside dwelling units and sleeping units . 2. Sprinkler waterflow devices. 3. Manual fire alarm boxes. 4. Automatic fire-extinguishing systems. Exception: Where notification systems are allowed elsewhere in Section 907 to annunciate at a constantly attended location. *** 907.6.2.1.1 Average sound pressure. The audible alarm notification appliances shall provide a sound pressure level of 15 decibels (dBA) above the average ambient sound level or 5 dBA above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupiable space within the building , or in the case of a partial alarm system, throughout the space that is being provided with the fire alarm system. The minimum sound pressure levels shall be: 75 dBA in occupancies in Groups R and I-1; 90 dBA in mechanical equipment rooms; and 60 dBA in other occupancies. In assembly occupancies with high sound levels such as nightclubs and bars, an interface shall be provided between the fire alarm system and the noise source to eliminate the noise source upon activation of the fire alarm system. Exceptions: 1. Private mode signaling in accordance with NFPA 72 is allowed in areas of Group I-2 and I -3 occupancies if occupants are not expected to self evacuate. 2. Audibility is not required for fire detection systems monitored by an approved central station in buildings not required by this section to be provided with a fire alarm system. ***
907.6.2.2 Emergency voice/alarm communication systems. Emergency voice/alarm communication systems required by this code shall be designed and installed in accordance with NFPA 72. The operation of any automatic fire detector, sprinkler waterflow device
or manual fire alarm box shall automatically sound an alert tone followed by voice instructions giving approved information and directions for a general or staged evacuation in accordance with the building's fire safety and evacuation plans required by
Section 404. In high-rise buildings, the system shall operate on a minimum of the alarming floor, the floor above and (( 1. Elevator groups.
2. Each (( 3. Each floor. 4. Areas of refuge as defined in Section 1002.1. Exception: In Group I-1 and I-2 occupancies, the alarm shall sound in a constantly attended area and a general occupant notification shall be broadcast over the overhead page. *** 907.6.2.3 Visible alarms. Visible alarm notification appliances shall be provided in accordance with Sections 907.6.2.3.1 through 907.6.2.3.4, and Administrative Rule 9.09.07, Visible Alarm Notification Devices and any future revisions of this rule adopted by the fire code official. Exceptions: 1. Visible alarm notification appliances are not required in alterations, except where an existing fire alarm system is upgraded or replaced, or a new fire alarm system is installed. 907.6.2.3 Point of Information See Administrative Rule 9.09.07, Visible Alarm Notification Devices and any future revisions of this rule adopted by the fire code official for clarification of terms upgraded and replaced. 2. Visible alarm notification appliances shall not be required in exits as defined in Section 1002.1. 3. Visible alarm notification appliances shall not be required in elevator cars. ***
907.7.3.1 (( *** 907.7.5 Monitoring. Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72. Exception: Monitoring by a supervising station is not required for: 1. Singleand multiple-station smoke alarms required by Section 907.2.11. 2. Smoke detectors in Group I-3 occupancies. 3. Automatic sprinkler systems in oneand two-family dwellings and townhouses . *** 907.8 Acceptance tests and completion. Upon completion of the installation, and after the electrical inspector has signed-off the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72, in the presence of the fire code official, by individuals who possess the proper certificate from the fire code official in accordance with Administrative Rule 9.01.09 Certification for Installing Maintaining, and Testing Life Safety Systems and Equipment and any future revisions of this rule adopted by the fire code official. 907.8.1 Singleand multiple-station alarm devices. When the installation of the alarm devices is complete, each device and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the smoke alarm provisions of NFPA 72. *** 907.10 Resetting fire alarm equipment. Fire alarm equipment shall be reset upon activation only by fire department personnel. Exception: If approved by the fire code official. ***
909.11 Power systems. The smoke control system shall be supplied with two sources of power. Primary power shall be from the normal building power systems. Secondary power shall be from an approved emergency (( Exception: A generator set with a diesel fuel tank system exceeding 660 gallons is not required to be located in a rated room if installed in a sprinklered parking garage of type I or II construction, unless a 1hour separation is required to separate control areas in accordance with Table 2703.1.1(3). *** 909.11.2 Wiring. In addition to meeting requirements of the Seattle Electrical Code, all wiring regardless of voltage, shall have fire-resistance-rated protection of at least two hours or as required in rules promulgated by the building official. Exception: Subject to the approval of the building official, fire-resistance rating is not required for wiring located in a parking garage. ***
909.12.1 Wiring. See section 909.11.2. (( *** 909.16 Fire-fighter's smoke control panel. A fire-fighter's smoke control panel for fire department emergency response purposes only shall be provided and shall include manual control or override of automatic control for mechanical smoke control systems. The panel shall be located in a fire command center complying with Section 508 in high-rise buildings or buildings with smoke-protected assembly seating. In all other buildings, the fire-fighter's smoke control panel shall be installed in an approved location adjacent to the fire alarm control panel. The fire-fighter's smoke control panel shall comply with Sections 909.16.1 through 909.16.3. The smoke control panel for high rise buildings shall include a visual depiction of the building showing typical floor plan(s) with locations of exit enclosures and elevator shafts. The panel shall also include section views of the building to show the extent of travel for each exit enclosure and elevator. Exit enclosures and elevator shafts shall be labeled on the plan section views to match the labeling used in the building itself.
909.16.1 Smoke control systems. Fans within the building shall be shown on the fire-fighter's control panel. Fan control switches shall be located on the panel in the vicinity of the location where the shaft supplied by each fan is depicted. A
clear indication of the direction of airflow and the relationship of components shall be displayed. Status indicators shall be provided for all smoke control fans , ((
1. Fans in a ready/non-operating status ((
2. Fans ((
3. Fans in operation ((
4. Fans (( 909.16.2 Smoke control panel. The fire-fighter's control panel shall provide control capability over the complete smoke-control system equipment within the building as follows:
1. ON-AUTO-OFF control over each shaft pressurization fan. ((
2. AUTO-OFF-POSITIVE PRESSURE-NEGATIVE PRESSURE control of each smoke control zone designed with such features. Individual control of each damper and fan used to achieve the positive or negative pressure condition is not required.
((
3. AUTO-EXHAUST-OFF control of each smoke exhaust zone using the exhaust method of smoke control. ((
Exception((
1. Complex exhaust systems using multiple exhaust fans and/or zones may require individual fan control if required by the fire code official. ((
*** 909.18.8 Special inspections for smoke control. Smoke control systems shall be tested by a special inspector for compliance with the approved plans. 909.18.8.1 Scope of testing. Special inspections shall be conducted in accordance with the following:
((
1(( *** [B] 909.21 Smokeproof enclosures. Where required by Section 1022.9, a smokeproof enclosure shall be constructed in accordance with Sections 909.10 through 909.21. A smokeproof enclosure shall consist of an enclosed interior exit stairway that conforms to Section 1022.1 and is pressurized according to the requirements of this section. Where access to the roof is required by this code, such access shall be from the smokeproof enclosure where a smokeproof enclosure is required. [B] 909.21.1 Stairway pressurization Exit stairways shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a maximum of 0.35 inches of water (87 Pa) in the shaft relative to the building measured with all stairway doors closed under maximum anticipated conditions of stack effect and wind effect. The pressure differential shall be measured between the exit enclosure and the adjacent area. In residential buildings, the pressure differential is permitted to be measured between the exit enclosure and the dwelling units. Exception: The pressure differential is permitted to be measured relative to outdoor atmosphere on floors other than the following: 1. the fire floor, 2. the two floors immediately below the fire floor, and 3. the floor immediately above the fire floor. [B] 909.21.1.1 Supply Air. Air for stairway pressurization shall be supplied at intervals sufficient to maintain the required pressure throughout the exit enclosure.
[B] 909.21.1.2 Supply air. Supply air shall be taken directly from an outside, uncontaminated source at least 20 feet (6096 mm) from any air exhaust system or outlet. The supply air intake shall be located at the exterior of the building. The intake shall be continuous to the exterior of the building. The fan system shall be equipped with two smoke detectors located in the duct in accordance with NFPA 72 arranged to automatically shut down the fan system only when both smoke detectors activate. The detectors shall be located downstream of the fan and shall be connected to the fire alarm as a supervisory signal. [B] 909.21.1.3 Dampered relief opening. The exit enclosure shall be equipped with a relief opening at the top. The relief opening shall be equipped with a barometric relief damper and a motorized damper that complies with the Washington State Energy Code with Seattle Amendments. The motorized damper shall be of the normally open type (open with the power off). Activation of the damper shall be initiated by the building fire alarm system and by actuation of the automatic sprinkler system. The pressurization system shall be capable of maintaining the differential pressure required by Section 909.21.1 while discharging 2,500 cubic feet per minute (1180 L/s) of air through the relief opening. The relief outlet shall be located at least 20 feet from elevator hoistway and stairway pressurization system supply air intake locations. [B] 909.21.2 Pressurization equipment. The pressurization equipment required by Section 909.21.1 shall be activated by a fire alarm signal origination anywhere in the building. Smoke detectors shall be installed in accordance with Section 907.3. [B] 909.21.2.1 Pressurization systems. Stairway pressurization systems shall be independent of other building ventilation systems. Exception: Ventilation systems other than exit enclosure supply air systems are permitted to be used to exhaust air from adjacent space when necessary to maintain the differential pressure relationships. Ventilation systems used to achieve stairway pressurization are not required to comply with Section 909. The equipment, control wiring, power wiring and ductwork shall comply with one of the following: 1. Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the exit enclosure or connected to the exit enclosure by ductwork enclosed by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712 of the Seattle Building Code, or both, with a fire-resistance rating not less than that required for the exit enclosure. 2. Equipment, control wiring, power wiring and ductwork shall be located within the exit enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712 of the Seattle Building Code, or both, with a fire-resistance rating not less than that required for the exit enclosure. 3. Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712 of the Seattle Building Code, or both, with a fire-resistance rating not less than that required for the exit enclosure. Exceptions: 1. Control wiring and power wiring utilizing a 2-hour rated cable or cable system. 2. Where encased with not less than 2 inches (51 mm) of concrete.
[B] 909.21.2.2 Emergency power systems. Stairway pressurization systems and automatic fire detection systems shall be powered by an approved emergency power system conforming to Section 403.4.8 and Chapter 27 of the Seattle Building Code. [B] 909.21.2.3 Rational analysis. A rational analysis complying with Section 909.4 shall be submitted with the construction documents.
[B] 909.21.2.4 Special inspection and acceptance testing. Special inspection and acceptance testing shall comply with Section 909.18 and 909.19. [B] 909.22 Pressurization for low-rise buildings. Where stairway pressurization is provided in accordance with Section 1021.2.1 item 3 or with Section 509.2 item 11 of the Seattle Building Code, the pressurization system shall comply with the following: 1. Stairways shall be pressurized to a minimum positive pressure of 0.15 inch of water column (37 Pa) relative to the main occupied area on each floor, and a maximum pressure that complies with Section 1008.1.3; 2. The stairway pressurization shall be activated by a fire alarm originating anywhere in the building. Smoke detectors shall be installed within 5 feet (1524 mm) of doors exiting into pressurized stairways; 3. Pressurization equipment and its duct work located within the building shall be separated from other portions of the building by construction equal to that required for the exit enclosure; 4. Supply air shall be taken directly from an outside, uncontaminated source at least 20 feet (6096 mm) from any air exhaust system or outlet. Air ducts shall be continuous to the exterior of the building. Two smoke detectors shall be located in the duct in accordance with NFPA 72 arranged to automatically shut down the fan system only when both smoke detectors activate. The detectors shall be located downstream of the fan and shall be connected to the fire alarm as a supervisory signal; 5. A legally required standby power system shall be provided for the pressurization system according to Seattle Electrical Code Section 701.11. A connection ahead of the service disconnecting means shall be permitted as the sole source of power to the pressurization system. 6. Other measures to prevent loss of pressurization shall be provided in the design and construction of exit enclosures, such as doors and door closers, quality of workmanship, and caulking of penetrations and joints. 7. A rational analysis complying with Section 909.4 is not required for stairway pressurization systems in low-rise buildings. 8. Special inspection and acceptance testing shall comply with Section 909.18 and 909.19. *** 914.3 High-rise buildings. High-rise buildings shall comply with Sections 914.3.1 through 914.3.5. See sections 903.3.1.1.2 and 905.3.6 for additional requirements. ***
((
***
914.3.5 (( *** 914.4.1 Automatic sprinkler system. An approved automatic sprinkler system shall be installed throughout the entire building. Exceptions: 1. That area of a building adjacent to or above the atrium need not be sprinklered, provided that portion of the building is separated from the atrium portion by not less than a 2-hour fire barrier constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 712 of the International Building Code, or both.
2. Where the ceiling of the atrium is more than 55 feet (16 764 mm) above any floor open to the atrium (( *** SECTION 915 ALERTING SYSTEMS 915.1 General. An approved alerting system in accordance with Sections 915.2 through 915.6 shall be provided in all Group E occupancies. Exception: Approved alerting systems in existing buildings, structures or occupancies. [W] 915.2 Power source. Alerting systems shall be provided with power supplies in accordance with Section 4.4.1 of NFPA 72 and circuit disconnecting means identified as "EMERGENCY ALERTING SYSTEM." Exception: Systems that do not require electrical power to operate. [W] 915.3 Duration of operation. The alerting system shall be capable of operating under nonalarm condition (quiescent load) for a minimum of 24 hours and then shall be capable of operating during an emergency condition for a period of 15 minutes at maximum connected load. [W] 915.4 Combination system. Alerting system components and equipment shall be allowed to be used for other purposes. [W] 915.4.1 System priority. The alerting system use shall take precedence over any other use. [W] 915.4.2 Fire alarm system. Fire alarm systems sharing components and equipment with alerting systems shall be in accordance with Section 6.8.4 of NFPA 72. [W] 915.4.2.1 Signal priority. Recorded or live alert signals generated by an alerting system that shares components with a fire alarm system shall, when actuated, take priority over fire alarm messages and signals. [W] 915.4.2.2 Temporary deactivation. Should the fire alarm system be in the alarm mode when such an alerting system is actuated, it shall temporarily cause deactivation of all fire alarm-initiated audible messages or signals during the time period required to transmit the alert signal. [W] 915.4.2.3 Supervisory signal. Deactivation of fire alarm audible and visual notification signals shall cause a supervisory signal for each notification zone affected in the fire alarm system. 915.5 Audibility. Audible characteristics of the alert signal shall be in accordance with Section 7.4.1 of NFPA 72 throughout the area served by the alerting system. Exception: Areas served by approved visual or textual notification, if the visible notification appliances are not also used as a fire alarm signal. [W] 915.6 Visibility. Visible and textual notification appliances are permitted in addition to alert signal audibility. *** Section 11. Chapter 10 of the 2009 International Fire Code is amended as follows: CHAPTER 10 MEANS OF EGRESS *** SECTION 1002 DEFINITIONS 1002.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. ***
EXIT. That portion of a means of egress system which is separated from other interior spaces of a building or structure (( ***
EXIT ENCLOSURE. An exit component that (( ***
EXIT PASSAGEWAY. An exit component that (( EXIT PLACARD. A non-illuminated sign or a sign painted on a wall indicating the direction of egress. ***
SUITE. A group of patient treatment rooms or patient sleeping rooms within Group I-2 occupancies where staff are in attendance within the suite, for supervision of all patients within the suite and the suite is in compliance with the requirements of
Sections 1014.2.2 through (( *** SECTION 1003 GENERAL MEANS OF EGRESS *** 1003.2 Ceiling height. The means of egress shall have a ceiling height of not less than 7 feet 6 inches (2286 mm). Exceptions:
1. ((
((
((
((
((
((
((
(( *** SECTION 1004 OCCUPANT LOAD *** TABLE 1004.1.1 MAXIMUM FLOOR AREA ALLOWANCES PER OCCUPANT
For SI: 1 square foot = 0.0929 m2. 1. For electrical equipment areas, see also Sections 110.26 and 110.32 through 110-34 of the Seattle Electrical Code. *** SECTION 1005 EGRESS WIDTH 1005.1 Minimum required egress width. The means of egress width shall not be less than required by this section. The total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by 0.3 inches (7.62 mm) per occupant for stairways and by 0.2 inches (5.08 mm) per occupant for other egress components. The width shall not be less than specified elsewhere in this code. In high-rise buildings for other than H and I-2 occupancies, the total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by 0.2 inches (5.1 mm) per occupant for stairways and by 0.15 inches (3.8 mm) per occupant for other egress components in buildings that are provided with sprinkler protection in accordance with 903.3.1.1 or 903.3.1.2. The width at any point in the path of egress travel shall not be less than the width required for doors in Section 1008. Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity to less than 50 percent of the required capacity. The maximum capacity required from any story of a building shall be maintained to the termination of the means of egress. Exception s : 1. Means of egress complying with Section 1028. 2. Aisles complying with Section 1017. 3. Corridors complying with Section 1018.2. 4. Stage stairways and catwalks complying with Section 1015.6. *** SECTION 1006 MEANS OF EGRESS ILLUMINATION ***
1006.2 Illumination level. Illumination shall be provided at every point in (( Exception: For auditoriums, theaters, concert or opera halls and similar assembly occupancies, the illumination at the walking surface is permitted to be reduced during performances to not less than 0.2 foot-candle (2.15 lux), provided that the required illumination is automatically restored upon activation of a premises' fire alarm system where such system is provided.
1006.3 Illumination (( 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1027.1, in buildings required to have two or more exits. 5. Exterior landings as required by Section 1008.1.6 for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Chapter 27. *** SECTION 1007 ACCESSIBLE MEANS OF EGRESS [W] 1007.1 Accessible means of egress required. Accessible means of egress shall comply with this section. Accessible spaces shall be provided with not less than one accessible means of egress. Where more than one means of egress are required by Section 1015.1 or 1021.1 from any accessible space, each accessible portion of the space shall be served by not less than two accessible means of egress. Exceptions: 1. Accessible means of egress are not required in alterations to existing buildings. 2. One accessible means of egress is required from an accessible mezzanine level in accordance with Section 1007.3, 1007.4 or 1007.5. 3. In assembly areas with sloped or stepped aisles, one accessible means of egress is permitted where the common path of travel is accessible and meets the requirements in Section 1028.8. 4. In parking garages, accessible means of egress are not required to serve parking areas that do not contain accessible parking spaces or other accessible elements. 1007.2 Continuity and components. Each required accessible means of egress shall be continuous to a public way and shall consist of one or more of the following components: 1. Accessible routes complying with Section 1104 of the International Building Code. 2. Interior exit stairways complying with Sections 1007.3 and 1022. 3. Exterior exit stairways complying with Sections 1007.3 and 1026. 4. Elevators complying with Section 1007.4. Interpretation I1007.2a: An exit passageway is not required on the level of exit discharge to connect the elevator with the exterior exit door. 5. Platform lifts complying with Section 1007.5. 6. Horizontal exits complying with Section 1025. 7. Ramps complying with Section 1010. 8. Areas of refuge complying with Section 1007.6. Exceptions: 1. Where the exit discharge is not accessible, an exterior area for assisted rescue must be provided in accordance with Section 1007.7. 2. Where the exit stairway is open to the exterior, the accessible means of egress shall include either an area of refuge in accordance with Section 1007.6 or an exterior area for assisted rescue in accordance with Section 1007.7. 1007.2.1 Elevators required. In buildings where a required accessible floor is four or more stories above or below a level of exit discharge, at least one required accessible means of egress shall be an elevator complying with Section 1007.4. Interpretation I1007.2b: The level of exit discharge is not counted when determining whether an accessible floor is four stories above or below a level of exit discharge. Exceptions: 1. In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the elevator shall not be required on floors provided with a horizontal exit and located at or above the levels of exit discharge. 2. In buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the elevator shall not be required on floors provided with a ramp conforming to the provisions of Section 1010. Interpretation I1007.2c: In exception 2, the ramp shall be part of an accessible means of egress.
***
1007.4 Elevators. In order to be considered part of an accessible means of egress, an elevator shall comply with the emergency operation and signaling device requirements of Section 2.27 of ASME A17.1. (( Exceptions: 1. Elevators are not required to be accessed from an area of refuge or horizontal exit in open parking garages. 2. Elevators are not required to be accessed from an area of refuge or horizontal exit in buildings and facilities equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2. 3. Elevators not required to be located in a shaft in accordance with Section 708.2 of the International Building Code are not required to be accessed from an area of refuge or horizontal exit. 4. Elevators are not required to be accessed from an area of refuge or horizontal exit for smoke protected seating areas complying with Section 1028.6.2.
1007.5 Platform lifts. Platform (wheelchair) lifts shall not serve as part of an accessible means of egress, except where allowed as part of a required accessible route in Section 1109.7, Items 1 through 9 of the International Building Code.
(( 1007.5.1 Openness. Platform lifts on an accessible means of egress shall not be installed in a fully enclosed hoistway.
1007.6 Areas of refuge. Every required area of refuge shall be accessible from the space it serves by an accessible means of egress. The maximum travel distance from any accessible space to an area of refuge shall not exceed the travel distance
permitted for the occupancy in accordance with Section 1016.1. Every required area of refuge shall have direct access to a stairway within an exit enclosure complying with Sections 1007.3 and 1022 or an elevator complying with Section 1007.4. Where an
elevator lobby is used as an area of refuge, the shaft and lobby shall comply with Section (( Exceptions: 1. A stairway serving an area of refuge is not required to be enclosed where permitted in Sections 1016.1 and 1022.1.
2. (( *** 1007.8 Two-way communication. A two-way communication system shall be provided at the elevator landing on each accessible floor that is one or more stories above or below the story of exit discharge complying with Sections 1007.8.1 and 1007.8.2. Exceptions: 1. Two-way communication systems are not required at the elevator landing where the two-way communication system is provided within areas of refuge in accordance with Section 1007.6.3. 2. Two-way communication systems are not required on floors provided with exit ramps conforming to the provisions of Section 1010. [W] 1007.8.1 System requirements. Two-way communication systems shall provide communication between each required location and the fire command center or a central control point location approved by the fire department.
Where the central control point is not constantly attended, a two-way communication system shall have a timed automatic telephone dial-out capability to a monitoring location (( 1007.8.2 Directions. Directions for the use of the two-way communication system, instructions for summoning assistance via the two-way communication system and written identification of the location shall be posted adjacent to the two-way communication system. *** SECTION 1008 DOORS, GATES AND TURNSTILES 1008.1 Doors. Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. See Section 3201 of the Seattle Building Code for doors swinging over public property. Means of egress doors shall be readily distinguishable from the adjacent construction and finishes such that the doors are easily recognizable as doors. Mirrors or similar reflecting materials shall not be used on means of egress doors. Means of egress doors shall not be concealed by curtains, drapes, decorations or similar materials. * * * 1008.1.4 Special doors. Special doors and security grilles shall comply with the requirements of Sections 1008.1.4.1 through 1008.1.4.5. 1008.1.4.1 Revolving doors. Revolving doors shall comply with the following: 1. Each revolving door shall be capable of collapsing into a bookfold position with parallel egress paths providing an aggregate width of 36 inches (914 mm). 2. A revolving door shall not be located within 10 feet (3048 mm) of the foot of or top of stairs or escalators. A dispersal area shall be provided between the stairs or escalators and the revolving doors. 3. The revolutions per minute (rpm) for a revolving door shall not exceed those shown in Table 1008.1.4.1. 4. Each revolving door shall have a side-hinged swinging door which complies with Section 1008.1 in the same wall and within 10 feet (3048 mm) of the revolving door. 5. Revolving doors shall not be part of an accessible route required by Section 1007 and Chapter 11. 1008.1.4.1.1 Egress component. A revolving door used as a component of a means of egress shall comply with Section 1008.1.4.1 and the following three conditions: 1. Revolving doors shall not be given credit for more than 50 percent of the required egress capacity. 2. Each revolving door shall be credited with no more than a 50-person capacity. 3. Each revolving door shall be capable of being collapsed when a force of not more than 130 pounds (578 N) is applied within 3 inches (76 mm) of the outer edge of a wing. 1008.1.4.1.2 Other than egress component. A revolving door used as other than a component of a means of egress shall comply with Section 1008.1.4.1. The collapsing force of a revolving door not used as a component of a means of egress shall not be more than 180 pounds (801 N). Exception: A collapsing force in excess of 180 pounds (801 N) is permitted if the collapsing force is reduced to not more than 130 pounds (578 N) when at least one of the following conditions is satisfied: 1. There is a power failure or power is removed to the device holding the door wings in position. 2. There is an actuation of the automatic sprinkler system where such system is provided. 3. There is an actuation of a smoke detection system which is installed in accordance with Section 907 to provide coverage in areas within the building which are within 75 feet (22 860 mm) of the revolving doors. 4. There is an actuation of a manual control switch, in an approved location and clearly defined, which reduces the holding force to below the 130-pound (578 N) force level. 1008.1.4.2 Power-operated doors. Where means of egress doors are operated by power, such as doors with a photoelectric-actuated mechanism to open the door upon the approach of a person, or doors with power-assisted manual operation, the design shall be such that in the event of power failure, the door is capable of being opened manually to permit means of egress travel or closed where necessary to safeguard means of egress. The forces required to open these doors manually shall not exceed those specified in Section 1008.1.3, except that the force to set the door in motion shall not exceed 50 pounds (220 N). The door shall be capable of swinging from any position to the full width of the opening in which such door is installed when a force is applied to the door on the side from which egress is made. Full-poweroperated doors shall comply with BHMA A156.10. Power-assisted and low-energy doors shall comply with BHMA A156.19. Exceptions: 1. Occupancies in Group I-3. 2. Horizontal sliding doors complying with Section 1008.1.4.3. 3. For a biparting door in the emergency breakout mode, a door leaf located within a multiple-leaf opening shall be exempt from the minimum 32-inch (813 mm) single-leaf requirement of Section 1008.1.1, provided a minimum 32inch (813 mm) clear opening is provided when the two biparting leaves meeting in the center are broken out. 1008.1.4.3 Horizontal sliding doors. In other than Group H occupancies, horizontal sliding doors permitted to be a component of a means of egress in accordance with Exception 6 to Section 1008.1.2 shall comply with all of the following criteria: 1. The doors shall be power operated and shall be capable of being operated manually in the event of power failure. 2. The doors shall be openable by a simple method from both sides without special knowledge or effort. 3. The force required to operate the door shall not exceed 30 pounds (133 N) to set the door in motion and 15 pounds (67 N) to close the door or open it to the minimum required width. 4. The door shall be openable with a force not to exceed 15 pounds (67 N) when a force of 250 pounds (1100 N) is applied perpendicular to the door adjacent to the operating device. 5. The door assembly shall comply with the applicable fire protection rating and, where rated, shall be self-closing or automatic closing by smoke detection in accordance with Section 715.4.8.3 of the International Building Code, shall be installed in accordance with NFPA 80 and shall comply with Section 715 of the International Building Code. 6. The door assembly shall have an integrated standby power supply. 7. The door assembly power supply shall be electrically supervised. 8. The door shall open to the minimum required width within 10 seconds after activation of the operating device. 1008.1.4.4 Access-controlled egress doors. The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, I-2, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, I-2, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria: 1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor. 2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors. 3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads "PUSH TO EXIT." When operated, the manual unlocking device shall result in direct interruption of power to the lock---independent of the access control system electronics---and the doors shall remain unlocked for a minimum of 30 seconds. 4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset. 5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset. 6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public. 7. The access control system shall be listed or shall be comprised of approved components. Note: Components bearing a "recognized component" mark from an approved agency shall be approved. 1008.1.4.5 Security grilles. In Groups B, F, M and S, horizontal sliding or vertical security grilles are permitted at the main exit and shall be openable from the inside without the use of a key or special knowledge or effort during periods that the space is occupied. The grilles shall remain secured in the full-open position during the period of occupancy by the general public. Where two or more means of egress are required, not more than one-half of the exits or exit access doorways shall be equipped with horizontal sliding or vertical security grilles. * * * 1008.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches (178 mm). When a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. When doors open over landings, doors in any position shall not reduce the landing length to less than 12 inches (305 mm). Landings shall have a length measured in the direction of travel of not less than 44 inches (1118 mm). Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches (914 mm). Interpretation I1008.1.6: Landing length, width and slope shall be measured as specified in Section 1009.5 and 1009.6.1. See Figures 1008.1.6(1), 1008.1.6(2) and 1008.1.6(3) for illustrations of the requirements of this section.
* * * 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. 1008.1.9.2 Hardware height. Door handles, pulls, latches, locks and other operating devices shall be installed 34 inches (864 mm) minimum and 48 inches (1219 mm) maximum above the finished floor. Locks used only for security purposes and not used for normal operation are permitted at any height. Exception: Access doors or gates in barrier walls and fences protecting pools, spas and hot tubs shall be permitted to have operable parts of the release of latch on self-latching devices at 54 inches (1370 mm) maximum above the finished floor or ground, provided the selflatching devices are not also self-locking devices operated by means of a key, electronic opener or integral combination lock. 1008.1.9.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint as approved by the building official . 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked;
2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED (( 2.3. The use of the key-operated locking device is revokable by the building official for due cause. 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware on the egress side of the door . 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 5. Fire doors after the minimum elevated temperature has disabled the unlatching mechanism in accordance with listed fire door test procedures. 6. Approved, listed locks without delayed egress shall be permitted in Group R-2 boarding homes licensed by Washington state, provided that: 6.1. The clinical needs of one or more patients require specialized security measures for their safety. 6.2. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system. 6.3. The doors unlock upon loss of electrical power controlling the lock or lock mechanism. 6.4. The lock shall be capable of being deactivated by a signal from a switch located in an approved location. 6.5. There is a system, such as a keypad and code, in place that allows visitors, staff persons and appropriate residents to exit. Instructions for exiting shall be posted within six feet of the door. 7. Doors from elevator lobbies providing access to exits are permitted to be locked during or after business hours where items 7.1 through 7.5 are satisfied. 7.1. The lobby doors shall unlock automatically upon fire alarm. 7.2. The lobby doors shall unlock automatically upon power loss. 7.3. The alarm system shall include smoke detection in the elevator lobby and at least two detectors on the tenant side within 15 feet of the door; 7.4. Access through the tenant portion of the building to both exits shall be unobstructed; and 7.5. The building shall have an automatic sprinkler system throughout in accordance with Section 903.3.1.1 or 903.3.1.2. 1008.1.9.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted on required means of egress doors . Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edgeor surface-mounted bolts or self-latching flush bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F or S occupancy, manually operated edgeor surface-mounted bolts are permitted on the inactive leaf. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually operated edgeor surface-mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress width requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 5. Where a pair of doors serves patient care rooms in Group I-2 occupancies, self-latching edge or surfacemounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress width requirements and the inactive leaf contains no doorknobs, panic bars or similar operating hardware. 1008.1.9.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. Exceptions: 1. Places of detention or restraint. 2. Where manually operated bolt locks are permitted by Section 1008.1.9.4. 3. Doors with automatic flush bolts as permitted by Section 1008.1.9.3, Exception 3. 4. Doors from individual dwelling units and sleeping units of Group R occupancies as permitted by Section 1008.1.9.3, Exception 4.
((
1008.1.9.6 Special locking arrangements in Group I-2. Approved (( 1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system. 2. The doors unlock upon loss of power controlling the lock or lock mechanism. 3. The door locks shall have the capability of being unlocked by a signal from the fire command center, a nursing station or other approved location. 4. The procedures for the operation(s) of the unlocking system shall be described and approved as part of the emergency planning and preparedness required by Chapter 4.
5. (( 6. Emergency lighting shall be provided at the door. Exception: Items 1 through 3 and 5 shall not apply to doors to areas where persons who , because of clinical needs, require restraint or containment as part of the function of a Group I-2 mental hospital provided that all clinical staff shall have the keys, codes or other means necessary to operate the locking devices. 1008.1.9.7 Delayed egress locks. Approved, listed, delayed egress locks shall be permitted to be installed on doors serving any occupancy except Group A, E and H occupancies in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or an approved automatic smoke or heat detection system installed in accordance with Section 907, provided that the doors unlock in accordance with Items 1 through 6 below. Delayed egress locks are permitted in libraries in both Group A and E occupancies in locations other than at main exit doors, and in Group E day care occupancies. A building occupant shall not be required to pass through more than one door equipped with a delayed egress lock before entering an exit. 1. The doors unlock upon actuation of the automatic sprinkler system or automatic fire detection system. 2. The doors unlock upon loss of power controlling the lock or lock mechanism. 3. The door locks shall have the capability of being unlocked by a signal from the fire command center. 4. The initiation of an irreversible process which will release the latch in not more than 15 seconds when a force of not more than 15 pounds (67 N) is applied for 1 second to the release device. Initiation of the irreversible process shall activate an audible signal in the vicinity of the door. Once the door lock has been released by the application of force to the releasing device, relocking shall be by manual means only. Exception: Where approved, a delay of not more than 30 seconds is permitted. 5. A sign shall be provided on the door located above and within 12 inches (305 mm) of the release device reading: PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS. 6. Emergency lighting shall be provided at the door. 1008.1.9.8 Electromagnetically locked egress doors. Doors in the means of egress that are not otherwise required to have panic hardware in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and doors to tenant spaces in Group A, B, E, M, R-1 or R-2 shall be permitted to be electromagnetically locked if equipped with listed hardware that incorporates a built-in switch and meet the requirements below: 1. The listed hardware that is affixed to the door leaf has an obvious method of operation that is readily operated under all lighting conditions. 2. The listed hardware is capable of being operated with one hand. 3. Operation of the listed hardware releases to the electromagnetic lock and unlocks the door immediately. 4. Loss of power to the listed hardware automatically unlocks the door. 1008.1.9.9 Locking arrangements in correctional facilities. In occupancies in Groups A-2, A-3, A-4, B, E, F, I-2, I-3, M and S within correctional and detention facilities, doors in means of egress serving rooms or spaces occupied by persons whose movements are controlled for security reasons shall be permitted to be locked when equipped with egress control devices which shall unlock manually and by at least one of the following means: 1. Activation of an automatic sprinkler system installed in accordance with Section 903.3.1.1; 2. Activation of an approved manual alarm box; or 3. A signal from a constantly attended location. 1008.1.9.10 Stairway doors. Interior stairway means of egress doors shall be openable from both sides without the use of a key or special knowledge or effort. Exceptions: 1. Stairway discharge doors shall be openable from the egress side and shall only be locked from the opposite side. 2. This section shall not apply to doors arranged in accordance with Section 403.5.3. 3. In stairways serving not more than four stories, doors are permitted to be locked from the side opposite the egress side, provided they are openable from the egress side and capable of being unlocked simultaneously without unlatching upon a signal from the fire command center, if present, or a signal by emergency personnel from a single location inside the main entrance to the building. 1008.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.9.3, Item 2. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet (1829 mm) wide that contain overcurrent devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. 1008.1.10.1 Installation. Where panic or fire exit hardware is installed, it shall comply with the following: 1. Panic hardware shall be listed in accordance with UL 305; 2. Fire exit hardware shall be listed in accordance with UL 10C and UL 305; 3. The actuating portion of the releasing device shall extend at least one-half of the door leaf width; and 4. The maximum unlatching force shall not exceed 15 pounds (67 N). 1008.1.10.2 Balanced doors. If balanced doors are used and panic hardware is required, the panic hardware shall be the push-pad type and the pad shall not extend more than onehalf the width of the door measured from the latch side. *** SECTION 1009 STAIRWAYS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44 inches (1118 mm). See Section 1007.3 for accessible means of egress stairways. Exceptions: 1. Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). 2. Spiral stairways as provided for in Section 1009.9. 3. Aisle stairs complying with Section 1028. 4. Where an incline platform lift or stairway chairlift is installed on stairways serving occupancies in Group R3, or within dwelling units in occupancies in Group R-2, a clear passage width not less than 20 inches (508 mm) shall be provided. If the seat and platform can be folded when not in use, the distance shall be measured from the folded position. 5. Stairways that are neither part of a required means of egress nor an accessible route. *** 1009.4 Stair treads and risers. Stair treads and risers shall comply with Sections 1009.4.1 through 1009.4.5. 1009.4.1 Dimension reference surfaces. For the purpose of this section, all dimensions are exclusive of carpets, rugs or runners. 1009.4.2 Riser height and tread depth. Stair riser heights shall be 7 inches (178 mm) maximum and 4 inches (102 mm) minimum. The riser height shall be measured vertically between the leading edges of adjacent treads. Rectangular tread depths shall be 11 inches (279 mm) minimum measured horizontally between the vertical planes of the foremost projection of adjacent treads and at a right angle to the tread's leading edge. Winder treads shall have a minimum tread depth of 11 inches (279 mm) measured between the vertical planes of the foremost projection of adjacent treads at the intersections with the walkline and a minimum tread depth of 10 inches (254 mm) within the clear width of the stair. Exceptions: 1. Alternating tread devices in accordance with Section 1009.10. 2. Ship ladders in accordance with Section 1009.11. 3. Spiral stairways in accordance with Section 1009.9. 4. Aisle stairs in assembly seating areas where the stair pitch or slope is set, for sightline reasons, by the slope of the adjacent seating area in accordance with Section 1028.11.2. 5. In Group R-3 occupancies; within dwelling units in Group R-2 occupancies; and in Group U occupancies that are accessory to a Group R-3 occupancy or accessory to individual dwelling units in Group R-2 occupancies; the maximum riser height shall be 7-3/4 inches (197 mm); the minimum tread depth shall be 10 inches (254 mm); the minimum winder tread depth at the walkline shall be 10 inches (254 mm); and the minimum winder tread depth shall be 6 inches (152 mm).A nosing not less than 3/4 inch (19.1 mm) but not more than 1-1/4 inches (32 mm) shall be provided on stairways with solid risers where the tread depth is less than 11 inches (279 mm). 6. See Section 3404.1 of the International Building Code for the replacement of existing stairways. 7. In Group I-3 facilities, stairways providing access to guard towers, observation stations and control rooms, not more than 250 square feet (23 m2) in area, shall be permitted to have a maximum riser height of 8 inches (203 mm) and a minimum tread depth of 9 inches (229 mm). 1009.4.3 Winder treads. Winder treads are not permitted in means of egress stairways except within a dwelling unit. Exceptions: 1. Curved stairways in accordance with Section 1009.8. 2. Spiral stairways in accordance with Section 1009.9. 1009.4.4 Dimensional uniformity. Stair treads and risers shall be of uniform size and shape. The tolerance between the largest and smallest riser height or between the largest and smallest tread depth shall not exceed 3/8 inch (9.5 mm) in any flight of stairs. The greatest winder tread depth at the walkline within any flight of stairs shall not exceed the smallest by more than 3/8 inch (9.5 mm). Exceptions: 1. Nonuniform riser dimensions of aisle stairs complying with Section 1028.11.2. 2. Consistently shaped winders, complying with Section 1009.4.2, differing from rectangular treads in the same stairway flight.
Where the bottom or top riser adjoins a sloping public way, walkway or driveway having an established grade and serving as a landing, the bottom or top riser is permitted to be reduced along the slope . (( 1009.4.5 Profile. The radius of curvature at the leading edge of the tread shall be not greater than 9/16 inch (14.3 mm). Beveling of nosings shall not exceed 9/16 inch (14.3 mm). Risers shall be solid and vertical or sloped under the tread above from the underside of the nosing above at an angle not more than 30 degrees (0.52 rad) from the vertical. The leading edge (nosings) of treads shall project not more than 1-1/4 inches (32 mm) beyond the tread below and all projections of the leading edges shall be of uniform size, including the leading edge of the floor at the top of a flight. Exceptions: 1. Solid risers are not required for stairways that are not required to comply with Section 1007.3, provided that the opening between treads does not permit the passage of a sphere with a diameter of 4 inches (102 mm). 2. Solid risers are not required for occupancies in Group I-3 or in Group F, H and S occupancies other than areas accessible to the public. There are no restrictions on the size of the opening in the riser. 3. Solid risers are not required for spiral stairways constructed in accordance with Section 1009.9. 4. Solid risers are not required for alternating tread devices constructed in accordance with Section 1009.10. *** 1009.7 Vertical rise. A flight of stairs shall not have a vertical rise greater than 12 feet (3658 mm) between floor levels or landings. Exceptions: 1. Aisle stairs complying with Section 1028. 2. Alternating tread devices used as a means of egress shall not have a rise greater than 20 feet (6096 mm) between floor levels or landings. 3. Stairways that are not part of a required means of egress. *** 1009.13 Stairway to roof. In buildings four or more stories above grade plane, one stairway shall extend to the roof surface unless the roof has a slope steeper than four units vertical in 12 units horizontal (33-percent slope). In buildings without an occupied roof, access to the roof from the top story shall be permitted to be by an alternating tread device. 1009.13.1 Roof access. Where a stairway is provided to a roof, access to the roof shall be provided through a penthouse complying with Section 1509.2.
Exception: In buildings without an occupied roof, access to the roof shall be permitted to be a roof hatch or trap door not less than 16 square feet (1.5 m2) in area and having a minimum dimension of 2 feet 6 inches ((( *** [W] 1009.15 Stairways in individual dwelling units. Stairs or ladders within individual dwelling units used for access to areas of 200 square feet (18.6 m2) or less which do not contain the primary bathroom or kitchen are exempt from the requirements of Section 1009. SECTION 1010 RAMPS 1010.1 Scope. The provisions of this section shall apply to ramps used as a component of a means of egress. Exceptions: 1. Other than ramps that are part of the accessible routes providing access in accordance with Sections 1108.2 through 1108.2.4 and 1108.2.6 of the International Building Code, ramped aisles within assembly rooms or spaces shall conform with the provisions in Section 1028.11. 2. Curb ramps shall comply with ICC A117.1.
3. Vehicle ramps in parking garages for pedestrian exit access shall not be required to comply with Sections 1010.3 through 1010.9 when they are not an accessible route serving accessible parking spaces(( 4. In a parking garage where one accessible means of egress serving accessible parking spaces or other accessible elements is provided, a second accessible means of egress serving that area shall be permitted to include a vehicle ramp that does not comply with Sections 1010.4, 1010,5 and 1010.8. A landing complying with Sections 1010.6.1 and 1010.6.4 shall be provided at any change of direction in the accessible means of egress. *** SECTION 1011 EXIT SIGNS 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit or the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Either exit signs or exit placards shall be located at any other location determined by the building official to be necessary to clearly indicate the direction of egress. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access other than in buildings designed with a single exit stairway according to Section 1021.2.1 item 3 . 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the building official. 3. Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3. 4. Exit signs are not required in dayrooms, sleeping rooms or dormitories in occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. 6. Exit signs are not required on exterior stairways serving exterior exit balconies. Interpretation I1011.1: Exit placards are permitted to be used to identify exits in occupancies where exit signs are not required. *** 1011.5 Externally illuminated exit signs. Externally illuminated exit signs shall comply with Sections 1011.5.1 through 1011.5.3. 1011.5.1 Graphics. Every exit sign , exit placard and directional exit sign shall have plainly legible letters not less than 6 inches (152 mm) high with the principal strokes of the letters not less than 3/4 inch (19.1 mm) wide. The word "EXIT" shall have letters having a width not less than 2 inches (51 mm) wide, except the letter "I," and the minimum spacing between letters shall not be less than 3/8 inch (9.5 mm). Signs and placards larger than the minimum established in this section shall have letter widths, strokes and spacing in proportion to their height. The word "EXIT" shall be in high contrast with the background and shall be clearly discernible when the means of exit sign illumination is or is not energized. If a chevron directional indicator is provided as part of the exit sign or placard , the construction shall be such that the direction of the chevron directional indicator cannot be readily changed. Exception: Existing exit signs or placards with letters at least 5 inches (127 mm) in height are permitted to be reused. 1011.5.2 Exit sign illumination. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Chapter 27 of the International Building Code.
Exception: Approved exit sign illumination means that provide continuous illumination independent of external power sources for a duration of not less than 90 minutes, in case of primary power loss, are not required to be connected to an emergency
(( 1011.6 Not-an-exit warnings. Placards reading "NOT AN EXIT" shall be installed at all doorways, passageways or stairways which are not exits, exit accesses or exit discharges, and which may be mistaken for an exit. A sign indicating the use of the doorway, passageway or stairway, such as "TO BASEMENT", "STORE ROOM", "LINEN CLOSET", is permitted in lieu of the "NOT AN EXIT" sign. SECTION 1012 HANDRAILS *** 1012.4 Continuity. Handrail-gripping surfaces shall be continuous, without interruption by newel posts or other obstructions. Exceptions: 1. Handrails within dwelling units are permitted to be interrupted by a newel post at a turn or landing. 2. Within a dwelling unit, the use of a volute, turnout, starting easing or starting newel is allowed over the lowest tread. 3. Handrail brackets or balusters attached to the bottom surface of the handrail that do not project horizontally beyond the sides of the handrail within 1-1/2 inches (38 mm) of the bottom of the handrail shall not be considered obstructions. For each 1/2 inch (12.7 mm) of additional handrail perimeter dimension above 4 inches (102 mm), the vertical clearance dimension of 1-1/2 inches (38 mm) shall be permitted to be reduced by 1/8 inch (3 mm). 4. Where handrails are provided along walking surfaces with slopes not steeper than 1:20, the bottoms of the handrail gripping surfaces shall be permitted to be obstructed along their entire length where they are integral to rash rails or bumper guards. 5. Handrails on stairways that are not part of a required means of egress need not be continuous. *** 1012.6 Handrail extensions. Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight or ramp run. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches (305 mm) beyond the top riser and continue to slope for the depth of one tread beyond the bottom riser. At ramps where handrails are not continuous between runs, the handrails shall extend horizontally above the landing 12 inches (305 mm) minimum beyond the top and bottom of ramp runs. The extensions of handrails shall be in the same direction of the stair flights at stairways and the ramp runs at ramps. Exceptions: 1. Handrails within a dwelling unit that is not required to be accessible need extend only from the top riser to the bottom riser. 2. Aisle handrails in Group A and E occupancies in accordance with Section 1028.13. 3. Handrails for alternating tread devices and ship ladders are permitted to terminate at a location vertically above the top and bottom risers. Handrails for alternating tread devices and ship ladders are not required to be continuous between flights or to extend beyond the top or bottom risers. 4. Handrail extensions are not required on handrails on stairways that are not part of a required means of egress. *** SECTION 1014 EXIT ACCESS *** 1014.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section. 1. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas and the area served are accessory to one or the other, are not a Group H occupancy and provide a discernible path of egress travel to an exit. Exception: Means of egress are not prohibited through adjoining or intervening rooms or spaces in a Group H, S or F occupancy when the adjoining or intervening rooms or spaces are the same or a lesser hazard occupancy group. 2. An exit access shall not pass through a room that can be locked to prevent egress. 3. Means of egress from dwelling units or sleeping areas shall not lead through other sleeping areas, toilet rooms or bathrooms. 4. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies when all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area; 2.2. Not more than 50 percent of the exit access is through the stockroom; 2.3. The stockroom is not subject to locking from the egress side; and 2.4. There is a demarcated, minimum 44-inch-wide (1118 mm) aisle defined by fullor partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. 5. Unless approved by the building official, where two or more exits are required, exit travel shall not pass through an exit enclosure as the only way to reach another exit. 1014.2.1 Multiple tenants. Where more than one tenant occupies any one floor of a building or structure, each tenant space, dwelling unit and sleeping unit shall be provided with access to the required exits without passing through adjacent tenant spaces, dwelling units and sleeping units. Exception: The means of egress from a smaller tenant space shall not be prohibited from passing through a larger adjoining tenant space where such rooms or spaces of the smaller tenant occupy less than 10 percent of the area of the larger tenant space through which they pass; are the same or similar occupancy group; a discernable path of egress travel to an exit is provided; and the means of egress into the adjoining space is not subject to locking from the egress side. A required means of egress serving the larger tenant space shall not pass through the smaller tenant space or spaces. [W] 1014.2.2 Group I-2. Habitable spaces and suites in Group I-2 occupancies are permitted to comply with this Section 1014.2.2.
1014.2.2.1 Exit access doors. Habitable (( Exception: Rooms with exit doors opening directly to the outside at ground level. 1014.2.2.2 Exit access through suites. Exit access from areas not classified as a Group I-2 occupancy suite shall not pass through a suite. In a suite required to have more than one exit, one exit access may pass through an adjacent suite if all other requirements of Section 1014.2 are satisfied. 1014.2.2.3 Separation. Suites in Group I-2 occupancies shall be separated from other portions of the building by a smoke partition complying with Section 711 of the Seattle Building Code. Partitions within suites are not required to be smoke-resistant or fire-resistance-rated unless required by another section of this code.
(( 1. The intervening room within the suite is not used as an exit access for more than eight patient beds. 2. The arrangement of the suite allows for direct and constant visual supervision by nursing personnel.
((
((
((
((
((
((
((
((
((
1014.3 Common path of egress travel. In occupancies other than Groups H-1, H-2 and H-3, the common path of egress travel shall not exceed 75 feet (22 860 mm). In Group H-1, H-2 and H3 occupancies, the common path of egress travel shall not exceed 25 feet (7620 mm). For common path of egress travel in Group A occupancies and assembly occupancies accessory to Group E occupancies having fixed seating, see Section 1028.8. Exceptions: 1. The length of a common path of egress travel in Group B, F and S occupancies shall not be more than 100 feet (30 480 mm), provided that the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1. 2. Where a tenant space in Group B, S and U occupancies has an occupant load of not more than 30, the length of a common path of egress travel shall not be more than 100 feet (30 480 mm). 3. The length of a common path of egress travel in a Group I-3 occupancy shall not be more than 100 feet (30 480 mm). 4. The length of a common path of egress travel in a Group R-2 or R-3 occupancy shall not be more than 125 feet (38 100 mm), provided that the building is protected throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. SECTION 1015 EXIT AND EXIT ACCESS DOORWAYS 1015.1 Exits or exit access doorways from spaces. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: Exception: Group I-2 occupancies shall comply with Section 1014.2.2 through 1014.2.7. 1. The occupant load of the space exceeds one of the values in Table 1015.1. Exception: In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. 2. The common path of egress travel exceeds one of the limitations of Section 1014.3. 3. Where required by Section 1015.3, 1015.4, 1015.5, 1015.6 or 1015.6.1. Where a building contains mixed occupancies, each individual occupancy shall comply with the applicable requirements for that occupancy. Where applicable, cumulative occupant loads from adjacent occupancies shall be considered in accordance with the provisions of Section 1004.1. Note: See Section 1008.1.9.3 for conditions in which exit access doors from elevator lobbies are permitted to be locked. 1015.1.1 Three or more exits or exit access doorways. Three exits or exit access doorways shall be provided from any space with an occupant load of 501 to 1,000. Four exits or exit access doorways shall be provided from any space with an occupant load greater than 1,000. TABLE 1015.1 SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
a. Day care maximum occupant load is 10. 1015.2 Exit or exit access doorway arrangement. Required exits shall be located in a manner that makes their availability obvious. Exits shall be unobstructed at all times. Exit and exit access doorways shall be arranged in accordance with Sections 1015.2.1 and 1015.2.2. 1015.2.1 Two exits or exit access doorways. Where two exits or exit access doorways are required from any portion of the exit access, the exit doors or exit access doorways shall be placed a distance apart equal to not less than one-half of the length of the maximum overall diagonal dimension of the building or area to be served measured in a straight line between exit doors or exit access doorways. Interlocking or scissor stairs and stairways that share a wall with other exit enclosures shall be counted as one exit stairway. Exceptions: 1. Where exit enclosures are provided as a portion of the required exit and are interconnected by a 1-hour fireresistance-rated corridor conforming to the requirements of Section 1018, the required exit separation shall be measured along the shortest direct line of travel within the corridor. Interpretation I1015.2: Exception 1 applies only where corridors have a one-hour fire-resistance-rating even where Section 1018 would allow non-rated corridors. 2. Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2, the separation distance of the exit doors or exit access doorways shall not be less than one-third of the length of the maximum overall diagonal dimension of the area served. 3.Where it is not practical to separate exits by onehalf the diagonal dimension, exits from retail and office tenant spaces in Group B and M occupancies and within dwelling units shall be as far apart as reasonably practicable as determined by the building official. 1015.2.2 Three or more exits or exit access doorways. Where access to three or more exits is required, at least two exit doors or exit access doorways shall be arranged in accordance with the provisions of Section 1015.2.1. *** SECTION 1016 EXIT ACCESS TRAVEL DISTANCE 1016.1 Travel distance limitations. Exits shall be so located on each story such that the maximum length of exit access travel, measured from the most remote point within a story along the natural and unobstructed path of egress travel to an exterior exit door at the level of exit discharge, an entrance to a vertical exit enclosure, an exit passageway, a horizontal exit, an exterior exit stairway or an exterior exit ramp, shall not exceed the distances given in Table 1016.1. Exceptions: 1. Travel distance in open parking garages is permitted to be measured to the closest riser of open exit stairways. 2. In outdoor facilities with open exit access components and open exterior exit stairways or exit ramps, travel distance is permitted to be measured to the closest riser of an exit stairway or the closest slope of the exit ramp. 3. In other than occupancy Groups H and I, the exit access travel distance to a maximum of 50 percent of the exits is permitted to be measured from the most remote point within a building to an exit using unenclosed exit access stairways or ramps when connecting a maximum of two stories. The two connected stories shall be provided with at least two means of egress. Such interconnected stories shall not be open to other stories. 4. In other than occupancy Groups H and I, exit access travel distance is permitted to be measured from the most remote point within a building to an exit using unenclosed exit access stairways or ramps in the first and second stories above grade plane in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The first and second stories above grade plane shall be provided with at least two means of egress. Such interconnected stories shall not be open to other stories. Where applicable, travel distance on unenclosed exit access stairways or ramps and on connecting stories shall also be included in the travel distance measurement. The measurement along stairways shall be made on a plane parallel and tangent to the stair tread nosings in the center of the stairway. Note: Additional exit enclosures or corridors constructed as smoke barriers may be required for standpipe hose connections. See Section 905.4. TABLE 1016.1 EXIT ACCESS TRAVEL DISTANCEa
For SI: 1 foot = 304.8 mm. a. See the following sections for modifications to exit access travel distance requirements: Section 402.4 of the International Building Code: For the distance limitation in malls. Section 404.9 of the International Building Code: For the distance limitation through an atrium space. Section 407.4 of the International Building Code: For the distance limitation in Group I-2. Sections 408.6.1 and 408.8.1 of the International Building Code: For the distance limitations in Group I-3. Section 411.4 of the International Building Code: For the distance limitation in special amusement buildings. Section 1014.2.2: For the distance limitation in Group I-2 hospital suites. Section 1015.4: For the distance limitation in refrigeration machinery rooms. Section 1015.5: For the distance limitation in refrigerated rooms and spaces. Section 1021.2: For buildings with one exit. Section 1028.7: For increased limitation in assembly seating. Section 1028.7: For increased limitation for assembly open-air seating.
(( Section 3104.9 of the International Building Code: For pedestrian walkways. b. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2. c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. *** SECTION 1018 CORRIDORS 1018.1 Construction. Corridors shall be fire-resistance rated in accordance with Table 1018.1. The corridor walls required to be fire-resistance rated shall comply with Section 709 of the International Building Code for fire partitions. Exceptions: 1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has at least one door opening directly to the exterior and rooms for assembly purposes have at least one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level. 2. A fire-resistance rating is not required for corridors contained within a dwelling or sleeping unit in an occupancy in Group R. 3. A fire-resistance rating is not required for corridors in open parking garages. 4. A fire-resistance rating is not required for corridors in an occupancy in Group B which is a space requiring only a single means of egress complying with Section 1015.1. 5. In office areas located in buildings of Types IA or IB construction, corridor walls need not be of fireresistance-rated construction where the corridor side of the corridor walls is finished with materials having a maximum Class B rating as defined in Chapter 8 of the Seattle Building Code. This exception does not apply to outpatient clinics and medical offices. 6. The occupant load of Group B conference rooms, lunch rooms without grease-producing cooking and other assembly rooms with an occupant load of less than 50 in each room need not be considered when determining whether corridor construction is required, provided such rooms are accessory to an office tenant located in a building of Type IA or IB construction. This provision is permitted to be used in other construction types when the floor on which the assembly room is located is equipped with an automatic sprinkler system. TABLE 1018.1 CORRIDOR FIRE-RESISTANCE RATING
a. For requirements for occupancies in Group I-2, see Section 407.3 of the International Building Code. b. For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.7 of the International Building Code. c. Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. ***
1018.4 Dead ends. Where more than one exit or exit access doorway is required, the exit access shall be arranged such that there are no dead ends in corridors more than (( Exceptions: 1. In occupancies in Group I-3 of Occupancy Condition 2, 3 or 4 (see Section 308.4), the dead end in a corridor shall not exceed 50 feet (15 240 mm).
2. In occupancies in Groups B, E, F, I-1, M, R-1, R-2, (( 3. A dead-end corridor shall not be limited in length where the length of the dead-end corridor is less than 2.5 times the least width of the dead-end corridor. 4. Dead ends are permitted to be 75 feet (22 860 mm) in length in areas containing Group B offices in buildings of Types IA and IB construction, where the cumulative occupant load does not exceed 50 for all areas for which the dead end serves as the only means of egress. 1018.5 Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts or plenums except as allowed by Seattle Mechanical Code Section 601.2 .
((
1018.5.1 Corridor ceiling. Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum is permitted for one or more of the following conditions: 1. The corridor is not required to be of fire-resistance-rated construction; 2. The corridor is separated from the plenum by fireresistance-rated construction; 3. The air-handling system serving the corridor is shut down upon activation of the air-handling unit smoke detectors required by the International Mechanical Code; 4. The air-handling system serving the corridor is shut down upon detection of sprinkler waterflow where the building is equipped throughout with an automatic sprinkler system; or 5. The space between the corridor ceiling and the floor or roof structure above the corridor is used as a component of an approved engineered smoke control system. 1018.6 Corridor continuity. Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms. Exception s : 1. Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. [W] 2. In Group R-2 boarding homes and residential treatment facilities licensed by Washington state, seating areas shall be allowed to be open to the corridor provided: 2.1 The seating area is constructed as required for the corridor; 2.2 The floor is separated into at least two compartments complying with Section 407.4; 2.3 Each individual seating area does not exceed 150 square feet (13.9 m2), excluding the corridor width; 2.4 The combined total space of seating areas per compartment does not exceed 300 square feet, excluding the corridor width; 2.5 Combustible furnishings located within the seating area shall be in accordance with Section 805; and 2.6 Emergency means of egress lighting is provided as required by Section 1006 to illuminate the area. SECTION 1019 EGRESS BALCONIES *** 1019.2 Wall separation. Exterior egress balconies shall be separated from the interior of the building by walls and opening protectives as required for corridors. Exception s : 1. Separation is not required where the exterior egress balcony is served by at least two stairs and a dead-end travel condition does not require travel past an unprotected opening to reach a stair. 2. Separation is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. *** SECTION 1020 EXITS *** 1020.2 Exterior exit doors. Buildings or structures used for human occupancy shall have at least one exterior door that meets the requirements of Section 1008.1.1 , Section 1008.1.2 and Section 1008.1.3 . 1020.2.1 Detailed requirements. Exterior exit doors shall comply with the applicable requirements of Section 1008.1. 1020.2.2 Arrangement. Exterior exit doors shall lead directly to the exit discharge or the public way. SECTION 1021 NUMBER OF EXITS AND CONTINUITY
1021.1 Exits from stories. All spaces within each story shall have access to the minimum number of (( Exceptions: 1. As modified by Section 403.5.2 of the International Building Code. 2. As modified by Section 1021.2. 3. Exit access stairways and ramps that comply with Exception 3 or 4 of Section 1016.1 shall be permitted to provide the minimum number of approved independent exits required by Table 1021.1 on each story. 4. In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. 5. Within a story, rooms and spaces complying with Section 1015.1 with exits that discharge directly to the exterior at the level of exit discharge, are permitted to have one exit. 1021.1.1 Exits maintained. The required number of exits from any story , including basements, shall be maintained until arrival at grade or the public way. 1021.1.2 Parking structures. Parking structures shall not have less than two exits from each parking tier, except that only one exit is required where vehicles are mechanically parked. Vehicle ramps shall not be considered as required exits unless pedestrian facilities are provided. 1021.1.3 Helistops. The means of egress from helistops shall comply with the provisions of this chapter, provided that landing areas located on buildings or structures shall have two or more exits. For landing platforms or roof areas less than 60 feet (18 288 mm) long, or less than 2,000 square feet (186 m2) in area, the second means of egress is permitted to be a fire escape, alternating tread device or ladder leading to the floor below. TABLE 1021.1 MINIMUM NUMBER OF EXITS FOR OCCUPANT LOAD
1021.2 Single exits. (( Mixed occupancies shall be permitted to be served by single exits provided each individual occupancy complies with the applicable requirements of Table 1021.2 for that occupancy. Where occupants from accessory spaces egress through a primary space, the occupant load of the primary space shall be calculated in accordance with Section 1004.1. In each story of a mixed occupancy building, the maximum number of occupants served by a single exit shall be such that the sum of the ratios of the calculated number of occupants of the space divided by the allowable number of occupants for each occupancy shall not exceed one. 1 021.2.1 Single exits allowed. Only one exit is required from the following: 1. Group R-3 occupancy buildings are permitted to have one exit. 2. Occupied roofs with an occupant load of 10 or less are permitted to have one exit. 3. Not more than 5 stories of Group R-2 occupancy are permitted to be served by a single exit under the following conditions: 3.1 The building has not more than 6 stories above grade plane. 3.2 The building does not contain a boarding house. 3.3 There shall be no more than four dwelling units on any floor. 3.4 The building shall be of not less than one-hour fire-resistive construction and shall also be equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Residential-type sprinkler heads shall be used in all habitable spaces in each dwelling unit. 3.5 There shall be no more than two single exit stairway conditions on the same property. 3.6 An exterior stairway or exit enclosure shall be provided. The exit enclosure, including any related exit passageway, shall be pressurized in accordance with Section 909.21. Doors in the exit enclosure shall swing into the exit enclosure regardless of the occupant load served, provided that doors from the exit enclosure to the building exterior are permitted to swing in the direction of exit travel. 3.7 A corridor shall separate each dwelling unit entry/exit door from the door to an exit enclosure, including any related exit passageway, on each floor. Dwelling unit doors shall not open directly into an enclosed stairway. Dwelling unit doors are permitted to open directly into an exterior stairway. 3.8 There shall be no more than 20 feet (6096 mm) of travel to the exit stairway from the entry/exit door of any dwelling unit. 3.9 Travel distance measured in accordance with Section 1016.1 shall not exceed 125 feet. 3.10 The exit shall not terminate in an exit court where the court depth exceeds the court width unless it is possible to exit in either direction to the public way. 3.11 Elevators shall be pressurized in accordance with Section 708.14.2 of the Seattle Building Code or shall open into elevator lobbies. Elevator lobbies shall be separated from the remainder of the building and from the exit stairway with fire partitions. Doors shall be automatic closing actuated by smoke detector. Where approved by the building official, natural ventilation is permitted to be substituted for pressurization where the ventilation would prevent the accumulation of smoke or toxic gases. 3.12 Other occupancies are permitted in the same building provided they comply with all the requirements of this code. Other occupancies shall not communicate with the Group R occupancy portion of the building or with the single-exit stairway. Exception: Parking garages accessory to the Group R occupancy are permitted to communicate with the exit stairway. 3.13 The exit serving the Group R occupancy shall not discharge through any other occupancy, including an accessory parking garage. 3.14 There shall be no openings within 10 feet (3048 mm) of unprotected openings into the stairway other than required exit doors having a one-hour fire-resistance rating. TABLE 1021.2 STORIES WITH ONE EXIT
For SI: 1 foot = 304.8 mm. a. For the required number of exits for parking structures, see Section 1021.1.2. b. For the required number of exits for air traffic control towers, see Section 412.3 of the International Building Code. c. Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescue openings in accordance with Section 1029. d. Group B, F and S occupancies in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall have a maximum travel distance of 100 feet. e. Day care occupancies shall have a maximum occupant load of 10. *** SECTION 1022 EXIT ENCLOSURES
1022.1 Enclosures required. Interior exit stairways and interior exit ramps shall be enclosed with fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with
Section 712 of the International Building Code, or both. Exit enclosures shall have a fire-resistance rating of not less than 2 hours where connecting more than four stories (( Exceptions: 1. In all occupancies, other than Group H and I occupancies, a stairway is not required to be enclosed when the stairway serves an occupant load of less than 10 and the stairway complies with either Item 1.1 or 1.2. In all cases, the maximum number of connecting open stories shall not exceed two. 1.1. The stairway is open to not more than one story above its level of exit discharge; or 1.2. The stairway is open to not more than one story below its level of exit discharge. 2. Exits in buildings of Group A-5 where all portions of the means of egress are essentially open to the outside need not be enclosed. 3. Stairways serving and contained within a single residential dwelling unit or sleeping unit in Group R-1, R-2 or R-3 occupancies are not required to be enclosed. 4. Stairways in open parking structures that serve only the parking structure are not required to be enclosed. 5. Stairways in Group I-3 occupancies, as provided for in Section 408.3.8 of the International Building Code, are not required to be enclosed. 6. Means of egress stairways as required by Sections 410.5.3 of the International Building Code and 1015.6.1 are not required to be enclosed. 7. Means of egress stairways from balconies, galleries or press boxes as provided for in Section 1028.5.1 are not required to be enclosed. 1022.2 Termination. Exit enclosures shall terminate at an exit discharge or a public way. Exception: An exit enclosure shall be permitted to terminate at an exit passageway complying with Section 1023, provided the exit passageway terminates at an exit discharge or a public way. 1022.2.1 Extension. Where an exit enclosure is extended to an exit discharge or a public way by an exit passageway, the exit enclosure shall be separated from the exit passageway by a fire barrier constructed in accordance with Section 707 of the International Building Code or a horizontal assembly constructed in accordance with Section 712 of the International Building Code, or both. The fire-resistance rating shall be at least equal to that required for the exit enclosure. A fire door assembly complying with Section 715.4 of the International Building Code shall be installed in the fire barrier to provide a means of egress from the exit enclosure to the exit passageway. Openings in the fire barrier other than the fire door assembly are prohibited. Penetrations of the fire barrier are prohibited. Exception s : 1. Penetrations of the fire barrier in accordance with Section 1022.4 shall be permitted. 2. A fire barrier and fire door assembly are not required to separate an exit passageway from a pressurized stairway.
1022.3 Openings (( Openings in exit enclosures other than unprotected exterior openings shall be limited to those necessary for exit access to the enclosure from normally occupied spaces and for egress from the enclosure. Elevators shall not open into an exit enclosure. Interpretation I1022.3: Accessory rooms such as restrooms, storage closets, laundry rooms, electrical, communication closets and similar spaces shall not open into an exit enclosure. 1022.4 Penetrations. Penetrations into and openings through an exit enclosure are prohibited except for the following: 1. required exit doors, 2. equipment and ductwork necessary for independent ventilation or pressurization, 3. sprinkler piping, standpipes, 4. electrical raceway for fire department communication systems and sprinkler monitoring terminating at a steel box not exceeding 16 square inches (0.010 m2), 5. electrical raceway serving the exit enclosure and terminating at a steel box not exceeding 16 square inches (0.010 m2) 6. piping used exclusively for the drainage of rainfall runoff from roof areas, provided the roof is not used for a helistop or heliport. 7. Unfired unit heaters required for freeze protection of fire protection equipment are permitted to penetrate one membrane; the conduit serving the heater is permitted to penetrate both membranes. 8. Equipment necessary for electrically-controlled stairway door locks and security cameras are permitted to penetrate one membrane; the conduit serving the equipment is permitted to penetrate both membranes. Such penetrations shall be protected in accordance with Section 713 of the International Building Code. There shall be no penetrations or communication openings, whether protected or not, between adjacent exit enclosures. Interpretation I1022.4: Ducts passing through exit enclosures shall be separated from the enclosure by construction having a fire-resistance rating at least equal to the exit enclosure walls. At least one side of the duct enclosure shall about the exit enclosure. ***
1022.8 Floor identification signs. A sign shall be provided at each floor landing in exit enclosures connecting more than three stories designating the floor level, the terminus of the top and bottom of the exit enclosure and the identification of the
stair or ramp. The signage shall also state the story of, and the direction to, the exit discharge , (( 1022.8.1 Signage requirements. Stairway identification signs shall comply with all of the following requirements: 1. The signs shall be a minimum size of 18 inches (457 mm) by 12 inches (305 mm). 2. The letters designating the identification of the stair enclosure shall be a minimum of 11/2 inches (38 mm) in height. 3. The number designating the floor level shall be a minimum of 5 inches (127 mm) in height and located in the center of the sign. 4. All other lettering and numbers shall be a minimum of 1 inch (25 mm) in height. 5. Characters and their background shall have a nonglare finish. Characters shall contrast with their background, with either light characters on a dark background or dark characters on a light background. 6. When signs required by Section 1022.8 are installed in interior exit enclosures of buildings subject to Section 1024, the signs shall be made of the same materials as required by Section 1024.4.
1022.9 ((
1022.9.1 Termination and extension. A ((
Exception((
((
((
1022.10 Equipment in exit enclosures. Equipment is prohibited in exit enclosures except for equipment necessary for independent pressurization, lighting of the exit enclosure, sprinkler piping, standpipes, electrical equipment for fire department communication and sprinkler monitoring, and unit heaters required to protect fire protection equipment from freezing. SECTION 1023 EXIT PASSAGEWAYS 1023.1 Exit passageway. Exit passageways serving as an exit component in a means of egress system shall comply with the requirements of this section. An exit passageway shall not be used for any purpose other than as a means of egress , circulation and access . *** 1023.5 Openings and penetrations. Exit passageway opening protectives shall be in accordance with the requirements of Section 715 of the International Building Code. Except as permitted in Section 402.4.6 of the International Building Code, openings in exit passageways other than exterior openings shall be limited to those necessary for exit access to the exit passageway from normally occupied spaces and for egress from the exit passageway. Where an exit enclosure is extended to an exit discharge or a public way by an exit passageway, the exit passageway shall also comply with Section 1022.2.1. Elevators shall not open into an exit passageway. Interpretation I1023.5: Accessory rooms such as restrooms, storage closets, laundry rooms, electrical, communication closets and similar spaces shall not open into exit passageways. Code Alternate CA1023.5: An elevator is permitted to open into an exit passageway when the following conditions are met: 1. A lobby shall separate the elevator from the exit passageway. This is allowed at only one location in the building. The lobby is required whether the elevator hoistway is pressurized or not. 2. The separation shall be constructed as a fire barrier having a fire-resistive rating and opening protectives as for the exit passageway. The door between the lobby and the exit passageway shall also comply with Section 715.4.3. The door shall have listed gaskets installed at head, jambs and meeting edges. This only applies to the walls common with the exit passageway. 3. The lobby shall have a minimum depth of 36 inches. (Note that areas of refuge may require a larger dimension). 4. An elevator lobby constructed as a smoke partition shall be provided at every floor below the level of the exit passageway served by the elevator. Hoistway pressurization is permitted to be used in lieu of the lobbies on floors below the level of the exit passageway. 5. A door as required by Section 1022.2.1 between an exit enclosure and the exit passageway shall be provided. 6. An automatic sprinkler system in accordance with Section 903.3.1.1 shall be provided throughout the floor on which the exit passageway is located. This alternate does not apply to vertical exit enclosures. 1023.6 Penetrations. Penetrations into and openings through an exit passageway are prohibited except for required exit doors, equipment and ductwork necessary for independent pressurization, sprinkler piping, standpipes, electrical raceway for fire department communication and electrical raceway serving the exit passageway and terminating at a steel box not exceeding 16 square inches (0.010m2). Such penetrations shall be protected in accordance with Section 713 of the International Building Code. There shall be no penetrations or communicating openings, whether protected or not, between adjacent exit passageways. Exception: Unfired unit heaters allowed by Section 1022.10 to be installed in exit enclosures are permitted to penetrate one membrane. The conduit serving the heater is permitted to penetrate both membranes. *** SECTION 1026 EXTERIOR EXIT RAMPS AND STAIRWAYS ***
1026.3 Open side. Exterior exit ramps and stairways serving as an element of a required means of egress shall be at least 50 percent open on at least one side. An open side shall have a minimum of (( *** SECTION 1027 EXIT DISCHARGE 1027.1 General. Exits shall discharge directly to the exterior of the building. The exit discharge shall be at grade or shall provide direct access to grade. The exit discharge shall not reenter a building except into an exit or as otherwise approved by the building official . The combined use of Exceptions 1 and 2 below shall not exceed 50 percent of the number and capacity of the required exits. Exceptions: 1. A maximum of 50 percent of the number and capacity of the exit enclosures is permitted to egress through areas on the level of discharge provided all of the following are met: 1.1. Such exit enclosures egress to a free and unobstructed path of travel to an exterior exit door and such exit is readily visible and identifiable from the point of termination of the exit enclosure. 1.2. The entire area of the level of exit discharge is separated from areas below by construction conforming to the fire-resistance rating for the exit enclosure. 1.3. The egress path from the exit enclosure on the level of exit discharge is protected throughout by an approved automatic sprinkler system. All portions of the level of exit discharge with access to the egress path shall either be protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, or separated from the egress path in accordance with the requirements for the enclosure of exits. 2. A maximum of 50 percent of the number and capacity of the exit enclosures is permitted to egress through a vestibule provided all of the following are met: 2.1. The entire area of the vestibule is separated from areas below by construction conforming to the fire-resistance rating for the exit enclosure. 2.2. The depth from the exterior of the building is not greater than 10 feet (3048 mm) and the length is not greater than 30 feet (9144 mm). 2.3. The area is separated from the remainder of the level of exit discharge by construction providing protection at least the equivalent of approved wired glass in steel frames. 2.4. The area is used only for means of egress and exits directly to the outside. 3. Stairways in open parking garages complying with Section 1022.1, Exception 4, are permitted to egress through the open parking garage at their levels of exit discharge. 4. Horizontal exits complying with Section 1025 shall not be required to discharge directly to the exterior of the building. *** 1027.5 Egress courts. Egress courts serving as a portion of the exit discharge in the means of egress system shall comply with the requirements of Section 1027. 1027.5.1 Width. The width of egress courts shall be determined as specified in Section 1005.1, but such width shall not be less than 44 inches (1118 mm), except as specified herein. Egress courts serving Group R-3 and U occupancies shall not be less than 36 inches (914 mm) in width. The required width of egress courts shall be unobstructed to a height of 7 feet (2134 mm). Exception: Doors complying with Section 1005.2. Where an egress court exceeds the minimum required width and the width of such egress court is then reduced along the path of exit travel, the reduction in width shall be gradual. The transition in width shall be affected by a guard not less than 36 inches (914 mm) in height and shall not create an angle of more than 30 degrees (0.52 rad) with respect to the axis of the egress court along the path of egress travel. In no case shall the width of the egress court be less than the required minimum. 1027.5.2 Construction and openings. Where an egress court serving a building or portion thereof is less than 10 feet (3048 mm) in width, the egress court walls shall have not less than 1-hour fire-resistance-rated construction for a distance of 10 feet (3048 mm) above the floor of the court. Openings within such walls shall be protected by opening protectives having a fire protection rating of not less than 3/4 hour. Exceptions: 1. Egress courts serving an occupant load of less than 10. 2. Egress courts serving Group R-3. 3. In buildings other than those which have a single means of egress under Section 1021.2.1 item 3, opening protection need not be provided where it is possible to exit in two directions from the court. *** SECTION 1028 ASSEMBLY *** 1028.13 Handrails. Ramped aisles having a slope exceeding one unit vertical in 15 units horizontal (6.7-percent slope) and aisle stairs shall be provided with handrails located either at the side or within the aisle width. Exceptions: 1. Handrails are not required for ramped aisles having a gradient no greater than one unit vertical in eight units horizontal (12.5-percent slope) and seating on both sides. 2. Handrails are not required if, at the side of the aisle, there is a guard that complies with the graspability requirements of handrails. 3. Handrail extensions are not required at the top and bottom of aisle stairs and aisle ramp runs to permit crossovers within the aisles. 1028.13.1 Discontinuous handrails. Where there is seating on both sides of the aisle, the handrails shall be discontinuous with gaps or breaks at intervals not exceeding five rows to facilitate access to seating and to permit crossing from one side of the aisle to the other. These gaps or breaks shall have a clear width of at least 22 inches (559 mm) and not greater than 36 inches (914 mm), measured horizontally, and the handrail shall have rounded terminations or bends.
(( *** Section 12. Chapter 12 of the 2009 International Fire Code is amended as follows: *** 1207.3 Solvent storage tanks. Solvent storage tanks for Class II, IIIA and IIIB liquids shall conform to the requirements of Chapter 34 and be located underground or outside, above ground.
Exception s : 1. As provided in NFPA 32 for inside storage o 2. Solvent tanks located within approved rooms or buildings in accordance with Section 3405.3.7 for use, mixing and dispensing of flammable and combustible liquids. *** Section 13. Chapter 13 of the 2009 International Fire Code is amended as follows: *** 1303.1.1 Static accumulation. If processes or conditions exist where combustible dust could be ignited by static electricity, means shall be provided to prevent the accumulation of a static charge. *** 1303.3 Dust collection equipment and interlocks. Suitable dust-collecting equipment shall be installed on all dust producing machinery and interlocked with the machinery power supply so that the machinery cannot be operated without the dust-collection equipment also operating. [M] 1303.4 Model shops and other intermittent use facilities. Equipment or machinery located inside buildings that emit dust but are used on an intermittent basis, including, but not limited to, model shops, research and development facilities, hobby, and other non-production uses, shall be provided with a local, point of use dust collection system. The dust collector can be a portable type with high efficiency filters to allow exhaust air to be discharged back into the space. Such collectors are not required to be provided with an approved explosion-control system. Such systems shall be limited to no more than 1,000 cfm. *** Section 14. Chapter 14 of the 2009 International Fire Code is amended as follows: CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration or demolition, including those in underground locations. Compliance with NFPA 241 is required for items not specifically addressed herein. Construction, alteration and demolition of fixed guideway transit and passenger rail systems tunnels shall comply with NFPA 130 as amended and WAC 296-155, Part Q, underground Construction. 1401.1.1 Point of Information Adopted local amendments to NFPA 130 can be accessed at http://www.seattle.gov/fire/FMO/firecode/nfpaAmendments.htm Construction, alteration and demolition of road tunnels shall comply shall comply with NFPA 502 as amended and WAC 296-155, Part Q, Underground Construction. 1401.1.2 Point of Information Adopted local amendments to NFPA 502 can be accessed at http://www.seattle.gov/fire/FMO/firecode/nfpaAmendments.htm *** 1404.5 Fire watch. Fire watch for buildings under construction or alteration shall be provided in accordance with the Administrative Rule 9.06.07, Out-Of-Service Fire Alarm, Standpipe, Fire Sprinkler and Emergency Alarm Systems and any future revisions of this rule adopted by the fire code official. When required by the fire code official for building demolition that is hazardous in nature, qualified personnel shall be provided to serve as an on-site fire watch. Fire watch personnel shall be provided with at least one approved means for notification of the fire department and their sole duty shall be to perform constant patrols and watch for the occurrence of fire.
1404.6 (( *** [B] 1411.3 Stairway floor number signs. Temporary stairway floor number signs shall be provided in accordance with the requirements of Section 1022.8.1. ***
1413.1 Where required. In buildings required to have standpipes by Section 905.3.1, not less than one Class I standpipe shall be provided , in accordance with Section 905, for use during construction. Such standpipes shall be installed
when the progress of construction is not more than 40 feet (12 192 mm) in height above the lowest level of fire department (( *** 1414.1 Completion before occupancy. In buildings where an automatic sprinkler system is required by this code or the International Building Code, it shall be unlawful to occupy any portion of a building or structure until the automatic sprinkler system installation has been tested and approved, except as provided in Section 105.3.4 , and Administrative Rule 9.07.07, Partial/Phased Occupancy, Occupancy During Construction and Temporary Certificates of Occupancy and any future revisions of this rule adopted by the fire code official . Section 15. Chapter 15 of the 2009 International Fire Code is amended as follows: *** 1501.2 Nonapplicability. This chapter shall not apply to :
1. S (( 1. 1 Liquids that have no fire point when tested in accordance with ASTM D 92.
1. 2(( 2. Mobile spray coaters registered with, and meeting the requirements of, the Puget Sound Clean Air Agency. 1501.2 Point of Information Details relating to the Puget Sound Clean Air Agency's (PSCAA) rules and requirements can be obtained online at: www.pscleanair.org/regulated/mobilespraycoaters/assistance.asp x or by contacting PSCAA at (206) 434-8800. *** 1504.2 Location of spray-finishing operations. Spray finishing operations conducted in buildings used for Group A, E, I or R occupancies shall be located in a spray room protected with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 and separated vertically and horizontally from other areas in accordance with the International Building Code. In other occupancies, sprayfinishing operations shall be conducted in a spray room, spray booth or spraying space approved for such use. Exceptions: 1. Automobile undercoating spray operations and spray-on automotive lining operations conducted in areas with approved natural or mechanical ventilation shall be exempt from the provisions of Section 1504 when approved and where utilizing Class IIIA or IIIB combustible liquids. 2. In buildings other than Group A, E, I or R occupancies, approved limited spraying space in accordance with Section 1504.9. 3. Resin application areas used for manufacturing of reinforced plastics complying with Section 1509 shall not be required to be located in a spray room, spray booth or spraying space. Spray-finishing operations are allowed in basements only if confined to either an approved spray booth or an approved spray room protected by an approved automatic fire sprinkler system and if such basement is protected throughout by an approved automatic sprinkler system in accordance with Chapter 9. ***
1504.7.8.5 Filter disposal. Discarded filter pads shall be immediately (( *** 1504.9 Limited spraying spaces. Limited spraying spaces shall comply with Sections 1504.9.1 through 1504.9.4. Limited spraying spaces are prohibited if they are used as the exclusive location for spray finishing operations and auto refinishing and collision repair are the primary business. 1504.9.1 Job size. The aggregate surface area to be sprayed shall not exceed 9 square feet (0.84 m2). 1504.9.2 Frequency. Spraying operations shall not be of a continuous nature. 1504.9.3 Ventilation. Positive mechanical ventilation providing a minimum of six complete air changes per hour shall be installed. Such system shall meet the requirements of this code for handling flammable vapor areas. Explosion venting is not required. Exception: Negative mechanical ventilation, providing a minimum of six complete air changes per hour, is allowed if a fan rated for Class I, Division 2 hazardous locations in accordance with the Electrical Code is installed. 1504.9.4 Electrical wiring and equipment . Electrical wiring and equipment within 10 feet (3048 mm) of the floor and 20 feet (6096 mm) horizontally of the limited spraying space shall be designed for Class I, Division 2 locations in accordance with NFPA 70. *** Section 16. Chapter 17 of the 2009 International Fire Code is amended as follows: *** 1703.2.1 Electricity. Electricity shall be shut off. Exception: Circulating fans that have been specifically designed for utilization in hazardous atmospheres and installed in accordance with NFPA 70 and temporary remote control power leads with control switches located outside the fumigant space for powering such fans . *** Section 17. Chapter 21 of the 2009 International Fire Code is amended as follows: CHAPTER 21
(( SECTION 2101 GENERAL
2101.1 Scope. This chapter shall apply to the installation and operation of Class A, Class B, and Class C (( *** 2102.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. FURNACE CLASS A. An oven or furnace that has heat utilization equipment operating at approximately atmospheric pressure wherein there is a potential explosion or fire hazard that could be occasioned by the presence of flammable volatiles or combustible materials processed or heated in the furnace. 2102.1.1 Point of Information
(( 1. Paints, powders, inks, and adhesives from finishing processes, such as dipped, coated, sprayed and impregnated materials. 2. The substrate material. 3. Wood, paper and plastic pallets, spacers or packaging materials. 4. Polymerization or other molecular rearrangements. Potentially flammable materials, such as quench oil, waterborne finishes, cooling oil or cooking oils that present a hazard are ventilated according to Class A standards. FURNACE CLASS B. An oven or furnace that has heat utilization equipment operating at approximately atmospheric pressure wherein there are no flammable volatiles or combustible materials being heated. FURNACE CLASS C. An oven or furnace that has a potential hazard due to a flammable or other special atmosphere being used for treatment of material in process. 2101.1.2 Point of Information This type of furnace can use any type of heating system and includes a special atmosphere supply system. Also included in the Class C classification are integral quench furnaces and molten salt bath furnaces . FURNACE CLASS D. An oven or furnace that is a pressure vessel that operates under vacuum for all or part of the process cycle, operates at temperatures from above ambient to over 5,000 degrees F (2760 degrees C) and at pressures normally below atmospheric using any type of heating system. These furnaces can include the use of special processing atmospheres. 2101.1.3 Point of Information Class D furnaces operate at or below atmospheric pressure (vacuum) and do not fall into the jurisdiction of the Boiler and Pressure Vessel Code. ***
2103.1 Ventilation. Enclosed rooms or basements containing (( ***
2103.3 Ignition source. (( *** SECTION 2104 FUEL PIPING
2104.1 Fuel-gas piping. Fuel-gas piping serving ((
2104.2 Shutoff valves. Each (( *** Section 18. Chapter 22 of the 2009 International Fire Code is amended as follows: CHAPTER 22 MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES SECTION 2201 GENERAL 2201.1 Scope. Automotive motor fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet vehicle motor fuel-dispensing facilities, aircraft motor-vehicle fueldispensing facilities and repair garages shall be in accordance with this chapter and the International Building Code, City of Seattle Source Control Technical Requirements Manual (DPD Director's Rule 15-2009), International Fuel Gas Code and International Mechanical Code. Such operations shall include both those that are accessible to the public and private operations. 2201.1 Point of Information For provisions relating to the transfer of flammable and combustible liquids directly from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, governmental or manufacturing establishments, see Section 3406.5.4.5. *** FIRE DISTRICT. Shall consist of that part of the city within the boundary described in Section 401 of the Seattle Building Code as follows: Beginning at the intersection of the center line of Alaskan Way and Clay Street; thence northeasterly along the center line of Clay Street to an intersection with the center line of Denny Way; thence easterly along the center line of Denny Way to an intersection with the center line of Yale Avenue; thence southeasterly along the center line of Yale Avenue to an intersection with the center line of Interstate Highway 5; thence southerly and southeasterly along the center line of Interstate 5 to an intersection with the center line of 7th Avenue South; thence southerly along the center line of 7th Avenue South to an intersection with the center line of Dearborn Street; thence westerly along the center line of Dearborn Street to an intersection with the center line of Airport Way; thence northwesterly along the center line of Airport Way to an intersection with the center line of 4th Avenue South; thence southerly along the center line of 4th Avenue south to an intersection with the center line of South Royal Brougham Way; thence westerly along said center line of South Royal Brougham Way to an intersection with the center line of South Alaskan Way; thence southerly along the center line of South Alaskan Way to an intersection with the center line of South Massachusetts Street; thence westerly along the centerline of South Massachusetts Street to the Outer Harbor Line in Elliott Bay; thence northerly and northwesterly along said Outer Harbor Line to an intersection with the center line of West Harrison Street; thence easterly along the center line of West Harrison Street to an intersection with the center line of Alaskan Way; then southeasterly along the center line of Alaskan Way to the point of beginning. 2202.1.1 Point of Information For a map of the City of Seattle Fire District, see the Seattle Building Code. *** 2202.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. ***
MARINE MOTOR FUEL-DISPENSING FACILITY. That portion of property where flammable or combustible liquids or gases used as fuel for (( 2202.1.2 Point of Information Marine motor fuel-dispensing facilities are not to be confused with marine bulk plants that transfer fuel by way of flange-to-flange connections. Marine motor fuel-dispensing facilities use automotive-type dispensing equipment for fueling primarily pleasure craft. MOTOR VEHICLE Includes, but is not limited to, a vehicle, machine, tractor, trailer or semitrailer, or any combination thereof, propelled or drawn by mechanical power and used upon the highways in the transportation of passengers or property. It does not include a vehicle, locomotive or car operated exclusively on a rail or rails, or a trolley bus operated by electric power derived from a fixed overhead wire, furnishing local passenger transportation similar to street-railway service. The term "motor vehicle" also includes freight containers or cargo tanks used, or intended for use, in connection with motor vehicles. 2202.1.3 Point of Information For reference, see 49 CFR Pt. 171.8 (October 2009). MOTOR VEHICLE, UNATTENDED A motor vehicle in such a condition that the driver cannot see the motor vehicle or hear noises in or near the motor vehicle. Exceptions: 1. Necessary absence in connection with loading and unloading the motor vehicle. 2. Stops for meals during the day or night, if the point of parking is well lighted. 3. If in case of accident or other emergency, the driver must leave to obtain assistance. *** 2203.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations and letters shall not be less than 3 inches (76.2 mm) in height and 1/2 inch (12.7 mm) in stroke . *** 2204.4.1 Approved containers required. Class I, II and IIIA liquids shall not be dispensed into a portable container unless such container does not exceed a 6-gallon (22.7 L) capacity, is listed or of approved material and construction, and has a tight closure with a screwed or spring-loaded cover so designed that the contents can be dispensed with-out spilling. Liquids shall not be dispensed into portable or cargo tanks. It is unlawful to sell, offer for sale or distribute any container for the storage and/or handling of flammable liquids, unless such container has been approved for such purpose under applicable provisions of this code. ***
2205.1 Tank filling operations for Class I, II (( ***
2206.2 Method of storage. Approved methods of storage for Class I, II , (( ***
2206.2.2 Above-ground tanks located inside buildings. Aboveground tanks for the storage of Class I, II , (( Exceptions: 1. Above-ground tanks listed and labeled as protected above-ground tanks containing Class I flammable liquids and having an individual capacity not exceeding 120 gallons (454 L) are not required to be located in special enclosures or in a liquid storage room or warehouse. 2. Above-ground tanks listed and labeled as protected above-ground tanks containing Class II or III-A combustible liquids and having an individual capacity not exceeding 660 gallons (908 L) are not required to be located in special enclosures or in a liquid storage room or warehouse. 3. Aboveground tanks for Class III-B liquids not exceeding a maximum individual capacity of 13,200 in unsprinklered buildings. 4. Aboveground tanks for Class III-B liquids in sprinklered buildings.
2206.2.3 Above-ground tanks located outside, above grade. Above-ground tanks shall not be used for the storage of Class I, II , (( 1. Above-ground tanks used for outside, above-grade storage of Class I liquids shall be listed and labeled as protected above-ground tanks and be in accordance with Chapter 34. Such tanks shall be located in accordance with Table 2206.2.3.
2. Above-ground tanks used for outside , above-grade storage of Class II or IIIA liquids (( 3. Above-ground tanks containing Class I liquids for fueling motor vehicles are prohibited in the fire district. 4. Above-ground tanks containing Class I liquids for fueling motor vehicles are allowed outside the fire district only if located within an industrial [I] zone, as defined in the Seattle Land Use Code.
5. (( Installations with the maximum allowable aggregate capacity shall be separated from other such installations by not less than 100 feet (30 480 mm).
6(( 7. Above-ground tanks used for outside, above-grade storage of Class III-B liquid motor fuels shall be listed and labeled as protected aboveground tanks or listed and labeled in accordance with UL 142, Standard for Steel Aboveground Tanks. 2206.2.4 Above-ground tanks located in above-grade vaults or below-grade vaults. Above-ground tanks used for storage of Class I, II or IIIA liquid motor fuels are allowed to be installed in vaults located above grade or below grade in accordance with Section 3404.2.8 and shall comply with Sections 2206.2.4.1 and 2206.2.4.2. Tanks in above-grade vaults shall also comply with Table 2206.2.3.
2206.2.4.1 Tank capacity limits. Tanks storing Class I liquids are limited to maximum individual capacity of 12,000 gallons (45 420 L) and an aggregate capacity at an individual site of 12,000 gallons (45 420 L). Tanks storing ((
2206.2.4.2 Above-ground tanks located in vaults at ((
2206.2.5 Portable tanks. Where approved by the fire code official, portable tanks are allowed to be temporarily used in conjunction with the dispensing of Class I, II , (( ***
2206.6.2 Piping, valves, fittings and ancillary equipment for above-ground tanks for Class I, II , (( ***
2206.7.6.1 Special requirements for nozzles. Where dispensing of Class I, II,(( 1. The hose nozzle valve shall be equipped with an integral latch-open device. 2. When the flow of product is normally controlled by devices or equipment other than the hose nozzle valve, the hose nozzle valve shall not be capable of being opened unless the delivery hose is pressurized. If pressure to the hose is lost, the nozzle shall close automatically. Exception: Vapor recovery nozzles incorporating insertion interlock devices designed to achieve shutoff on disconnect from the vehicle fill pipe. 3. The hose nozzle shall be designed such that the nozzle is retained in the fill pipe during the filling operation. 4. The system shall include listed equipment with a feature that causes or requires the closing of the hose nozzle valve before the product flow can be resumed or before the hose nozzle valve can be replaced in its normal position in the dispenser. *** 2207.1.1 Prohibited locations. Motor fuel-dispensing facilities for liquefied petroleum gas (LP-gas) fuel are prohibited in the fire district. *** 2209.1.1 Prohibited locations. Hydrogen motor fueldispensing and generation facilities are prohibited in the fire district. *** Section19. Chapter 24 of the 2009 International Fire Code is amended as follows: ***
2403.2 Approval required. Tents and membrane structures having an area in excess of 400 square feet (37 m2) shall not be erected(( Exceptions: 1. Tents used exclusively for recreational camping purposes. 2. Funeral tents and curtains or extensions attached thereto, when used for funeral services.
((
((
((
(( *** 2404.2 Flame propagation performance treatment. Before a permit is granted, the owner or agent shall file with the fire code official a certificate executed by an approved testing laboratory certifying that the tents and membrane structures and their appurtenances; sidewalls, drops and tarpaulins; floor coverings, bunting and combustible decorative materials and effects, including sawdust when used on floors or passageways, are composed of material meeting the flame propagation performance criteria of NFPA 701 or other approved standard, or shall be treated with a flame retardant in an approved manner and meet the flame propagation performance criteria of NFPA 701, and that such flame propagation performance criteria are effective for the period specified by the permit. 2404.2 Point of Information Accepted flame certificates for decorative materials include: 1. Certificates indicating compliance with NFPA 701. 2. Certificates verifying approval through the California State Fire Marshal. 3. Certificates indicating compliance with CPAI-84 (Canvas Products Association International). *** Section 20. Chapter 25 of the 2009 International Fire Code is amended as follows: *** 2505.4 Distance from lot lines and buildings. Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings. Exception: When stored on a single rack having dimensions not exceeding 68 inches by 48 inches by 76 inches (1727 mm by 1219 mm by 1930 mm) for commercial display, the distance to property lines that can be built upon may be reduced to 10 feet (3048 mm) and no separation is required from buildings on the same property. *** Section 21. Chapter 26 of the 2009 International Fire Code is amended as follows: CHAPTER 26 WELDING AND OTHER HOT WORK SECTION 2601 GENERAL 2601.1 Scope. Welding, cutting, open torches and other hot work operations and equipment shall comply with this chapter. Exception: Hot work on board marine vessels at dock or under construction or repair shall be in accordance with Administrative Rules 26.01.09, Cutting, Welding and Other Hot Work on Marine Vessels and 26.02.09 Designated Marine Hot Work Facilities and Shipyards and any future revisions of this rule adopted by the fire code official. ***
2601.5 Design and installation of oxygen-fuel gas systems. (( *** 2602.1 Definitions. The following words and terms shall, for the purposes of this chapter and as used elsewhere in this code, have the meanings shown herein. HOT WORK. Operations including cutting, welding, Thermit welding, brazing, soldering, grinding, thermal spraying, thawing pipe, installation of torch-applied roof systems , glass blowing, weed burning, or any other similar spark, arc or flame-producing activity. *** PF DEVICE. A wet or dry device (or assembly of devices) in a fuel gas line designed to perform the following three functions: (a) Prevent backflow of oxygen into the fuel gas supply system; (b) Prevent the passage of flame into the fuel gas supply system (flashback); (c) Prevent the development of a fuel gas-oxygen mixture at sufficient pressure so that its ignition would achieve combustion pressures that could cause failure to perform functions (a) and (b). This device is given a diagram symbol, PF. A wet PF device is commonly known as a hydraulic seal, hydraulic valve or hydraulic back-pressure valve. *** 2604.2.2 Location. The fire watch shall include the entire hot work area and be positioned so that the extinguishment of a spot fire is not delayed . Hot work conducted in areas with vertical or horizontal fire exposures that are not observable by a single individual shall have additional personnel assigned to fire watches to ensure that exposed areas are monitored.
2604.2.3 Duties. Individuals designated to fire watch duty shall have no other duties except to watch for fire, ((
2604.2.4 Fire extinguishing equipment training. The individuals responsible for performing the hot work and individuals responsible for providing the fire watch shall (( 2604.2.5 Fire hoses. Where hoselines are required, they shall be connected, charged and ready for operation.
2604.2.6 Fire extinguisher. A minimum of one portable fire extinguisher complying with Section 906 and with a minimum (( *** 2605.4 Fuel gases and liquid oxygen. 2605.4.1 Acetylene gas and other nonliquefied flammable gases . 2605.4.1.1 Prohibitions. Acetylene gas shall not be:
1. ((
2. (( 2605.4.1.2 Unalloyed copper. Acetylene gas shall not be brought in contact with unalloyed copper, except in a blowpipe or torch. 2605.4.1.3 Maximum acetylene and other nonliquefied flammable gas quantities inside buildings. The maximum quantity of acetylene and other nonliquefied flammable gas used and stored inside buildings in conjunction with hot work operations shall be in accordance with this section. 2605.4.1.3.1 Group A, B, E, I, M and R occupancies. Acetylene gas and other nonliquefied flammable gas shall not be stored or used in Group A, B, E, I, M or R occupancies. Exceptions: 1. Individual cylinders not exceeding 150 cubic feet (4m3) each at normal temperature and pressure (NTP). Aggregate quantity of flammable gas shall not exceed 1,000 cubic feet (28 m3) in unsprinklered buildings and 2,000 cubic feet (57m3) in sprinklered buildings. 2. Buildings under construction or demolition where individual acetylene gas and other nonliquefied flammable gas cylinders do not exceed 300 cubic feet (8 m3) each at normal temperature and pressure and the aggregate storage quantity inside the building does not exceed 1,000 cubic feet (28 m3). 2605.4.1.3.2 Group F and S occupancies. Acetylene and other nonliquefied flammable gas shall not be stored or used in Group F and S occupancies in excess of the maximum allowable quantities set forth in Table 2703.1.1 (1). 2605.4.1.3.3 Mixed use occupancies. Individual fuel gas cylinders within F or S occupancies in buildings having any other use shall be limited to 250 cubic feet (7 m3) at normal temperature and pressure and shall be limited to a total aggregate gas capacity of 1,000 cubic feet (70.8 m3) at normal temperature and pressure of acetylene or other nonliquefied flammable gas. 2605.4.2 Liquefied petroleum gas (LP-gas) and methylacetylenepropadiene (MAPP gas). 2605.4.2.1 Maximum LP-gas and MAPP gas quantities inside buildings. The maximum quantity of LP-gas and MAPP gas used and stored inside buildings in conjunction with hot work operations shall be in accordance with this section. 2605.4.2.1.1 Group A, B, E, I, M and R occupancies. LP-gas and MAPP shall not be stored or used in Group A, B, E, I, M or R occupancies. Exceptions: 1. A single LP-gas or a single MAPP gas cylinder not exceeding 50-pounds (22.7 kg) water capacity [nominal 20 pounds (9 kg) LP-gas] in Group E and M occupancies. 2. Individual LP-gas or MAPP gas cylinders not exceeding 12-pounds (5.4 kg) water capacity [nominal 5 pounds (2.3 kg) LP-gas] in Group I occupancies. 3. Unoccupied buildings under construction or demolition where individual LP-gas or MAPP gas cylinders do not exceed 240-pounds (109 kg) water capacity [nominal 100 pounds (45.4 kg) LP-gas] and the aggregate quantity inside the building does not exceed an aggregate water capacity of 735 pounds (333.4 kg) [nominal 300 pounds (136 kg) LP-gas] on the site. 4. Occupied buildings under construction or demolition where individual LP-gas or MAPP gas cylinders do not exceed 104-pounds (47 kg) water capacity [nominal 43.5 pounds (19.7 kg) LP-gas] and the aggregate quantity inside the building does not exceed 357-pounds (162 kg) water capacity [nominal 150 pounds (68 kg) LP-gas]. 5. Approved self-contained torch assemblies fueled by LP-gas containers having an individual water capacity not exceeding 2.7 pounds (1.2 kg). 2605.4.2.1.2 Group F and S occupancies. LP-gas and MAPP gas shall not be stored or used in excess of 735 pounds (333.4 kg) aggregate water capacity [nominal 300 pounds (136 kg) LP-gas] in Group F and S occupancies. 2605.4.2.1.3 Mixed use occupancies. LP-gas and MAPP gas storage and use inside Group F and S occupancies within buildings having any other use shall be limited to cylinders having an individual water capacity not exceeding 50 pounds (22.7 kg) [nominal 20 pounds (9 kg) LP-gas] and a total aggregate water capacity not to exceed 144 pounds (65 kg) [nominal 60 pounds (27 kg) LP-gas]. 2605.4.3 Liquid oxygen (LOX). Liquid oxygen shall not be stored or used in an unsprinklered building in an aggregate quantity exceeding 45 gallons (170 L) per control area or an aggregate quantity of 90 gallons (340 L) per control area in a sprinklered building. 2605.4.4 Separation of cylinders in storage. Fuel gas cylinders shall be separated from compressed oxygen cylinders and liquid oxygen containers by a minimum of 20 feet (6096 mm) or by a barrier of noncombustible construction at least 5 feet (1524 mm) high having a fire-resistive rating of at least 1/2 hour. The barrier shall interrupt all lines of sight between oxygen and fuel gas cylinders within 20 feet (6096 mm) of each other. 2605.5 Remote locations. Oxygen and fuel-gas cylinders and acetylene generators shall be located away from the hot work area to prevent such cylinders or generators from being heated by radiation from heated materials, sparks or slag, or misdirection of the torch flame.
2605.6 Cylinders shutoff. The torch valve shall be closed and the gas supply to the torch completely shut off when gas (( *** 2609.8 PF devices. PF devices shall be designed and installed in fuel gas lines in accordance with NFPA 51. Section 22. Chapter 27 of the 2009 International Fire Code is amended as follows: CHAPTER 27 HAZARDOUS MATERIALS---GENERAL PROVISIONS SECTION 2701 GENERAL 2701.1 Scope. Prevention, control and mitigation of dangerous conditions related to storage, dispensing, use and handling of hazardous materials and notification of biosafety level 3 and biosafety level 4 operations shall be in accordance with this chapter. This chapter shall apply to all hazardous materials, including those materials regulated elsewhere in this code, except that when specific requirements are provided in other chapters, those specific requirements shall apply in accordance with the applicable chapter. Where a material has multiple hazards, all hazards shall be addressed. Exceptions: 1. The quantities of alcoholic beverages, medicines, foodstuffs, cosmetics and consumer or industrial products containing not more than 50 percent by volume of watermiscible liquids and with the remainder of the solutions not being flammable, in retail or wholesale sales occupancies, are unlimited when packaged in individual containers not exceeding 1.3 gallons (5 L). 2. Application and release of pesticide and agricultural products and materials intended for use in weed abatement, erosion control, soil amendment or similar applications when applied in accordance with the manufacturers' instructions and label directions. 3. The off-site transportation of hazardous materials when in accordance with Department of Transportation (DOTn) regulations. 4. Building materials not otherwise regulated by this code. 5. Refrigeration systems (see Section 606). 6. Stationary storage battery systems regulated by Section 608. 7. The display, storage, sale or use of fireworks and explosives in accordance with Chapter 33. 8. cryogenics utilized in personal and household products in the manufacturers' original consumer packaging in Group M occupancies. 9. The storage of distilled spirits and wines in wooden barrels and casks. 10. The use of wall-mounted dispensers containing alcohol-based hand rubs classified as Class I or II liquids when in accordance with Section 3405.5. 11. Hazardous materials handled at marine terminals in accordance with Section 2701.1.2.
2701.1.1Waiver. The provisions of this chapter are waived when the fire code official determines that such enforcement is preempted by other codes, statutes or ordinances. The details of any action granting such a waiver shall be recorded and entered in
the files of the (( 2701.1.2 Hazardous materials at marine terminals. Hazardous materials that are handled and temporarily located at marine terminals and are incidental to transportation shall be in accordance with the Administrative Rule 27.01.09, Marine Terminals and any future revisions of this rule adopted by the fire code official. 2701.1.3 Underground storage tanks. Pursuant to Section 106.5.1, the fire code official approves permits to install underground tanks issued by and inspections of underground tanks conducted by the Washington State Department of Ecology. ***
2701.5.2 Hazardous Materials Inventory Statement (HMIS). Where required by the fire code official, (( 1. Product name. 2. Component. 3. Chemical Abstract Service (CAS) number. 4. Location where stored or used. 5. Container size. 6. Hazard classification. 7. Amount in storage. 8. Amount in use-closed systems. 9. Amount in use-open systems. 2701.5.2 Point of Information Prior to developing a HMIS, please contact the Special Hazards Unit of the Fire Prevention Division for specific guidelines, format and assistance. *** 2701.6.1 Temporarily out-of-service facilities. Facilities that are temporarily out of service shall continue to maintain a permit and be monitored and inspected. Facilities for which a closure plan is required in accordance with Section 2701.5 shall notify the fire code official when the facility out-of-service period exceeds 15 days. *** | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||